Power quality and harmonics Published 7 min read

Short answer

Trace and clear every ground-path current to a clean baseline before energizing power factor correction capacitors. Going from a 0.71 to a 0.85 power factor takes about 0.372 kvar per kilowatt of measured load, but capacitors only move reactive current: they neither find nor fix the insulation fault or stray neutral-to-ground bond still carrying the unexplained 20 A.

On this page
  1. Why capacitors cannot fix a ground-path current
  2. What a steady ground current can be
  3. Trace every remaining ampere to an owner
  4. What the correction math gives you
  5. The order that protects both projects
  6. Questions asked

Repair the ground path before you energize any correction capacitor. The var math for a stepwise improvement from 0.71 to 0.85 is straightforward and ready when you are, but a capacitor bank only displaces reactive current — it neither finds nor fixes the insulation fault or stray neutral-to-ground bond still carrying the unexplained 20 A in this facility. Energizing the bank first also destroys attribution: after it is in, every ampere measured on the grounding conductor is a blend of old fault, bank leakage and system capacitance, and no later measurement separates them again. Trace the remaining current to an owner, repair it, record a clean baseline, then size and switch in the capacitor steps from measurements taken after the repairs.

Why capacitors cannot fix a ground-path current #

A correction capacitor supplies leading reactive current at the fundamental frequency to cancel the lagging reactive current of an inductive load. A ground-path current is not reactive load: it is current that leaves a phase through an insulation fault, a stray bond or accumulated leakage and returns through grounding conductors and bonded metal. Nothing in the kvar ledger changes the resistance of that path, so correction improves the utility-side power factor while the fault keeps running underneath it.

The bank also changes the thing you are measuring. Every capacitor adds capacitance to ground, and in an ungrounded-wye bank a failed unit with a grounded tank hands the system exactly the phase-to-ground path you are trying to clear. The resonance screening is already done; the missing step is the baseline, because after energization you can no longer tell how much of any ground reading belongs to the bank and how much to the fault.

What a steady ground current can be #

Four mechanisms produce steady current in grounding paths, and more than one can run at once:

  • An insulation fault on a branch, a motor winding or a heater that never draws enough phase current to reach the overcurrent pickup.
  • A neutral-to-ground bond downstream of the service disconnect: neutral load current divides, and part of it returns through grounding conductors, conduit and structural steel instead of the neutral.
  • Accumulated leakage from EMC filters, long cable capacitance and damp or contaminated insulation — many small contributors that sum to a real current.
  • A parallel metallic return path carrying current that belongs to a corroded or broken neutral.

A balanced supply clears none of this: phase currents can read perfectly balanced while a downstream bond or symmetric leakage runs underneath. And the absence of a trip proves nothing here — fuses and breakers respond to phase current, current returning through grounding paths can sit below their pickup forever, and this facility has neither a ground-fault indicator nor a shunt trip able to announce it.

Trace every remaining ampere to an owner #

Before any step that opens a panel, enclosure or load termination: de-energize, lock out and verify the absence of voltage with a meter proven on a known live source. Never open a grounding conductor to measure it while the circuit is energized.

Then work the list:

  1. Confirm the reading before chasing it. Use a true-RMS clamp meter rated above the expected current, zeroed per its instructions, with the jaw closed over the conductor's insulation and other conductors kept away from the measurement point. Repeat upstream and downstream; a reading that changes between two points marks where the current leaves.
  2. Run a residual check per circuit. Clamp all current-carrying conductors of one circuit together — phases plus neutral where present. Outgoing current must return inside the jaw, so any steady reading is escaping through ground, conduit or another parallel path.
  3. Identify the conductor that carries the current. Mark both ends and establish from the one-line diagram and a physical trace whether it serves as an equipment grounding conductor, a grounding electrode conductor, a bonding jumper, conduit, a cable shield or structural steel.
  4. Divide the distribution one level at a time. Measure at the service, then each feeder, then each branch; the level where the reading splits identifies the circuits to open next — the same divide-and-conquer used when locating a ground fault on a resistance-grounded 480 V system.
  5. Open loads through their normal disconnects, one at a time or in small groups, and record the step change after each operation. One large step means a concentrated fault; many small steps mean accumulated leakage or parallel paths. Any kW, kvar or power factor numbers captured during this work are diagnostic only — do not size capacitors from them.
  6. Insulation-test suspect circuits only after they are de-energized and verified dead, with electronics and other test-voltage-sensitive equipment disconnected first. Compare phases and conductors against each other with a megohmmeter rather than against a memorized pass value; the equipment manufacturer's method sets the test voltage and the acceptance basis.
  7. Inspect the usual defects: damaged insulation, moisture and contamination, a neutral-to-ground bond downstream of the service, shared neutrals, a grounded conductor touching an enclosure, and return paths through machine frames.

Keep opening loads until doing so no longer moves the residual reading at the service. Whatever that reading has settled to is the baseline — record it with the date, the operating condition and the instrument, because every post-installation measurement is judged against it.

What the correction math gives you #

Sizing uses the standard correction formula from capacitor design guides, with P in kilowatts, PF_init the measured power factor, PF_target the target, and Qc in kilovars:

Qc = P × [tan(cos⁻¹ PF_init) − tan(cos⁻¹ PF_target)]

Worked example — inputs: one load measured at 75 kW while running at 0.71 power factor, target 0.85:

  • tan(cos⁻¹ 0.71) = 0.9918
  • tan(cos⁻¹ 0.85) = 0.6197
  • Qc = 75 kW × (0.9918 − 0.6197) = 75 kW × 0.3721 = 27.9 kvar

So Qc ≈ 0.372 × P for these targets. That result is an estimate: round to the nearest rating the capacitor manufacturer offers at the actual system voltage — for the example, a 30 kvar step on most low-voltage tables — and check it against the governing code and the manufacturer's data. Measure every candidate load's kW and power factor simultaneously while it runs normally, never combine readings from different load states, and apply the same per-load discipline described in correcting power factor on a motor with a low measured PF.

Two checks remain before the step sizes are fixed. Confirm whether the meter reports displacement or true power factor: capacitors correct displacement only, and harmonic current keeps true power factor below the target regardless of installed kvar — the same gap covered in the true power factor of a single-phase input VFD and how to raise it. Then record voltage at light load and at full load, because with the facility's regulation problems, capacitance held on the bus at light load raises voltage and can push the power factor leading; split the total into switched steps rather than one fixed block.

Specify units listed to UL 810, the safety standard for power factor correction capacitors, which covers their protective fusing, and install the bank to NFPA 70 (NEC), 2023 edition, Article 460; requirements differ by edition and local amendment, so confirm both with your authority having jurisdiction and the manufacturer's documentation. After any de-energize, wait out the nameplate discharge time and verify before touching a capacitor terminal — the can holds charge after the source is off.

The order that protects both projects #

Sequence Effect on ground current Effect on the power factor project
Energize the bank first, trace afterwards The bank adds capacitance to ground on top of a path with no owner, and every later reading mixes fault, bank and system terms Measured power factor improves while the fault keeps running, and the bank inherits readings it did not cause
Trace, repair, then energize Every remaining ampere gets an owner, and the post-repair residual becomes a documented baseline Steps sized from clean measurements, and each step's own contribution verifiable against that baseline

In this example the identified faults accounted for 90 A − 20 A = 70 A of the original reading, so the remaining 20 A still has no owner. The decision: no capacitor step is energized until opening any load in the facility no longer changes the residual reading at the service grounding conductor, and immediately after each step switches in, its own contribution is measured and logged against the baseline. The var import then drops on schedule and the grounding system stays explainable.

Questions asked

Can the capacitors be energized first if a utility deadline leaves no time to trace?

Only as a last resort, and only the smallest step that meets the deadline. Log its contribution to the ground reading immediately after it switches in, and keep the tracing program running with the bank in service. Full energization over an unowned ground path hides the fault, mixes its current with the bank's, and a failed wye unit with a grounded tank adds a new phase-to-ground path on top of the one you already have.

How many kvar does each kilowatt of load need to move from 0.71 to 0.85?

About 0.372 kvar per measured kilowatt of load at these two power factors. Apply the ratio per load, at the operating point where you measured it: the 75 kW example load takes 27.9 kvar, and a 400 kW plant at the same power factors would need about 149 kvar in total, split into switched steps. Select physical ratings from the manufacturer's table at the actual system voltage.

Ground current rose after the bank was switched in — what does that mean?

First compare the reading with the contribution you logged when that step switched in. If the increase matches the step's own capacitive contribution, it is expected. If it exceeds the log, suspect a new insulation fault, moisture in the bank terminations, or harmonic current finding a resonance path with the bank; re-run the residual survey feeder by feeder and compare against the pre-energization baseline.

Why did the two ground faults found earlier never trip a breaker?

Fuses and breakers respond to current in the phase conductors. Current that leaves through an insulation fault and returns over grounding conductors and bonded metal can sit below the phase overcurrent pickup indefinitely, and with no ground-fault indicator or shunt trip nothing announces it. Ground-fault protection of equipment that sees this current is required by NFPA 70 (NEC), 2023 edition, Section 230.95, only on solidly grounded wye services at 480Y/277 V with a rated disconnect of 1000 A or more; confirm the applicable edition and local amendments with your authority having jurisdiction.

Keep reading

  • How-to

    Correcting power factor on a motor with low measured PF

    The nameplate full-load current already contains the motor's power factor and efficiency, so a measured 0.56 does not raise the 195 A limit — only a stamped service factor does. Correcting 0.56 to a 0.95 target needs about 1.15 kvar per measured kilowatt and cuts supply line current to about 59% of what it was.

    Power quality and harmonics

  • How-to

    Where to connect power factor correction on a star-delta starter

    Connect a star-delta starter's power factor correction bank on the line side of the contactors, never at the motor terminals of an open transition, with its own Article 460 disconnect, overcurrent protection and conductors at 135 percent of capacitor current. If the bank must sit downstream of the overload relays, route its leads through the sensing elements or resize the relays to the reduced current.

    Power quality and harmonics

  • How-to

    Splitting ground fault current for substation grid GPR design

    Size the substation grounding grid from the portion of the primary ground-fault current that actually enters the grid and earth, not from the total fault current. IEEE Std 80's current-split factor gives that portion, and a fourth conductor bonded to the grid at both ends carries the rest — its name, neutral or ground, does not matter.