Identifying wires on an unmarked three-phase motor

Motors and motor starters Published 5 min read By Current Intel engineering team

Short answer

With six terminals and no rating plate, first lock out and prove dead, then identify the three winding pairs with an ohmmeter and confirm the metal strip joins three winding ends as a star point. Wrong phase order only reverses rotation and is fixed by swapping any two supply conductors; wrong voltage or winding connection damages the motor, so recover the rating before energizing.

On this page
  1. Reject the shortcuts first
  2. Resolve the terminal labeling
  3. Ohm out the windings with power isolated
  4. Confirm the connection and the supply voltage
  5. Set the rotation by swapping two supply conductors
  6. Verify before release
  7. Questions asked

A motor with six terminals, three same-color leads and no rating plate can be identified safely without guessing at the supply: the terminal stamps and an ohmmeter give you the winding pairs, and rotation is a phase-order question you settle last. The dangerous mistake is the reverse one — energizing to "see which way it goes" before the winding connection and voltage are known. A wrong phase order merely reverses the shaft; a wrong voltage across the wrong connection can burn the windings. Work through the checks below in order and stop at any step that fails.

Reject the shortcuts first #

  • Reading phases off the wire positions or colors. Three leads of one color carry no phase identity. Trace each conductor to its stamped terminal and test the winding pairs with a meter instead.
  • Energizing to discover the ratings. If the motor runs on the wrong winding connection, it may run briefly and then fail. Find the rated voltage and connection before the first energization.
  • Trusting the links on the terminal strip without testing. A metal strip across three terminals is a star point only if those three points are three winding ends. Confirm each pair with an ohmmeter.
  • Using continuity to the frame to identify a winding. No winding conductor should reach the frame. A reading there is a fault, and the protective earth stays bonded to the case regardless.
  • Raising overload or breaker settings to keep it running. Protection is sized to the motor's rated current, which no terminal layout tells you.

Resolve the terminal labeling #

The terminal stamps in this case name six points: a1, b1, c1, a2, b2 and c2. The links are described as joining a1, a2 and a3 — a seventh label that is not on the six-terminal list. That conflict has to be resolved at the board before the links can be called a star point: remove the cover, verify each stamped label by eye and by meter, and sketch what you actually find. If one link joins three winding ends, one from each winding pair, the windings are in star. A similar labeling trap on a smaller scale is covered in the guide on identifying unmarked 9-lead motor leads and wiring them for 240 V, and the underlying NEMA MG 1 terminal-marking convention for three-phase machines is the same idea: one numeral set per winding end, joined by links for the chosen connection.

A casting mark such as AEI on the end plate is a maker's stamp, not a rating. It gives none of the rated voltage, current, frequency, power, duty or permitted star/delta arrangement, so it cannot justify a connection decision.

Ohm out the windings with power isolated #

One safety note before any terminal box is opened: lock out and tag the machine supply, then test for absence of voltage at the motor terminals with a properly rated tester before touching a conductor or link.

  1. Remove the links and disconnect the three leads if needed so all six winding terminals are electrically separate.
  2. With an ohmmeter, find the three independent pairs. For example, on a small motor you might read about 2.0 Ω between a1 and a2, 2.1 Ω between b1 and b2, and 2.0 Ω between c1 and c2, with open readings between any two terminals of different pairs. Each terminal then belongs to exactly one winding, and the three resistances should match closely — in the example, within roughly 5 percent. A badly unbalanced pair or an open pair points to a winding or joint fault.
  3. Test every winding terminal to the case with insulation-test equipment, not a continuity buzzer. On a 480 V-class machine tested at 500 V DC, a healthy winding shows a very high reading; a reading near zero or a steady climb toward a low value means stop and investigate.
  4. Confirm the protective earth is bonded to the case and separate from every winding terminal.
  5. Record the verified pairs on a sketch; faded stamps and strip positions are not reliable records.

Confirm the connection and the supply voltage #

The star links place the line-to-line supply voltage across two windings in series; a delta connection places full line voltage across each winding. The same physical motor can therefore be linked either way, and the correct choice depends on the winding's rated voltage against the measured supply — a relationship the resistance test cannot reveal. Measure the supply line-to-line voltage with rated test equipment, then search the motor body, the terminal-cover interior, the machine documentation and maintenance records for the rated voltage and connection diagram. If the recovered rating calls for delta at your supply voltage, remove the star links and cross-link the ends per the documented diagram.

If no rating can be recovered anywhere, stop: do not use a trial start to find it. Identification by a motor shop or replacement with a motor whose ratings match the supply is the decision. Overload protection then gets set from the motor nameplate full-load current, as covered in setting overload relays from motor nameplate full-load current.

Set the rotation by swapping two supply conductors #

Only after voltage, connection, insulation and protection check out:

  1. Connect the three verified leads to the three supply phases in any order.
  2. With the driven mechanism safe to move and personnel clear, run the motor briefly and observe the direction.
  3. If it runs backward, lock out, prove dead, and exchange any two of the three supply conductors. There are no electrically special outer phases — any pair swap reverses a three-phase motor, as explained in why any two phase swaps reverse a three-phase motor, and a phase rotation meter confirms the sequence before energizing if you want the direction settled without a run, per what a phase rotation tester tells you about motor direction.
  4. Recheck the direction before coupling to a direction-sensitive load. Never move the earth conductor or alter the star links to change rotation.

Note the contrast with drives: on the supply side of a VFD the phase order does not even change rotation, which is a different situation from a direct-on-line motor.

Verify before release #

Run the machine under controlled conditions and record the result: commanded direction, smooth acceleration, stable current in all three conductors, and correct starter and stop action. Compare the three phase currents with each other; a large imbalance calls for supply, connection or winding investigation. Before returning the machine to service, check the terminal cover, cable restraint, earth bond and guards, label the three conductors permanently, and add the terminal sketch to the machine record so the next disconnection does not recreate the fault.

Questions asked

Can I connect three same-color motor leads to the supply in any order?

Only after the supply voltage matches the motor's rated winding voltage, the winding pairs are proven, the connection is confirmed, and overload protection matches the motor's rated current. The initial order affects only rotation direction, and exchanging any two supply conductors reverses it. Swap the conductors, never the star links or the earth.

Does a metal strip across three terminals mean the windings are in star?

It indicates star only if meter tests prove the strip joins three winding ends, one from each of the three winding pairs. Terminals labeled a1, a2, a3 joined by a strip conflict with a six-terminal list naming a1, b1, c1, a2, b2, c2, so trace every terminal with the ohmmeter before trusting the links.

What if no rating information can be found anywhere?

Do not energize on trial. A winding pair resistance reading confirms continuity, not rated voltage or current. Send the motor to a motor shop for identification or replace it with a motor whose rated voltage, current and connection match the supply and the driven machine.

Which two phases do I swap to reverse the motor?

Any two of the three supply conductors. There is nothing special about the outer two. A three-phase motor reverses whenever the phase sequence reverses, and moving any one pair of supply conductors does that. Confirm with the lockout and dead-test steps before opening the terminal box again.

Keep reading

  • How-to

    Identifying leads on a six-wire two-speed single-phase motor

    No standard assigns colors to U, Um, V, Vm, W and Wm on a two-speed single-phase motor; the machine's winding diagram and rotary-switch contact schedule are the only authority. Map the six leads de-energized with an ohmmeter, land them per the schedule, and fit the specified run capacitor — 30 µF on the 230 V motor recorded here, where a 40 µF substitute ran rough on low speed.

    Motors and motor starters

  • How-to

    Identifying terminals on an old star-delta starter panel

    A1 and A2 are the contactor coil terminals, and the coil's labeled voltage must sit within the 85 to 110 percent band IEC 60947-4-1 requires against the control supply. NO only means a contact is open at rest; its traced wiring decides whether it is a start or holding contact. With the panel locked out and verified dead, tracing the six motor leads through the contactors is what proves a star-delta scheme.

    Motors and motor starters

  • Troubleshooting

    What the seven wires on a single-phase capacitor motor mean

    Seven leads mean the manufacturer brought internal junctions out separately: run-winding sections, the start circuit, capacitor taps and thermal-protection conductors. Identify each pair by continuity and resistance with the supply locked out and capacitors discharged, then match the motor's own connection diagram. Never wire a reversing switch to guessed leads with power on.