Troubleshooting
Why open transition wye-delta starters burn delta contacts
Short answer
The delta contactor does not close harder on the bad starts; the open-transition reconnection strikes the just-closed contacts with a current spike that changes with each start. The 120 A line current gives a 69.3 A steady branch current, but the make lands in the hundreds of amperes. Prove the transition sequence on a recorded trace, size both main contactors equal, and close the transition if the spike persists.

On this page
- Why does one start slam the delta contacts and the next start close softly?
- Can the transition current spike pull the contacts shut harder?
- What actually burns the delta contacts?
- How much current are the delta contacts really switching?
- Does a 40 hp starter on a 50 hp motor explain the burnouts?
- How much gap does the starter need between wye opening and delta closing?
- What is the fix that actually stops the burnouts?
- Questions asked
A contactor that slams shut on some starts and lands softly on others is not changing its mechanical force. The coil and magnetic circuit fix the closing force, and they repeat start after start; what repeats imperfectly is the electrical make, because an open-transition wye-delta starter reconnects the motor at a different point of the supply wave every time. On roughly one start in three, the delta contacts touch while the motor's decaying EMF sits far enough out of phase with the supply to strike an arc through the normal contact bounce, and that is the burnout you are seeing. The supplier's square-root-of-three math is correct for steady running and says nothing about the make event. The checks below separate the two, and the fix is sequencing and sizing, not a stronger contactor.
Why does one start slam the delta contacts and the next start close softly? #
Closing force does not change from start to start: it is set by the coil and the magnetic circuit, identical every time; what varies is the voltage across the delta poles at the instant of touch, because the transition lands on a different point of the supply wave.
A contactor is a solenoid. Coil voltage drives current, the core and armature complete the magnetic path, and the pull is fully developed before the main contacts touch, because touch is the final step of the armature stroke. The load conductors have no way into that magnetic path — the coil-and-core system is magnetically closed, so a current transient in the motor circuit cannot add force to the armature. A mechanically failing contactor would slam on every start or on none; it cannot sample the load and pick one start in three.
What does vary start to start is the point on the supply wave where the poles touch, the magnitude and phase of the motor's residual EMF at that instant, and how long the contacts bounce afterward. Those three make each transition a lottery, and damage on roughly one start in three matches an unlucky intersection of touch point and residual voltage far better than it matches a mechanical fault.
Can the transition current spike pull the contacts shut harder? #
No — the coil current alone builds the magnetic pull, and motor current cannot flow until the contacts touch, so a reconnection spike arrives too late to add any force; what it feeds instead is a violent arc into the normal bounce.
The burning current flows in the main circuit, not the coil circuit. Until the delta poles touch, no load current passes through them, and by the time the spike exists the armature is already seated, so there is no mechanical story in which the spike closes the contactor harder. What the spike does is feed the bounce: every make bounces the contacts apart by a fraction of a millimeter, harmless when the first-touch current is tens of amperes, destructive when it is hundreds and the voltage across the just-separated gap sustains an arc. Arc pressure and molten bridge material inside the contact chamber also produce a bang that reads as a violent mechanical close. Record coil voltage and line current on one time base and the armature motion will look identical on good and bad starts while the current at touch differs by an order of magnitude.
What actually burns the delta contacts? #
The open-transition reconnection burns them: during the dead interval the motor coasts on its decaying EMF, out of phase with the supply, published analyses put that voltage difference above 1.5 times line voltage, and the resulting current spike lands at 1.5 to 2 times a full-voltage start.
During the dead interval the wye contactor has opened, the motor floats on its decaying flux, and the rotor keeps turning just short of synchronous speed, so the residual EMF slips in phase relative to the supply. The voltage across the closing delta poles is the vector difference between supply and residual EMF, and with an unlucky phase angle that difference exceeds 1.5 times line voltage — on this 208 V supply, more than 312 V across contacts that are touching and bouncing. Two factors set how bad it gets. A transfer fired before the motor is near full speed leaves a large EMF and a large slip, and that multiplies the spike. And the reconnect point moves along the supply wave from start to start, which is what makes the damage intermittent. The same event family appears as contactor contact melting on a high-speed transfer and as a star-delta starter breaker that trips at transition; your burned delta contacts are the contact-level version of it.
How much current are the delta contacts really switching? #
Two currents matter, and the sizing argument covers only the smaller one: the steady inside-delta branch current on this motor is 120 A divided by the square root of 3, which is 69.3 A, while the current at the make lands in the hundreds of amperes.
Worked example: the nameplate reads 200 V, 50 hp, three-phase; the supply measures 208 V; the arithmetic is independent of supply frequency.
I_branch = I_line / sqrt(3)
I_branch = 120 A / 1.732 = 69.3 A
That branch value is the continuous current each delta pole carries in the delta run, and it is the entire basis of the supplier's 70 A argument. It is not the current at the make. At the delta make, each winding suddenly sees full line voltage with the rotor just short of synchronous speed, so the winding current heads toward its locked-rotor value. Assuming a locked-rotor current of 6 to 8 times the winding's rated current — an assumption to replace with the motor's locked-rotor data or the captured trace — each delta pole makes into:
69.3 A × 6 = 416 A
69.3 A × 8 = 554 A
before the first-half-cycle penalty from the phase displacement described above. Treat these as estimates for the selection check; the governing numbers are the motor's locked-rotor data and your own recorded trace.
| Quantity | Value | What it decides |
|---|---|---|
| Motor nameplate | 200 V, 50 hp, three-phase | the duty the selection must match |
| Supply | 208 V | the applied voltage used in the rating tables |
| Full-load line current | 120 A | the input to the branch calculation |
| Steady delta branch current | 69.3 A | continuous duty of the delta poles in the run |
| Estimated make current per delta pole | 416 A to 554 A | the making duty the frame must survive |
| Starter as supplied | 40 hp, 105 A | steady margin says nothing about the make |
Does a 40 hp starter on a 50 hp motor explain the burnouts? #
Not by itself: IEC contactor ratings are currents and duty categories, not only horsepower, so the 105 A frame may hold in steady run yet still fail at the make if its utilization category and making capacity were never checked against this transition.
The horsepower label is a shortcut for current at a stated voltage, and the ratings that decide this failure sit one level below it. IEC 60947-4-1, 2018 edition, the product standard for low-voltage contactors and motor starters, sorts switching duty into utilization categories: AC-3 covers starting a squirrel-cage motor and switching it off once it is at speed, while AC-4 covers starting, plugging and inching, where the contactor makes or breaks against a motor that is still generating voltage. The standard verifies making and breaking capacities at 8 times the rated operational current for AC-3 and 10 times for AC-4, so no contactor is qualified by its steady current alone. An open-transition delta make against a live residual EMF is AC-4-like stress landed on a frame that was picked, at best, by its AC-3 steady current.
Work the selection in this order. Many contactor manufacturers publish a separate rating column for inside-delta wye-delta duty, because the delta position carries branch current and makes against reconnection events a direct-on-line column never sees: select from that column at the applied voltage, and compare its stated making capacity with the estimated make current from the example above. The steady comparison passes on paper exactly as the supplier argued — the delta poles carry 57.7 percent of line full-load current and the wye shorting contactor about 33 percent — but the make comparison is the check that has been missing, and it is where this selection fails. Confirm the category and the numbers in the manufacturer's data for the exact contactor, and confirm installation requirements with the authority having jurisdiction; the inside-delta wiring also changes what the overload relays carry, covered in overload relay placement in a wye-delta starter circuit.
So the 40 hp frame on a 50 hp motor proves nothing by itself; the unverified make duty is what has been burning the contacts.
How much gap does the starter need between wye opening and delta closing? #
Long enough that the wye contacts are fully open and their arc is out before the delta contacts touch; in practice the transfer timer lands near 50 ms, and the number that decides the repair is the measured gap on a captured trace, not the timer dial.
The measured gap is the wye contactor's drop-out time plus its arc duration plus the delta contactor's pick-up time, and in a healthy starter that chain lands near 50 ms. Two hardware features exist to guarantee the order: the mechanical interlock keeps the two armatures from moving together, and the electrical interlock — the wye auxiliary contact wired in series with the delta coil — keeps the delta coil from energizing until the wye contacts are mechanically open. Assume neither works and prove both on the trace; if the delta poles touch while the wye path still conducts, the wye short sits across energized delta windings and the current is limited by almost nothing.
The second timing decision is transfer speed. The acceleration timer must let the motor reach close to full speed before the transfer: an early transfer leaves high residual EMF and high slip, produces the worst spike of the whole sequence, and adds a mechanical jerk the driven machine feels. A late transfer only lengthens the start; it does not hurt the contacts.
What is the fix that actually stops the burnouts? #
Fix the transition, then the sizing: make the two main contactors equal, prove the wye-opens-before-delta sequence on a recorded trace, move the transfer to full speed, and if the spike survives all that, change to a closed-transition starter rather than chasing a bigger frame.
Work the list in order; each step either finds the fault or clears it.
- De-energize, lock out and verify absence of voltage at the starter before opening it — NFPA 70E, 2024 edition, covers electrical safe work practices including the verify-de-energized step, and your site procedure and the authority having jurisdiction govern the rest. Then inspect the delta contacts and photograph the erosion pattern.
- Pull the contactor data: the inside-delta and direct-on-line AC-3 ratings at the applied voltage, the making and breaking capacities, the utilization category, and the permitted operating cycle. The comparison that matters is against the make current, not the steady branch value.
- Record a series of starts on one time base: the three line currents with clamps rated for at least ten times the motor's rated line current, the delta coil voltage, and the wye and delta auxiliary contact states. The bad start is intermittent, so capture enough of them to catch it.
- Read the traces against the sequence: wye current at zero, a clear gap you can measure, then the delta make. Overlap, or a gap too short to measure, makes the interlock and the transition timer the first fault to repair.
- Move the transfer to full speed. If the acceleration timer fires early, every later check happens on top of the worst spike the starter can produce.
- Re-select, do not just upsize: both main contactors the same frame, each chosen for inside-delta duty at the applied voltage, making capacity above the measured make current, operating cycle above your starting frequency with margin. Equal frames remove the marginal selection; the wye contactor carries less in the run, but its duty is a start, and the symmetry is worth more than the savings.
- If the measured spike still exceeds every frame the duty justifies, specify a closed-transition starter: transition resistors and one extra contactor hold the motor connected through the interval, so the phase jump and the spike never occur.
The decision, case by case: overlap or a gap too short to measure — repair the interlock and the transition timer before anything else; transfer below full speed — move the acceleration timer later and retest; make current above the frame's making capacity — re-select both main contactors equal for inside-delta duty; sequence correct and the make still destructive — closed transition is the fix, and a bigger frame is not.
Questions asked
Would a bigger delta contactor alone stop the burning?
No. A larger frame adds making margin and shrugs off bounce better, but it does not remove the reconnection spike that is eroding the contacts, and a marginal transition will burn a bigger frame too, only more slowly. Fix sequence and transfer speed first, then size both main contactors equal for inside-delta duty, and use closed transition if the measured make current still exceeds the frame's making capacity.
How does a closed-transition starter remove the spike?
It never lets the motor float. Transition resistors and one extra contactor bridge the windings for the short interval between wye and delta, so the motor keeps a reduced-voltage connection and its EMF stays in step with the supply. The voltage difference at the delta make collapses, and with it the spike; the cost is the resistor bank, the extra pole and the extra interlock wiring.
What coil voltage problem can mimic a violent close?
A sagging or marginal control voltage. Most contactor coils are specified to pick up and hold across roughly 85 to 110 percent of rated control voltage; below that the armature creeps in, bounces on weak holding force and arcs at every start. Measure the delta coil voltage at its terminals during real starts, on several starts, and compare it with the coil's rated control voltage before accepting the transition as the only cause.
How many starts per hour can a wye-delta starter handle?
Whatever the contactor manufacturer's operating-cycle table allows at the current you are actually switching — that table decides it, not a rule of thumb. Count the starts per hour at peak duty, compare the number with the permitted cycle for the frame at the measured make current, and select a category and frame that cover that duty with margin; frequent elevator starting is exactly the duty that turns a marginal make into repeated burnout.

