Motor starting time calculation: torque margin and inertia

Motors and motor starters Published 7 min read

Short answer

Starting time equals combined motor-plus-load inertia times the speed change, divided by average net accelerating torque: for the 585 kW, 2975 rpm pump case that works out near 7 s, so a reported 15 s points to an input error first. On the larger machine, confirm the rating is 2950 kW and not MW before using any reported current, torque or voltage-drop number.

On this page
  1. The formula and where each term comes from
  2. Why inertia dominates the duration
  3. Worked example: 585 kW pump motor, 21.25 kg·m² combined inertia
  4. What the reported results can and cannot establish
  5. What to collect before trusting the calculation
  6. Accepting the start: limits and commissioning checks
  7. Questions asked

A motor accelerates only while its torque exceeds the load's, and the starting time follows from what is left over: t = J·Δω / T_acc, where J is the combined motor-and-load inertia, Δω the speed change and T_acc the average net accelerating torque. Inertia, not locked-rotor torque, dominates the duration, and the two reported 11 kV cases show it: the smaller pump machine carries 21.25 kg·m² combined against 66 kg·m² on the larger one. That ratio, more than the torque ratings, is what separates a few seconds of acceleration from tens of seconds — and what makes the reported 15 s pump result and the reported 3.47 s start with 6% voltage drop worth rebuilding before either is trusted.

The formula and where each term comes from #

The exact duration is the integral of J·ω / T_net(ω) dω from standstill to full speed, because both the motor torque and the load torque change with speed. The constant-torque form, t = J·Δω / T_acc, is the working estimate: it is correct to within the accuracy of the average net torque you feed it. Work in kg·m² for inertia, rad/s for angular speed and N·m for torque, and the result comes out in seconds.

Δω runs from zero to the speed the motor settles at under load, just below synchronous because of slip. On a 50 Hz machine at roughly 2975 to 2990 rpm rated, use the rated speed. The net torque is the motor's torque-speed curve minus the driven equipment's curve at the same speed, both read at the actual starting condition: valve position, static head, driven gas or fluid state. The motor curve comes from the manufacturer; the load curve comes from the driven-equipment maker. A single locked-rotor torque figure is the value at zero speed only and does not describe the curve through the rest of the ramp.

Why inertia dominates the duration #

Rearranging the formula shows the sensitivity: double the combined inertia and the start takes twice as long, even with identical torque. The larger reported machine — the one whose rating is written 2950 MW and is almost certainly 2950 kW — carries 60 kg·m² of motor inertia plus 6 kg·m² of load, and starts with a locked-rotor torque of 0.47 of rated. The pump machine carries less than half that inertia and starts with 0.6 of rated. More inertia and less torque margin pull the same physics in opposite directions from what the locked-rotor figures alone suggest.

Two practical traps sit alongside the physics. First, the curves may pinch: if the motor torque dips toward the load curve somewhere mid-range, the acceleration slows sharply there even when the locked-rotor point looks strong. Second, the inertia convention matters: some vendors publish direct moment of inertia J, others publish flywheel effect GD² or WK², and entering one where the calculation expects the other moves the answer by a factor of four. Confirm the convention of both the data sheet and the calculation tool before trusting any duration.

Worked example: 585 kW pump motor, 21.25 kg·m² combined inertia #

Inputs, all from the reported pump case: an 11 kV motor rated 585 kW at 2975 rpm; motor inertia 16.25 kg·m² and load inertia 5 kg·m², taken as direct J pending confirmation of the convention; locked-rotor torque 0.6 of rated, used only as a zero-speed reference.

The rule: starting time equals combined inertia times the speed change, divided by average net accelerating torque.

The arithmetic:

  1. Speed change to rated: Δω = 2π × 2975 / 60 = 311.7 rad/s.
  2. Rated torque: T_N = 585,000 W ÷ 311.7 rad/s = 1,877 N·m.
  3. Average net accelerating torque: with a centrifugal pump started against a closed discharge valve, load torque near zero speed is small and the motor curve sits well above the load through most of the ramp, so take 0.5 × 1,877 = 938 N·m as a declared assumption — the true average comes from the two curves.
  4. Combined inertia: J = 16.25 + 5 = 21.25 kg·m².
  5. Starting time: t = 21.25 × 311.7 ÷ 938 = 7.1 s.

The decision: a correct dynamics study for this machine should land on the order of 7 s. The reported 15 s is more than double that estimate, which points to an input problem before it points to physics. Check whether the inertia was entered under the flywheel-effect convention instead of direct J, whether the load curve was taken with the discharge valve open or against static head, and whether the motor curve belongs to this machine. If every input verifies and the two curves genuinely pinch mid-range, then the long duration is real and the thermal and protection checks below govern. This is an estimate built on an assumed average torque; confirm it against the curves and the governing documentation before it drives any setting.

What the reported results can and cannot establish #

Reported figure What it is What it does not give you
3.47 s start, 6% voltage drop A dynamics-software result for one model run of the larger machine Not a verified starting limit; it stands only while every input behind it is confirmed
Rating written 2950 MW The data as reported Almost certainly 2950 kW from the nameplate; the two differ by a factor of 1,000 in every downstream current and torque number
6.2 × rated current, 20% starting power factor, 0.47 × rated locked torque Zero-speed points on the current and torque curves Neither the current nor the torque behaviour through acceleration
60 kg·m² motor and 6 kg·m² load inertias Inertias as reported Whether they are direct J or flywheel effect GD²/WK²
11 kV, 50 kA, 3 s switchgear rating Short-circuit withstand of the gear Not a permissible start duration and not a thermal allowance for the motor

What to collect before trusting the calculation #

  • Motor nameplate: power, voltage, rated speed, rated current, and the locked-rotor data that goes with it.
  • Motor torque-versus-speed and current-versus-speed curves from the manufacturer.
  • Driven-load torque curve from the equipment maker, at the real starting condition — valve position and static head included.
  • Motor and load inertias, with their convention stated explicitly.
  • Transformer impedance from the test report: the reported case names a 60 MVA, 132/11 kV unit but no impedance, and a power rating alone cannot produce a voltage-drop result.
  • Feeder cable length, size and impedance from the cable schedule.
  • Existing load with its power factor: 7.9 MW on the 11 kV bus gives no pre-start current until the power factor is stated.

The voltage side of this same start is its own calculation: dip magnitude depends on the locked-rotor current and the source impedance, not on how long the start lasts. The motor starting voltage dip calculation on an 11 kV bus works that side, and estimating voltage sag from motor inrush current gives the quick sag check from inrush alone. A start can hold a modest dip for many seconds and still be unacceptable on thermal grounds.

Accepting the start: limits and commissioning checks #

Accept a start only when all three hold. First, net torque stays positive through the whole speed range, checked from the two curves at the actual starting condition. Second, motor-terminal voltage during the start stays within the limits the motor and driven-equipment documentation set. Third, starting current and duration sit inside the motor's permitted starting duty and the protection curves; the 50 kA, 3 s rating of the switchgear is short-circuit withstand and says nothing about how long the machine may sit at starting current. Restart intervals come from the motor manufacturer's starting-duty data, not from the gear.

At commissioning, record acceleration time, motor-terminal voltage and current, and any protection events, then compare them with the study at equivalent conditions. A start longer than modeled points to a different network condition, a wrong inertia or load curve, or a mechanical mismatch on the driven side — each is an input error to chase, not a reason to widen the protection setting.

One safety note before any of those measurements: opening the switchgear or the motor terminal box means de-energizing first, locking out, and verifying absence of voltage with a tested instrument. NFPA 70E, the standard for electrical safety in the workplace, 2024 edition, covers those safe work practices; confirm the applicable requirements with the local authority having jurisdiction and the equipment documentation.

Questions asked

The software asks for GD squared — how does that convert to inertia?

Flywheel effect GD² expressed in kgf·m² equals four times the moment of inertia J in kg·m², so divide the GD² figure by four before entering it as J. Check the manual for which convention it expects: entering GD² as if it were J inflates the inertia fourfold and stretches the calculated start time by the same factor.

Does a soft starter change the starting time?

Yes, usually to a longer value. Reducing voltage at the motor terminals cuts motor torque roughly with the square of the voltage, so a reduced-voltage start leaves less net torque to accelerate the same inertia. Recalculate with the reduced-voltage torque curve for the actual starter ramp, not the full-voltage curve.

Why does the voltage drop not depend on how long the start takes?

Dip magnitude is set by the starting current and the source impedance between the supply and the measurement point: transformer impedance and feeder cable dominate it. A long start at moderate current can hold a small steady dip while still overheating the motor, so duration is a thermal and protection question, not a dip-magnitude one.

What makes a motor stall partway through a start?

Net accelerating torque crossing zero where the motor and load curves come closest. If the load torque rises into the motor curve — a jammed impeller, or a pump started against an open valve and high static head — acceleration stops and the motor holds near locked-rotor current. Check the curve intersection, not only the locked-rotor point.

How soon can a motor be restarted after a start?

Read the permitted starting duty and restart interval from the motor manufacturer's data. Heat from a start stays in the rotor bars and stator windings after the machine is up to speed, so a second start before it cools can exceed its thermal capability. The switchgear's short-time current rating says nothing about the motor's thermal state.

Keep reading

  • How-to

    Estimating voltage sag from motor inrush current

    Do not divide the motor's asymmetrical first-cycle peak by √2; screen the dip with RMS locked-rotor current as dip % = transformer Z% × I_start ÷ I_rated. On a 750 kVA, 480 V, 6% transformer, a 50 HP motor at 395 A locked-rotor dips the bus about 2.6%, to roughly 467 V — start it across the line.

    Motors and motor starters

  • Troubleshooting

    Why a single phase motor stalls on start at 200 V

    The motor stalls because 200 V at its terminals leaves about 69% of rated starting torque — torque varies with the square of voltage — and the primed pump needs more than that. Recover the margin by starting against a throttled discharge, cutting the 20 V feeder drop with a step-up/step-down transformer pair, or converting to a three-phase motor and a drive sized for single-phase input.

    Motors and motor starters

  • Selection guide

    Setting overload relays for high-inertia motor starts

    Set the current dial at the motor's nameplate full-load current and buy starting time with the trip class, not with a higher setting: Class 10 holds starts up to about 7 s at 600 percent, Class 20 to about 14 s, Class 30 to about 21 s. Longer starts need reduced-current starting, not a bigger relay.

    Motors and motor starters