How-to

Identifying leads on a six-wire two-speed single-phase motor

Motors and motor starters Published 8 min read

Short answer

No standard assigns colors to U, Um, V, Vm, W and Wm on a two-speed single-phase motor; the machine's winding diagram and rotary-switch contact schedule are the only authority. Map the six leads de-energized with an ohmmeter, land them per the schedule, and fit the specified run capacitor — 30 µF on the 230 V motor recorded here, where a 40 µF substitute ran rough on low speed.

On this page
  1. Is there a standard color code for U, Um, V, Vm, W and Wm?
  2. What do U, Um, V, Vm, W and Wm mean on a two-speed single-phase motor?
  3. How do I identify six unmarked motor leads with an ohmmeter?
  4. What should I do about a green winding lead?
  5. How do I connect the six leads to the rotary speed switch?
  6. Why did a 40 µF run capacitor make low speed run rough?
  7. The motor hums but will not start — is the winding faulty?
  8. Questions asked

There is no standard color code for the leads of a two-speed single-phase motor. Red, white, blue, green, grey and yellow identify nothing on their own: U, Um, V, Vm, W and Wm take their colors from the individual motor build, and the only authority is the winding diagram and switch contact schedule for that machine. What follows recovers the connections without the colors: map the six leads with an ohmmeter, chain them into the winding ring, land them on the rotary speed switch per the recorded schedule, and fit the specified run capacitor — on the 230 V sawbench motor this procedure was recorded from, 30 µF, where a 40 µF stand-in ran rough at low speed. The letters, the meter work, the green lead, the switch and the capacitor, in the order you meet them.

Is there a standard color code for U, Um, V, Vm, W and Wm? #

No. Lead colors on two-speed single-phase motors are a build-specific marking, and none of the six positions U, Um, V, Vm, W or Wm has an assigned color in any standard, so the machine's own winding diagram and switch schedule are the only authority. Motor factories run builds that differ only in lead colors, so a wire that means U on one machine can be Vm on the next.

What survives between machines is the letter scheme, the winding geometry and the switch logic — not the insulation color. Your working documents are the winding diagram that names the terminals and the contact schedule that says which switch contacts close in each position. If both are gone, the meter procedure below recovers the winding ring and the switch positions; the corner-versus-midpoint assignment is the one thing that has to come from the diagram, the maker, or a rewind shop that will derive it.

What do U, Um, V, Vm, W and Wm mean on a two-speed single-phase motor? #

They mark a delta of six winding sections: U, V and W sit at the corners, Um is the midpoint of the U–V side, Wm of the V–W side and Vm of the W–U side, and each side is split into two sections. The letters and the triangle look like three-phase practice, and that resemblance sends people wrong. The reconnection idea itself is the Dahlander approach — two speeds from one set of windings by changing how the sections connect, drawn for three-phase machines as delta or double-star in a six-wire two-speed motor wiring guide — but on this motor U, V and W are corner labels, not supply phases. The nameplate settles it: single-phase, with line and neutral landing on the switch and the run capacitor phase-shifting the auxiliary sections.

Mind where the midpoints sit, because the suffixes do not simply repeat the far corner: Um belongs to the U–V side, Wm to V–W and Vm to W–U. Draw the triangle and place each midpoint where the diagram puts it before you label anything. Lead schemes belong to the winding that carries them — a nine-lead wye-start motor that will not spin numbers its leads 1 to 9, and that numbering means something else again — which is exactly why no color or letter chart transfers between machines.

How do I identify six unmarked motor leads with an ohmmeter? #

Measure all fifteen pairwise resistances with the motor isolated: each lead reads lowest to exactly two partners, its adjacent sections, and those pairs chain the six leads into the winding ring. Work at the motor with everything de-energized. Lock out the supply and test for absence of voltage at the terminals with a proven tester before the terminal box comes open — that verification is what NFPA 70E, 2024 edition, covers for this kind of electrical work; confirm the procedure with your local authority having jurisdiction and the machine documentation.

  1. Photograph the terminal box, then disconnect all six leads from the switch and from each other. Label each lead with its color and its old position.
  2. On a digital multimeter's ohms range, check every lead to the motor frame. All six must read open; a low reading is an insulation fault, and reading motor lead-to-ground ohms on a 480 V compressor covers what those numbers mean.
  3. Measure all fifteen pairwise resistances between the six leads and enter them in a six-by-six table.
  4. Expect every pair to conduct, because the ring offers two paths between any two leads. Each lead reads lowest to exactly two partners — its adjacent winding sections — and highest to exactly one partner three positions around the ring.
  5. With six similar sections, expect the adjacent reading near five-sixths of one section's resistance and the opposite reading near one and a half times it, about 1.8 times apart; uneven sections shift the numbers but not the ordering.
  6. Chain the adjacencies into the ring. The pattern is fixed: each corner's opposite is a midpoint — U faces Wm, V faces Vm, W faces Um.
  7. The meter cannot tell you which alternate set of three is the corners and which the midpoints; that assignment comes from the winding diagram or the switch schedule.
  8. Test the run capacitor on a capacitance range and record the value against the machine's specification before the box closes.

What should I do about a green winding lead? #

Treat it as a winding lead only after you prove it: on the machine this record comes from, green carried Wm, a midpoint connection, so trace the conductor back to the winding, confirm it reads like a winding and never use it as the frame bond. Green, alone or with a yellow stripe, is the protective-conductor color in the European and North American wiring conventions this machine gets serviced under, so a green wire at a motor is exactly what an earlier repairer may have re-purposed or "corrected". Prove its function before you trust either story: it must trace back into the winding network, read low ohms to its two ring neighbors and open to the frame. Then mark it with the identifier the diagram gives it. The frame gets its protective bond from the supply's protective conductor on the frame stud — never through a winding lead, and never land the protective conductor on a winding terminal.

How do I connect the six leads to the rotary speed switch? #

The switch, not the colors, defines the connection: copy the machine's contact schedule by checking continuity between switch terminals in each position with the power off, then land each lead where the schedule puts its winding identifier. The speed switch is a rotary cam switch with an off position and two speed positions, and its schedule — which terminals close in which position — is the real wiring diagram; the leads simply land where the schedule expects each winding identifier. The continuity-mapping skill is the same as identifying unknown terminals on a NEMA size 1 motor starter, applied across three positions instead of one. For the machine this record comes from, the surviving notes give the mapping below. Use it to cross-check that machine's diagram and your own measurements — matching colors on any other motor prove nothing.

Winding identifier Recorded lead color Recorded switch terminal
U red 5
Um white 1
V blue 7
Vm yellow 3
W grey 10
Wm green 18
Line, from supply wiring — 13
Neutral, from supply wiring — 2

If the switch itself needs replacing, equivalence is contact-for-contact. The original design spread this schedule over five decks; a commonly fitted replacement reproduced it on four by using a spare contact on its fourth layer. Deck count and terminal numbering follow the maker, so compare published schedules position by position, never the outside of the switch.

Why did a 40 µF run capacitor make low speed run rough? #

Because 40 µF is 33 percent above the specified 30 µF: the extra capacitance cuts the capacitor's reactance to 75 percent and shifts the auxiliary-circuit phase angle, and on this machine the error showed up as rough running on low speed while high speed still sounded acceptable. Worked example, with illustrative inputs — a 230 V, 50 Hz supply and an ideal capacitor straight across it:

  • The substitution raises capacitance by (40 − 30)/30 × 100 = 33.3%.
  • Capacitive reactance is Xc = 1/(2πfC). At the specified 30 µF: 1/(2π × 50 Hz × 30 µF) = 106 Ω. At 40 µF: 79.6 Ω, which is 75% of the specified figure.
  • Current through that ideal part follows I = V/Xc: 230 V/106 Ω = 2.17 A against 230 V/79.6 Ω = 2.89 A, a 33.3% rise.

In the motor the capacitor sits in series with auxiliary winding sections, so these figures are an estimate of direction and size, not a prediction of line current. What the phase shift does to torque is the real effect, and each speed arranges the sections differently around the capacitor, which is why a wrong value can pass at one speed and fail at the other — high speed running acceptably is not an acceptance test. The decision: fit the specified 30 µF in continuous motor-run duty, at the original's voltage rating or higher, and try both speeds.

The motor hums but will not start — is the winding faulty? #

Not on the machine this procedure comes from: the no-start fault there was a bad connection and a short-circuited run capacitor, and the windings were sound, so test connections, capacitor and switch schedule before you condemn the winding. Test in the order of cheapest first. Connections: a loose or oxidized termination can open the whole auxiliary circuit, and because it dissipates P = I²R, a terminal that is warm after a short attempt is telling you where the fault is. Capacitor: measure it — a shorted run unit is a recorded failure on this machine, and it removes the phase shift the motor needs to accelerate. Switch: verify the schedule in the failing position, since each speed has its own contact set. Windings: compare the section readings from your ring table; a sound set is consistent with its neighbors, and an open or low section is the rewind shop's territory.

Set a stop rule: if the motor hums without turning, switch off at once — a stalled start pushes many times running current through windings with no fan turning, and repeating it turns a capacitor fault into a rewind.

Questions asked

Can I replace the speed switch with a VFD?

Not with a standard drive. A capacitor-run single-phase motor depends on its run capacitor and auxiliary winding for the phase shift, and a drive with a three-phase output does not serve that circuit; only drives built specifically for single-phase capacitor motors apply, and they must match this winding arrangement. Restoring the rotary switch and the specified capacitor is the simpler documented repair.

What voltage rating should the replacement run capacitor have?

Fit a part rated for continuous motor-run duty at the same or a higher voltage than the original. The capacitor sits in series with the auxiliary winding and can see more than its simple share of the supply voltage, so never fit a lower-rated part even when the capacitance matches; the rating is printed on the original can and belongs in the order.

Where do I get the winding diagram if the manual is lost?

Ask the machine maker first, even where the manual is sold rather than supplied. Check whether a previous repairer left corrected notes with the machine, since a hand-updated drawing is often better than the original. Failing both, a motor rewind shop can derive the connections from the resistance ring and a switch schedule you tabulate yourself, so send the nameplate data with any request.

Is this six-lead delta the same as a three-phase Dahlander motor?

The letters are shared, the machines are not. A three-phase Dahlander motor changes speed by reconnecting its windings into delta or double-star and is fed with three phases; this motor is single-phase, with the run capacitor and switch producing the phase shift. Wiring it to three phases because the terminals read U, V and W would be wrong.

Keep reading

  • How-to

    Choosing a start capacitor for a 1/4 HP 120 V motor rewind

    Install 160 µF, inside the 100-200 µF range for this size, as the start capacitor on the 56-turn, 22 AWG start winding of a 1/4 HP, 4-pole motor, then verify by measuring start current and switch opening. The winding impedance, not the horsepower, fixes the value.

    Motors and motor starters

  • Troubleshooting

    Why motors burn up with no overload trips on 480 V

    Crystallized insulation several feet back from motor terminals is the signature of high-resistance terminations cooking the leads from I²R heat, while unbalanced voltage adds negative-sequence heating that current-magnitude overload heaters never see. Record all three line-to-line voltages and all three phase currents under load, verify the transformer grounding, and measure insulation resistance on every failed branch before any restart. Welded contacts and ruptured starters are consequences of closing onto failed motors, not a separate mystery.

    Motors and motor starters

  • Troubleshooting

    Why neutral-side switching trips a smart DOL starter

    Move the direction changeover contactor to the line side so the starter feeds the selected winding directly, and leave the run capacitor between the CW and CCW terminals: in the tested 110 V, 2.6 A circuit that raised successful starts from about 1 in 20 to 19 in 20. Return-side switching lets capacitor charging current through the unselected winding distort the current the starter measures at closure, so its residual-current diagnostic reports a missing path.

    Motors and motor starters