Short answer

In a wye-delta starter, put the overload relay in the three line conductors feeding the main contactor and set it from the motor nameplate full-load current. Use the 58% (FLA ÷ √3) setting only after you confirm the relay sits in series with the delta windings. Add no fuses or overloads on the second lead set: trace what M2 and M3 switch first.

On this page
  1. Six leads do not identify the starter
  2. Where the overload relay goes
  3. Example: setting both relays for a 30 A mixer motor
  4. Why the second lead set gets no new devices
  5. Trace the circuit before you set anything
  6. What the current transformer on the power meter does
  7. Open transition, closed transition, or a soft start
  8. Questions asked

Where protection goes in this starter comes down to one question: which current does each device actually sense? Put the overload relay in the three conductors that carry full line current — upstream of the point where the delta contactor branches off — and set it from the motor nameplate full-load current. Use the 58 percent (FLA ÷ √3) setting only when the drawing proves the relay sits in series with the delta windings. Add no fuses and no overload relay to the second lead set, the one switched by the M2 and M3 contactors, until you have traced it; six leads on a mixer can belong to a two-speed connection just as easily as to a wye-delta starter. And the current transformer marked CT-3 feeds the power meter: a meter measures, it does not protect.

Six leads do not identify the starter #

Manufacturers build the wye-start/delta-run scheme around six-lead, single-voltage motors: three winding starts fed from the supply through the main contactor, three winding ends bridged into a star for starting and crossed into delta for running. Starter connection diagrams published for these motors show exactly that arrangement, for six-lead single-voltage and 12-lead dual-voltage machines alike.

But a Dahlander two-speed motor also brings out six leads through interlocked contactors, and its windings select speeds rather than a start-then-run sequence. Read the nameplate connection marking and the terminal-box diagram, then follow every conductor from the supply through each contactor to the motor leads. If the contactors bridge a star point and then re-cross the winding ends, you have a wye-delta starter and the rest of this article applies. If they select two separate windings, stop and size protection for each speed's own rated current instead. While the contactors are out, confirm the mechanical and electrical interlocks that keep the star and delta contactors from closing together — the whole scheme depends on that interlock surviving the swap.

Where the overload relay goes #

Locate the delta tap-off point on the drawing: the node where the delta contactor picks up current for the winding ends. In the common scheme the delta contactor branches off ahead of the main contactor, so everything between the branch-circuit device and that tap carries full line current in both the wye start and the delta run, while everything between the tap and a winding carries winding current — the line current divided by √3, or 0.577 of it. The relay setting must match what its sensing elements actually sit in:

Relay location Current sensed Setting basis
Line conductors, upstream of the delta tap Full line current in both states Nameplate FLA (delta connection)
In series with the windings, inside the delta loop Winding current = line current ÷ √3 0.577 × FLA
On the switched winding ends at M2 and M3 Winding current in one running state only Not a protection point

NFPA 70, the National Electrical Code, 2023 edition, covers motor circuits in Article 430: Part III limits a separate overload relay to 125 percent of nameplate full-load current for a motor with a service factor of 1.15 or higher or a nameplate temperature rise of 40 °C or less, and 115 percent otherwise; Part IV, through 430.52 and Table 430.52, governs the branch-circuit short-circuit and ground-fault device at the head of the circuit. Confirm the percentages and the device sizing against your edition and local amendments with the authority having jurisdiction and against the starter documentation. How a nameplate figure becomes a dial position is the same in both locations: Setting overload relays from motor nameplate full-load current covers it.

Example: setting both relays for a 30 A mixer motor #

Worked example, with hypothetical inputs: a 460 V, three-phase, 60 Hz mixer motor, continuous duty, service factor 1.15, nameplate full-load current of 30 A in the delta connection.

Line-side relay. The sensing elements sit upstream of the delta tap, so they carry the full 30 A in both states. The Article 430 cap for this motor is 125 percent of that: 30 A × 1.25 = 37.5 A. Set the dial no higher than 37.5 A and pick a relay whose range puts that value mid-scale.

Inside-delta relay. The elements sit in series with the windings, so each carries 30 A ÷ 1.732 = 17.3 A of winding current at rated load. Apply the same 125 percent factor to the current the relay senses — the method relay sizing guides use for inside-delta placement: 17.3 A × 1.25 = 21.6 A maximum setting.

Both results are estimates: verify them against the relay and starter documentation and the governing edition before the job closes out. A mixer is a high-inertia load, so check the trip class against the measured acceleration time as well — Setting overload relays for high-inertia motor starts walks through that choice.

Why the second lead set gets no new devices #

In the classic scheme, M2 and M3 are the star and delta contactors. Their leads end at winding ends; the same three windings carry every ampere the motor draws. Article 430 requires no fuses on those leads — the branch-circuit device Part IV demands already sits at the head of the circuit — and adding them creates a failure mode: a tie that opens inside a running delta leaves the remaining windings carrying the load unbalanced, the exact damage an overload relay exists to trip on. An extra overload on those leads senses current in only one running state and nothing in the other, so it protects nothing reliably.

The decision: no fuses and no overload on the M2 and M3 leads. Trace what they switch before the contactor swap anyway, because if the six leads turn out to be a speed-selection arrangement rather than star and delta, the settings change for each speed.

Trace the circuit before you set anything #

  • De-energize first: lock out, tag, and test for absence of voltage at the starter and the motor terminal box before opening either. NFPA 70E, 2024 edition, governs energized work; tracing a live panel is not part of this job.
  • Follow the three supply conductors from the disconnect through the branch-circuit device, the overload relay, and the main contactor, marking each point.
  • Locate the delta tap-off point and record which side of it the overload relay sits on: upstream means the nameplate basis, downstream means the inside-delta basis from the table.
  • Compare the terminal-box lead destinations with the motor connection diagram: winding starts, winding ends, the star bridge, and the three delta cross-ties.
  • Read the nameplate for the delta-connection full-load current, the service factor, and the temperature rise — the three inputs the settings depend on.
  • Confirm the star and delta contactors cannot close together: mechanical interlock fitted, electrical interlock wired and proven with the contactors racked out.
  • After restoring power, clamp each line in the delta run and compare the reading against the setting before calling the job done.

What the current transformer on the power meter does #

The transformer marked CT-3 provides the current reference for the power meter, which multiplies voltage by current to produce watts. It opens nothing and carries only a secondary circuit; it is neither an overload relay nor short-circuit protection, and a meter alarm is monitoring, not the protection Article 430 requires. If the mixer runs one CT on a deliberately balanced load, confirm the meter's documentation lists single-CT wiring as a supported configuration, and check the secondary polarity and the meter's programmed mode before trusting the kilowatt readings.

Open transition, closed transition, or a soft start #

Open-transition starters drop the motor entirely for a moment between star and delta. If the rotor's residual voltage meets the incoming line out of phase, the reconnection draws a current peak well above the starting current; starter manufacturers document that spike and its effect on breakers, contactors and couplings, and closed-transition starters bridge the gap with resistors for exactly this reason. If the mixer trips at the instant of transition rather than during acceleration, check the transition timer and contactor sequencing before touching any setting.

Since the contactors are being replaced anyway, weigh a soft starter or a drive: one device replaces the three-contactor bank, removes the transition step entirely, and sets its electronic overload directly from the nameplate current. If the motor may later run from a drive, the starter's contactor scheme must never sit between the drive output and the motor, and the six leads get reconnected for full-voltage delta — the wye-delta motor connection on a 480 V wye VFD system page covers that connection and its checks.

Either way the decision stands: set the relay to match the current its own path carries, and leave the second lead set bare.

Questions asked

Why 58 percent and not half the full-load current?

In delta run each line conductor feeds two windings whose currents are 60 degrees apart, and the phasor sum makes the line current 1.732 times a single winding current. A winding therefore carries 1 ÷ 1.732, about 0.577, of the line current, which is why a relay inside the delta loop sees roughly 58 percent of what a line-side relay sees. The nameplate full-load current is line current for the delta connection, so the inside-delta basis is that nameplate value divided by 1.732.

Does an inside-delta overload still protect the motor during the wye start?

Yes. During the wye start the same conductors carry the starting current, and each winding sees about one third of the delta-connection locked-rotor current. The relay senses continuously; the 58 percent figure is the running basis for the setting, not a starting current value. What matters for the start is the trip class: confirm the relay's class covers the measured or documented acceleration time so a normal start does not nuisance-trip it.

How are the three contactors in a wye-delta starter sized?

In the common scheme the delta contactor branches off ahead of the main contactor, so the main and the delta contactors each carry winding current rather than full line current, and starter manufacturers size both from their own tables for that duty. The star contactor conducts only during the start, at about one third of the delta-connection locked-rotor current, and is rated for short-time duty. Use the starter maker's rating table for the motor's output rather than judging from the old hardware's frame sizes.

Can the power meter take over the overload protection?

No. The current transformer and meter form a measurement circuit: the meter can display, log and alarm on current, but it opens nothing. NFPA 70 requires motor overload protection that disconnects the motor from its supply, so the overload relay stays and its trip contact drops out the contactor coils. Treat the meter as an early-warning and energy-logging tool that backs up the relay, never as the protection itself.

Keep reading

  • How-to

    Wiring overload relay contacts to the coil and the PLC

    The overload relay's NC trip contact (95-96) belongs in series with the contactor coil so a trip drops the motor out even while the PLC still commands run; the NO auxiliary (97-98) is a separate status input to the PLC. A PLC input is not overload protection, because no general-purpose controller input is a listed motor overload device, so a panel wired the other way needs rewiring.

    Motors and motor starters

  • Selection guide

    Selecting overload and jam protection for a reversible motor

    Set a bimetallic or electronic overload relay from the motor's nameplate full-load current — never from wattage — and give the electronic-clutch trip to a separate current-sensing jam or shock relay set above the highest normal process current. Its adjustable reset delay must outlast the cycle timer's worst-case command drop-out, and auto reset needs a deliberate-restart decision because a live run command restarts the motor.

    Motors and motor starters

  • Troubleshooting

    Why neutral-side switching trips a smart DOL starter

    Move the direction changeover contactor to the line side so the starter feeds the selected winding directly, and leave the run capacitor between the CW and CCW terminals: in the tested 110 V, 2.6 A circuit that raised successful starts from about 1 in 20 to 19 in 20. Return-side switching lets capacitor charging current through the unselected winding distort the current the starter measures at closure, so its residual-current diagnostic reports a missing path.

    Motors and motor starters