Current IntelPower LibraryShop main store

Comparison

How busbar differential protection detects a bus fault

Protection: breakers, fuses and SCCR Published 7 min read By Current Intel engineering team

Short answer

A bus fault must clear fast and zone-selectively, and it must not be reclosed into. Overcurrent relays are acceptable only where fast clearance is not required; current differential and voltage (high-impedance) differential schemes sum the currents at the bus, trip every breaker in the zone, and block reclosing because bus faults are usually permanent.

On this page
  1. Why a bus fault gets zone-wide treatment
  2. The three schemes at a glance
  3. How current differential decides
  4. How voltage differential decides
  5. Worked example: phasor sum on a six-circuit bus with 3000:5 CTs
  6. What CT saturation does to both schemes
  7. Where each scheme fits
  8. Questions asked

A bus fault takes out the whole lineup behind it, so the protection decision comes down to speed and selectivity. Overcurrent relays on the bus are acceptable only where a delayed, coordinated trip is tolerable. Where it is not, a differential scheme — current differential or voltage (high-impedance) differential — sums the currents at the bus, detects the imbalance of an internal fault, trips every breaker in the zone, and blocks automatic reclosing, because bus faults are usually permanent. This article compares the three schemes and works the phasor sum on a six-circuit bus so you can see each scheme make its decision.

Why a bus fault gets zone-wide treatment #

A bus-zone fault comes from a failed support insulator, a breaker that fails while closed, or a foreign object across the bus. The fault current is high, the mechanical forces on the bus are destructive, and every feeder tied to that zone loses supply until the fault is gone. That is why the ANSI/IEEE C37.2 device number 87B exists: a bus differential relay owns a defined zone, and when it operates, it trips every circuit breaker connected to that zone in one shot.

That trip also blocks automatic reclosing. A line fault is often a transient arc that a reclose successfully clears; a bus fault is broken insulation or metal where metal should not be, so reclosing would just re-energize a live fault. Confirm the reclosing policy for your installation with the local authority having jurisdiction and the utility's interconnection documents, because those requirements differ by country and local amendment.

The current the scheme must interrupt is the bolted fault current at the bus, and that is the same value you need for breaker duty and arc-flash work: see which bolted fault current to use for breaker duty and arc flash before you rate anything against it.

The three schemes at a glance #

Scheme Operating basis Fit it when Watch out for
Overcurrent (50/51) Current magnitude above a setting, with time delay Fast bus-fault clearance is not required and the coordination delay is acceptable No zone boundary; it must coordinate with every feeder relay, and that coordination costs clearing time
Current differential (low-impedance 87B) The phasor sum of all currents entering the zone must be zero A numerical relay with one CT set per circuit; many circuits on the bus False differential current when a CT saturates on an external fault
Voltage differential (high-impedance 87B) CT secondaries of all zone circuits connected in series in a closed loop; the relay responds to voltage across a high impedance Dedicated, matched CT sets; the scheme used on most buses in North America, with a long record of good performance Every circuit in the zone needs a suitable, matched CT, and polarity must be proven at commissioning

How current differential decides #

Current differential applies Kirchhoff's current law to the bus zone: with no internal fault, the phasor sum of all currents entering and leaving the zone is zero. A nonzero sum means current is going somewhere inside the zone — into a fault — and the relay trips.

The scheme's weak point is the external fault. On a six-circuit bus, five circuits may feed an external fault with unequal currents while the sixth carries the combined return. All of that return current runs through one CT, and if that CT cannot reproduce it, the relay computes a false differential current. Scheme design, CT selection and relay algorithms all exist to keep that false differential below the trip threshold, and you verify them against the relay manufacturer's stability requirements before putting the scheme in service.

It is the same phasor-sum principle that makes a transformer differential operate on inrush while overcurrent waits, which we work through in why differential trips on transformer inrush but overcurrent does not.

How voltage differential decides #

Voltage differential, the high-impedance scheme, connects the secondaries of all incoming and outgoing feeder CTs in series with the differential relay instead of in parallel, forming one closed loop. With matched CT polarities and no fault in the zone, the summed CT secondary voltage is zero, so no voltage appears across the relay and nothing operates.

An internal fault unbalances the loop. The resulting voltage drives a current around the loop, that current passes through the relay, and the relay trips every breaker associated with the bus zone. A stabilizing resistor in series with the relay raises the voltage the scheme needs before it will operate, so the false current from a saturating CT on an external fault flows through that CT's own magnetizing branch rather than through the relay; a nonlinear resistor across the relay limits the peak voltage the loop can develop. The scheme still has to be proven against CT saturation, because every bus differential relay, whatever its design, must tell a true internal fault apart from the false differential current a saturated CT produces.

Worked example: phasor sum on a six-circuit bus with 3000:5 CTs #

Example inputs, chosen to be easy to check rather than measured values:

  • Six circuits on one bus zone, each with a 3000:5 current transformer, a 600:1 ratio.
  • An external fault beyond circuit 6. Circuits 1 through 5 each deliver 12,000 A primary into the bus, and circuit 6 carries the combined 60,000 A primary out of the zone.
  • The relay picks up on 1 A of differential secondary current (an example setting; use your relay's own setting in practice).

The rule: the relay operates when the magnitude of the summed secondary currents exceeds the pick-up value. Convert each primary current by dividing by the CT ratio, add currents into the zone as positive and currents out as negative.

External fault on circuit 6:

  • Each of circuits 1 to 5: 12,000 A ÷ 600 = 20 A secondary, into the zone.
  • Circuit 6: 60,000 A ÷ 600 = 100 A secondary, out of the zone.
  • Sum: (5 × 20 A) − 100 A = 100 A − 100 A = 0 A secondary.
  • 0 A is below the 1 A pick-up, so the scheme restrains. Correct — the fault is outside the zone.

Now the same bus with a fault on the bus itself. Circuits 1 through 5 still deliver 12,000 A each, total 60,000 A, but the current terminates in the fault and nothing leaves the zone (the load feeders carry negligible current in this example):

  • Sum: 5 × 20 A = 100 A secondary, into the zone, no return.
  • 100 A is far above the 1 A pick-up, so the relay operates.

Decision: the external fault sums to zero and the scheme holds; the internal fault sums to 100 A secondary, well above pick-up, so every breaker in the zone trips and reclosing stays blocked.

What CT saturation does to both schemes #

On an external fault, the faulted circuit's CT carries the sum of everyone else's current, which is exactly the 60,000 A of the example. Pushed that hard, its secondary can collapse while the other five CTs faithfully reproduce their primaries, and the computed sum stops being zero. That collapse happens above the CT's knee-point voltage, and what it does to the delivered secondary current is covered in why CT saturation at the knee point cuts secondary current.

Both differential schemes answer the same threat. The high-impedance design forces the false current through the saturating CT's magnetizing branch with its stabilizing resistor, and a numerical low-impedance relay applies saturation-detection and percentage-restraint logic in software. Either way, the CTs on every circuit in the zone must be adequate for the maximum through-fault current, and the manufacturer's sizing method for the scheme — CT performance class, burden and the stabilizing resistor value — is what sets the margin, not a rule of thumb.

Where each scheme fits #

  • Overcurrent on the bus: use it when no requirement at the installation demands fast clearance and the coordinated time delay is acceptable. It is the simplest scheme and it has no zone boundary, so accept that it clears late by design.
  • Current differential: use it when you have a numerical relay and a CT set on every circuit and you need fast, zone-selective clearance. Verify the external-fault stability for your worst through-fault current against the relay documentation.
  • Voltage differential (high-impedance): use it when the bus has dedicated, matched CTs — it is the majority choice on North American buses for good reason, and it rides through external-fault saturation well when the CTs and stabilizing resistor are sized for the job.

Whichever scheme you select, the operating decision does not change: a bus differential trip closes every breaker in the zone and blocks reclosure, because the fault it saw is usually still there.

One safety note before you prove any of this: de-energize the bus, lock out, and test for absence of voltage before opening any panel or CT circuit, and never open a differential CT secondary under load — short it out first, because an open CT secondary can develop a hazardous voltage.

Questions asked

What does the 87B device number mean?

ANSI/IEEE C37.2 assigns numbers to protection functions: 87 is any differential relay that compares currents entering and leaving a zone, and the suffix B tags the bus as that zone. You will see the same 87 family on transformers and motors with different suffixes. The label identifies the function only; the scheme, settings and CT requirements come from the relay manual and the protection design.

Can overcurrent relays protect a busbar?

Yes, when fast clearance is not required. Time-delayed overcurrent sees a bus fault through the same current the feeder relays see, so it must coordinate with them and clears later than a differential trip would. That delay is acceptable on a small bus with modest fault duty; on a large or high-duty bus the extra clearing time shows up as more equipment damage and a longer outage.

Why is reclosing blocked after a bus differential trip?

A bus fault is usually permanent metal-to-metal damage: a shattered support insulator, a breaker that failed while closed, or a foreign object thrown across the bus. Reclosing would re-energize a fault that is still there, so a bus differential trip closes every zone breaker and locks the scheme out. Line protection is different, because many line faults are transient and reclosing there is normal practice.

What causes false differential current on an external fault?

On an external fault, the circuit that carries the fault current out of the zone also carries the sum of every other circuit's contribution, so its current transformer works hardest. If that CT saturates, its secondary no longer reproduces the primary current, and the relay's computed sum settles at a nonzero value even though no bus fault exists. How far the CT drives past its knee point sets how large that error becomes.

Keep reading

  • Explainer

    Why a 51N earth fault setting trips without a fault

    A residual 51N element set at 0.05 In with a 0.7 s delay trips without a fault when the residual connection reports more than that in normal operation: load unbalance, a CT circuit error, or a low-level earth fault. Read the event record, verify the CTs, measure the normal residual current, then set the pickup above it, 0.10 In first and 0.12–0.13 In if the measurement demands it, keeping the delay only where coordination supports it.

    Protection: breakers, fuses and SCCR

  • Troubleshooting

    Why SKM shows zero fault current on the 480 V bus

    The zero is a result-field problem, not a calculation failure: ANSI Sym 3P Mom and ANSI Asym 3P Mom are momentary duty variables defined above 600 V, so they read 0 kA at a 480 V bus while ANSI 3P int populates. Confirm the bus is inside the study scope, then display the documented half-cycle symmetrical RMS low-voltage result and compare it with the breaker short-circuit rating.

    Protection: breakers, fuses and SCCR

  • How-to

    Conduit material and bolted faults in fault current calcs

    Enter the nonmagnetic (PVC) conduit entry when the run is mostly PVC; give steel elbows their own steel segments only if your method accepts them. A bolted fault is a zero-impedance fault at the point of study, so it yields the maximum available current, limited by the source and path impedance alone, and it is the value compared against interrupting ratings and SCCR.

    Protection: breakers, fuses and SCCR