Current IntelPower LibraryShop main store

Selection guide

Grounding transformer short-time rating for a 30 s fault

Power distribution and transformers Published 6 min read

Short answer

Size a star-open-delta grounding transformer by ground-fault duty, not nameplate kVA: at 11 kV the 30 s duty is 6.35 kV times the limited ground current, about 159 kVA at 25 A. Select the smallest frame whose manufacturer documents a short-time rating above one third of that current per winding, and reserve IEEE C57.96-2013 for repeat-event life loss.

On this page
  1. How much short-time duty does a grounding transformer carry?
  2. Why can a small frame carry six times its nameplate for 30 seconds?
  3. Which frame wins: nameplate kVA or a documented short-time rating?
  4. What resistor closes the open delta under a solid fault?
  5. What does a repeated event cost the winding?
  6. Will the small frame fit and survive inside the switchgear cubicle?
  7. Which transformer and resistor do you order for this duty?
  8. Questions asked

A grounding transformer is sized by the fault it must feed, not by its continuous kVA. On an 11 kV system with ground current limited to 25 A, the 30 s duty is 6.35 kV × 25 A ≈ 159 kVA, and a 25 kVA dry-type frame can carry it only where the manufacturer documents that short-time capability at your cubicle's starting temperature. This selection walks the decision in the order you meet it: the fault duty, why a small frame survives the pulse, the frame choice, the open-delta resistor, repeat-event life loss, the cubicle, and the order you place.

How much short-time duty does a grounding transformer carry? #

The short-time duty is the line-to-neutral voltage times the limited ground-fault current: 159 kVA for a 25 A fault, carried by all three windings for the full event.

The bank works as a zero-sequence source: a line-to-ground fault drives one third of the ground current through each wye-connected primary winding at line-to-neutral voltage — the same mechanism behind why a grounded wye sources ground fault current and a delta does not. Total duty follows as S = V_LN × I_g, with V_LN = 11 kV ÷ √3 = 6.35 kV, where V_LN is the line-to-neutral voltage and I_g the ground-fault current. Take I_g from the protection study, because the resistor sets it, and take the duration from primary clearing plus backup time. The duty figure is an estimate from the connection arithmetic; the frame decision is always checked against the manufacturer's short-time data.

Why can a small frame carry six times its nameplate for 30 seconds? #

Over the full event a dry-type winding heats almost adiabatically, so temperature rise follows current density squared times time, and a 25 kVA frame can carry the 159 kVA duty only where the manufacturer documents that short-time capability at your starting temperature.

Dry-type thermal time constants run in tens of minutes, so during the pulse almost none of the I²R heat escapes the copper: the winding behaves as a calorimeter, and the ceiling is the hot-spot temperature its insulation class allows above the temperature it started from. Steady-state methods — the dry-type transformer hot spot temperature rise arithmetic that governs continuous loading — answer a different question and give no short-time figure. The deciding number is the manufacturer's short-time grounding rating; a ratio of nameplate kVAs is not one.

Which frame wins: nameplate kVA or a documented short-time rating? #

Buy the smallest frame whose datasheet states a short-time grounding current at or above 8.33 A per winding at your cubicle starting temperature; on the example duty that is 6.35 times a 25 kVA frame's continuous 1.31 A and 1.44 times a 110 kVA frame's 5.77 A.

Both continuous per-winding figures come straight off the nameplate as bank kVA ÷ 3 ÷ V_LN.

Quantity Example value Basis
Ground-fault current I_g 25 A protection study, resistor-limited
Line-to-neutral voltage V_LN 6.35 kV 11 kV ÷ √3
Bank duty for the 30 s event 159 kVA V_LN × I_g
Current per winding 8.33 A I_g ÷ 3
110 kVA frame, continuous per winding 5.77 A 110 kVA ÷ 3 ÷ V_LN
25 kVA frame, continuous per winding 1.31 A 25 kVA ÷ 3 ÷ V_LN
Multiplication the frame must survive 1.44× / 6.35× 8.33 A ÷ frame rating
Deciding document short-time rating ≥ 8.33 A per winding manufacturer datasheet or test report

If the datasheet carries no short-time grounding line, that frame is not selectable at any kVA: ask the manufacturer to state current, duration, starting temperature, insulation class and repeat capability, or step up in frame until one does. Sizing for a short, heavy event is the same discipline as sizing a transformer for a 200 HP across-the-line motor start — the transient duty, not the nameplate, picks the frame.

What resistor closes the open delta under a solid fault? #

Treat the nameplate 230 V as the per-winding secondary voltage and a solid fault puts about 3 × 230 = 690 V across the open delta, so the resistor is 3 Ω carrying 230 A and burning about 159 kW, roughly 4.8 MJ of heat.

Illustrative inputs: the example primary voltage, 25 A limited ground current, 230 V per-winding secondary, solid fault, 30 s duration. The turns ratio is N = V_LN ÷ 230 V ≈ 27.6, and the resistor carries the secondary winding current, N × I_g ÷ 3 ≈ 230 A. Under a bolted fault the neutral displaces fully, so the open-corner voltage approaches three times the winding voltage; R = 690 V ÷ 230 A = 3.0 Ω, and the deposited energy is (230 A)² × 3 Ω × 30 s = 4.76 MJ, which cross-checks against the primary-side duty.

Some datasheets quote 230 V as the open-corner terminal rating instead; the winding voltage is then 76.7 V, the ratio about 82.8, the resistor current about 690 A and R about 0.33 Ω for the same energy. Confirm which voltage the datasheet means before ordering, and specify the resistor as a pulse rating — the energy for the full event — never as a continuous kW figure.

What does a repeated event cost the winding? #

A grounding event inside the insulation's thermal capacity is not free when it repeats: use IEEE C57.96-2013, section 4, to estimate the life-expectancy sacrifice of loading beyond nameplate, and require the manufacturer's repeat capability or a cooldown time before a second event.

The guide sets loading guidelines and limitations for dry-type distribution and power transformers against nameplate rating, and its section 4 gives the expected sacrifice of life expectancy for loading beyond that — hour-scale accounting, not a short-time limit, which still comes from the manufacturer. What it gives you here is the way to charge repeated events against insulation life. Residual heat matters as well: a second event inside the cooldown starts from a hotter winding with less adiabatic headroom. Editions and local amendments differ, so confirm the applicable requirements with the authority having jurisdiction and the equipment documentation.

Will the small frame fit and survive inside the switchgear cubicle? #

That small a frame fits many medium-voltage breaker cubicles, but the cubicle's continuous ambient becomes the winding's starting temperature for the pulse, and the switchgear maker must accept the mounted unit and its clearances.

The magnetizing loss heats the cubicle around the clock, so set the short-time rating's starting temperature at the highest ambient the cubicle reaches with the lineup loaded, not at the room's. Keep the frame's fault heat away from adjacent busbar and cable insulation, and check phase-to-earth clearances, mounting rails and door swing before ordering. Mounting a separately supported device inside the cubicle is the switchgear manufacturer's call: confirm it accepts the unit without affecting the assembly rating. One safety note: before opening the cubicle to survey the space or to install, de-energize the lineup, lock out, and verify absence of voltage with a tester rated for the system voltage.

Which transformer and resistor do you order for this duty? #

Order the smallest frame with a documented short-time grounding rating of at least 8.33 A per winding at your cubicle's highest ambient, and pair it with a resistor rated for the pulse energy, not a continuous kW figure.

On the example numbers the 110 kVA class frame runs the duty at 1.44 times nameplate and is accepted once its datasheet carries that line. The 25 kVA frame wins the cubicle only with an explicit short-time statement, the starting temperature it assumes, and a repeat or cooldown provision; without them, take the larger frame and the separate enclosure. The resistor follows the arithmetic of the resistor section, pulse-rated for the stored energy. After any real event, measure the winding resistance and compare it with the factory value: a rise beyond the manufacturer's tolerance says the limit was exceeded.

Questions asked

How does the duty change on a 13.8 kV system?

The line-to-neutral voltage rises to 7.97 kV, so the short-time duty becomes 7.97 kV times the ground-fault current, about 199 kVA at the same 25 A. Per-winding current stays at one third of the ground current, so the frame selection rule is unchanged; only the turns ratio, the open-delta voltage and the resistor ohms scale with the higher primary voltage.

Does a zig-zag grounding transformer size differently?

No. The bank duty is still the line-to-neutral voltage times the ground-fault current, because the zero-sequence current splits the same one third per leg even though it flows through two half-windings in series. What changes is the winding geometry, impedance and magnetizing behavior, so the manufacturer's short-time grounding rating for the zig-zag design is the figure that decides the frame.

Can the open delta also supply a small continuous load?

Keep the bank dedicated to grounding. Its impedance is high and its windings are designed for short-time duty, so a continuous auxiliary load would heat the winding around the clock, consume the adiabatic headroom the rating assumes, and interact with the resistor circuit that the sizing relied on. Take control and station power from a separate source.

Keep reading

  • Explainer

    Isolation transformer design checks for a new 480 V neutral

    The 650 kVA delta-star isolation transformer at Substation 2 is the right fix: its star point is a separately derived, solidly grounded 480 V neutral the 3P+E feeder can never supply. It is sound once five checks pass: load-based sizing, nameplate percent impedance, separately derived system grounding, redone protection settings, and no ties across the transformer's phase shift.

    Power distribution and transformers

  • Troubleshooting

    Checking a delta high leg arc flash calculation's numbers

    The 9.127 kA at the panelboard checks out against the 11.33 kA infinite-source terminal limit once utility impedance is counted. The 73 cal/cm² hinges on clearing time: the referred bolted current clears the 600 A primary breaker in 0.033 s, but IEEE 1584 sets device time from the arcing current, which falls below the 3,600 A pickup into the thermal band — so the label is credible until the study file shows otherwise.

    Electrical safety and codes

  • Selection guide

    Sizing a padmount transformer for a 120/240 V delta load

    Select the 300 kVA four-wire delta padmount and reject the 225 kVA unit: the center-tapped winding runs at 129% of its rating during the start on the smaller unit and 97% on the larger one. The choice holds only with a written tapped-section rating covering the start and continuous loading calculated here; otherwise use a single-phase bank or a 208Y/120 V wye secondary.

    Power distribution and transformers