Identifying terminals on an old star-delta starter panel

Motors and motor starters Published 7 min read By Current Intel engineering team

Short answer

A1 and A2 are the contactor coil terminals, and the coil's labeled voltage must sit within the 85 to 110 percent band IEC 60947-4-1 requires against the control supply. NO only means a contact is open at rest; its traced wiring decides whether it is a start or holding contact. With the panel locked out and verified dead, tracing the six motor leads through the contactors is what proves a star-delta scheme.

On this page
  1. What A1, A2 and NO actually identify
  2. Isolate the panel before any conductor moves
  3. Trace the power path first
  4. Measure the six motor leads
  5. Decode the pushbuttons and the coil circuit
  6. Check the motor nameplate against the supply
  7. The decision your tracing gives you
  8. Questions asked

You will not identify an old star-delta panel from its markings alone. A1 and A2 are the contactor coil terminals, NO only says a contact sits open at rest, and no printed label proves which contactor is main, star or delta — on your panel the buttons do not even own contact blocks, they push levers. What settles every terminal is where its conductor lands and what your meter reads with the panel dead. One dead-panel session does it: record the as-found state, trace the power path, measure the six motor leads, decode the buttons and the coil circuit, then test the scheme against the motor nameplate.

What A1, A2 and NO actually identify #

Under the IEC terminal convention used by contactor makers worldwide, A1 and A2 are the operating-coil connections. The coil's own label — voltage, AC or DC, and for AC the frequency — decides what may feed it; never infer the rating from the motor supply. IEC 60947-4-1, the 2018 edition of the product standard for contactors and motor starters, requires a contactor to close and hold on any control voltage between 85 and 110 percent of its rated coil voltage. Example: a coil labeled 240 V AC is healthy on 0.85 × 240 V = 204 V up to 1.10 × 240 V = 264 V, so a control transformer measured at 238 V feeds it correctly, while the same transformer would burn out a coil labeled 110 V.

NO means normally open: open while its operating mechanism is at rest. It names a state, not a role — the same marking appears on start contacts, holding contacts and sequence contacts. Where the green and red buttons push levers mechanically, the lever markings themselves may even be reversed, so treat every label as a report to verify, never as the finding.

Isolate the panel before any conductor moves #

Lock out every source into the panel — the power feeder and any separately fed control circuit — and verify absence of voltage with a tester rated for that circuit; that is the electrically safe work condition NFPA 70E, 2024 edition, the workplace electrical safety standard, requires before you touch a conductor, and your site's lockout procedure supplies the detail. The panel stays dead through everything below.

While nothing has moved yet, photograph the door linkage, the levers and every terminal from more than one angle, copy each nameplate, and tag every conductor with where it sat before you lift it. If a reading later contradicts another, those tags are what let the panel go back together exactly as found.

Trace the power path first #

Follow the heavy conductors in order; the control wiring only makes sense once the power topology is known.

  1. Find the incoming supply: three large conductors run from the isolator or breaker to the line side of one contactor. That contactor is the main one.
  2. Follow its load side: the conductors run through the overload relay element and on to three positions of the motor terminal block. Which current the overload should sense depends on whether it sits in the main path or the delta path, and overload relay placement in a wye-delta starter circuit settles that choice.
  3. Find the star contactor: the one whose three line-side terminals are joined by a commoning link or jumpers, collecting three winding ends into one point.
  4. Find the delta contactor: the one whose poles cross-connect each fed winding end to a different winding end.
  5. Count the motor conductors at the terminal block. Six power conductors must reach the motor; three means this is not a star-delta starter, whatever the panel looks like.
  6. With the contactors at rest, meter each main pole from its line-side to its load-side terminal. Every pole reads open; a closed reading is a welded contact to fix before anything else.

Operate nothing but the buttons' own mechanisms, and never restore power just to see what an unidentified lever does. Where a continuity reading makes no sense, coils, other contacts and connected devices are giving you parallel paths: lift one conductor, label it, measure, return it to its tag.

Measure the six motor leads #

A multimeter on its resistance range identifies the winding pairs. Touch the probes together first and note the lead resistance. Worked example: the probes read 0.3 Ω, and two terminal-block positions read 1.9 Ω between them, so that winding is 1.9 Ω - 0.3 Ω = 1.6 Ω. Work through all six positions until you hold three pairs, and compare them: in this example 1.6 Ω, 1.6 Ω and 1.5 Ω. The absolute figure scales with motor size, so judge the balance between the three, not against any table. An open pair, or a pair far from its two companions, means the lead labels are wrong or a winding is damaged — resolve that before anything is reconnected.

Decode the pushbuttons and the coil circuit #

Press each button with the panel still dead and watch which lever, contact block or latch it moves, and whether it returns when released.

  • Open at rest and closed while pressed: a momentary start contact.
  • Closed at rest and open while pressed: a stop contact.
  • The button moves a contactor armature directly and stays put when released: a mechanically latched assembly, which is not an electrical start-stop station and needs the maker's operating diagram before you interpret it.

If the lever markings look reversed, the meter settles it: whichever contact opens the coil path when pressed is stop, whatever its color.

Then trace the coil circuit of the main contactor. The conventional layout runs control supply, stop contact, start contact with a normally open auxiliary contact of the main contactor wired in parallel across it, the overload trip contact, and A2. That parallel auxiliary is the holding path that keeps the coil energized after you release start — but only its traced endpoints prove that role; the NO marking never does. If nothing parallels the start contact, the circuit is held some other way, and you find that way before calling the panel wired.

Check the motor nameplate against the supply #

The traced wiring only makes sense for a motor wound for the scheme. Worked example: the supply is 400 V three-phase and the nameplate reads 400 V delta, 690 V star. Delta run mode puts the full line voltage across each winding; star start mode puts 400 V ÷ 1.732 = 231 V across each winding, which is 231 ÷ 400 = 58 percent of rated, so torque and current in star are about 0.58² = 0.33 of the direct-on-line values. A nameplate reading 400 V star instead describes windings rated 231 V, which cannot carry the line voltage in delta: that motor can never be star-delta started on this supply, and the panel was built for a different motor.

The decision your tracing gives you #

  • Six motor conductors, one contactor collecting three winding ends, one cross-connecting them: a confirmed star-delta starter. Assign main, star and delta roles exactly as traced, never by position in the lineup, and before it runs confirm that the star and delta contactors are interlocked mechanically and electrically — their overlap short-circuits the windings, which is the failure behind why open transition wye-delta starters burn delta contacts.
  • Three motor conductors, or a fixed link plate at the block: not star-delta but a direct-on-line starter, and identifying unknown terminals on a NEMA size 1 motor starter is the closer guide.
  • A coil rated outside the band your control supply can hold it in: fit a coil rated for that supply before the panel is energized; do not feed a mismatched coil from whatever tap is nearest.
  • A latching button with no electrical holding path: treat it as a mechanically held starter and get the maker's diagram; do not improvise a coil circuit around the latch.
  • Whatever you reconstruct, the finished circuit still has to satisfy Article 430 of NFPA 70, the National Electrical Code, 2023 edition — a disconnecting means, a controller and overload protection — as the authority having jurisdiction applies it and the motor documentation requires.

With the photographs, the conductor tags and these five decisions, the panel goes back together as a circuit you can defend terminal by terminal.

Questions asked

Can the wire colors identify the terminals on an old panel?

Not reliably. Colors were never consistent between makers, countries or decades, and a repaired panel can carry two generations of wiring in one loom. Use a color only to follow a conductor you have already identified along its route. Identification comes from the component each conductor lands on and what the meter reads with the circuit isolated, never from the insulation.

The coil reads open between A1 and A2. Is the whole contactor scrap?

The coil is. With the probe resistance accounted for, an open reading between A1 and A2 means a broken winding, and the contactor will never close electrically. The power contacts may still be serviceable, so fit a replacement coil with the same rated voltage and frequency before judging anything else about the starter.

How many conductors must run to the motor in a star-delta scheme?

Six power conductors, one per winding end, plus the protective conductor. Count them at the terminal block and again at the motor, because the protective conductor, heaters or sensors can share the cable route and inflate the count. Six power conductors that trace back through the contactors are the physical signature the scheme cannot work without.

Can I test the button logic with the motor disconnected?

Yes, once tracing is complete and the panel is closed up. Lift the six motor conductors off the terminal block while the panel is dead, restore only the control supply, and press start: the main and star contactors should close, and at transition the star contactor should open before the delta contactor closes. Wrong order, or both closed together, points at interlock or transition wiring to correct before the motor is reconnected.

Keep reading

  • How-to

    Wiring overload relay contacts to the coil and the PLC

    The overload relay's NC trip contact (95-96) belongs in series with the contactor coil so a trip drops the motor out even while the PLC still commands run; the NO auxiliary (97-98) is a separate status input to the PLC. A PLC input is not overload protection, because no general-purpose controller input is a listed motor overload device, so a panel wired the other way needs rewiring.

    Motors and motor starters

  • Troubleshooting

    Overload relay placement in a wye-delta starter circuit

    In a wye-delta starter, put the overload relay in the three line conductors feeding the main contactor and set it from the motor nameplate full-load current. Use the 58% (FLA ÷ √3) setting only after you confirm the relay sits in series with the delta windings. Add no fuses or overloads on the second lead set: trace what M2 and M3 switch first.

    Motors and motor starters

  • Troubleshooting

    Why a motor starter coil has voltage but won't pull in

    Voltage across A1 and A2 with no current flowing proves only that the wiring is intact, not that the coil can pick up. Log the coil voltage during the failed closing attempt: most of these faults are a supply or wiring sag below the coil's pickup window, or a latched overload state that the reset button does not clear. Replace the starter only when the voltage stays inside its window and the unit still refuses to close.

    Motors and motor starters