Troubleshooting
Why a contactor contact melts on high speed transfer
Short answer
A contactor pole that melts during the low-to-high speed transfer is usually hammered by coil chatter from a dipping control supply or by an unverified winding transition, not by an undersized frame. Record the coil voltage synchronized with all three phase currents across one transfer before buying a larger contactor: a coil that falls into its drop-out band, or a contactor that closes onto a live winding, will melt the next frame too.
On this page
- What a melted pole at transfer means
- Check the coil supply before anything else
- Verify the low-to-high transfer sequence
- Rule out a one-pole connection fault
- Example: how far a 120 V coil dips at the high-speed start
- The recorded transfer test that decides it
- When a larger frame is actually the answer
- Questions asked
A contactor pole that melts during the low-to-high speed transfer is not telling you the frame is too small — it is telling you the closing event went wrong. On this 200 hp two-speed motor, three size 5 contactors have failed the same way, each after roughly five to six weeks, and that repeat pattern points to two causes in order: coil chatter from a control supply that dips when the high-speed winding energizes, then an unverified transfer sequence that lets the high-speed poles close onto the wrong electrical state. Both hammer the contacts with arcs at starting surge, and the weakest pole melts first. Record the coil voltage synchronized with the three phase currents across one transfer before buying a fourth contactor — the trace decides between a supply fix, an interlock fix and a frame change.
What a melted pole at transfer means #
Contact heating follows I²R: heat at the contact interface scales with the square of the current through it. The reported running currents — about 64 A on low speed and 223 A on high speed — describe steady operation, which a healthy size 5 carries without complaint. The damage happens in the seconds of the transfer, because closing onto the high-speed winding means making the motor's starting surge, and why an induction motor draws heavy current at starting covers why that surge runs several times the running current. Every bounce or re-make under that surge strikes an arc that erodes contact material, so chatter turns one closing into dozens of making events. A pole melted at transfer was melted in that window, not by weeks of steady running — which is also why replacing the contactor without changing the closing conditions only restarts the same clock.
Check the coil supply before anything else #
Vibration greater than normal while pulled in is the symptom to chase first. An AC armature that never fully seats holds with a small air gap, draws extra coil current and releases easily, so any dip in the control supply drops it out and lets it pick up again — and each drop-out under load current is an arc at the contacts. AC coils commonly release somewhere around 70% of nominal coil voltage; confirm the figure for your coil in the manufacturer's data, but treat that level as the working threshold for chatter.
Measure across the coil terminals during a real start, not at the control panel. A reported 3-4% drop at the MCC bus is exactly the sag a control transformer feeds straight into its coil, and locating the contactor inside the MCC does not rule the dip out — the drop between that bus and the motor terminals, 85 ft of cable away, is unmeasured and the starting surge multiplies it.
With the starter isolated, inspect the magnetic circuit too: corroded or damaged pole faces, a cracked shading ring, armature binding and, on a DC-operated or rectified coil, the suppression diode and the coil marking. A broken shading ring is rare; dirty pole faces are not. The chatter-from-a-dipped-supply mechanism is worked end to end in fixing AC contactor chatter on a loaded 80 HP motor start, and the coil-side checks continue in why a motor starter coil has voltage but won't pull in.
Verify the low-to-high transfer sequence #
A timer command is not proof that the low-speed contactor has opened. Until the contact states are proven with the recorder, the sequence is unverified, and two different failure shapes are possible:
- Low speed stays energized through the delay, and the high-speed contactor closes onto winding connections that are already live from the other contactor. The current the closing poles make is then set by the overlap between two sources on one winding, not by the motor's normal start.
- Low speed opens first and the 30 s delay leaves the motor coasting, so the high-speed contactor closes onto a spinning, partially magnetized motor whose surge depends on how far the speed has decayed.
Which sequence applies comes from the actual drawings: two-speed motors use different winding arrangements, and the required contactor order must be read from the motor's connection diagram and the starter prints, not assumed. Check the electrical interlock — the low-speed auxiliary contact in the high-speed coil circuit — and the mechanical interlock between the two armatures. Because the motor has been rebuilt, match its leads to the approved diagram and confirm balanced phase current at both speeds; a misidentified lead set on a rebuilt two-speed winding produces exactly this kind of wrong-connection surge.
Rule out a one-pole connection fault #
With the starter isolated and verified dead, work the failed pole on its own. Heat concentrated at a lug or in the conductor end points to a termination problem; erosion and melting at the contact faces point to arcing or low contact force. After repairs, compare the closed-pole voltage drop across all three poles at comparable current — a pole that drops noticeably more than its neighbours carries extra resistance and will cook first. Check the contact-pressure springs and the armature seating on that pole as well, because a pole that rides slightly open under load does the same resistive-heating damage chatter does, concentrated on one phase.
Example: how far a 120 V coil dips at the high-speed start #
The inputs, and where each comes from:
- Nominal coil voltage of 120 V — an illustrative assumption for a control-transformer coil fed from the MCC bus; read the coil marking on your own starter before substituting your numbers.
- Voltage drop at the MCC bus at high-speed running current — reported as 3-4%, midpoint 3.5% used here.
- Starting surge — 6 to 8 times running current, the range commonly used for an across-the-line induction motor start.
- Coil release point — about 70% of nominal voltage, the level where an AC armature commonly drops out; confirm against the coil manufacturer's data.
The rule: if the feeder impedance stays roughly constant over the few seconds of the surge, the voltage dip scales with current, so the dip during the start is the running dip multiplied by the surge ratio.
The arithmetic:
- At 6 times running current: 6 × 3.5% = 21% dip, so the coil sees 120 V × (1 - 0.21) = 94.8 V, and 94.8 ÷ 120 = 79% of nominal.
- At 8 times: 8 × 3.5% = 28% dip, so the coil sees 120 V × (1 - 0.28) = 86.4 V, and 86.4 ÷ 120 = 72% of nominal.
The result: at the top of the surge range the coil sits at 86.4 V — 72% of nominal, inside the band where AC armatures release — and that is before any added drop in the control wiring, the control transformer's own regulation or a low pilot contact. The result is an estimate; the recording is the proof. If the trace shows the coil falling to about 70% of nominal or below during pickup, this melt is a supply problem: feed the coil from its own control transformer on a bus the start does not sag, and keep the installed frame.
The recorded transfer test that decides it #
Two recorder channels and one clean transfer separate the three causes:
- De-energize the starter, lock out and tag, and test for absence of voltage on the line and load sides before opening any cover or touching the pole assembly.
- Inspect the failed pole, its termination, the contact-pressure springs, the armature and pole faces, and the interlocks; read the motor nameplate, the connection diagram and the coil marking.
- Connect one channel directly across the high-speed coil terminals and current channels on all three motor phases, set the instrument to resolve individual pickups and dropouts in milliseconds rather than averages, and use leads and instruments rated for the measurement category of the points they attach to.
- Re-energize and record a complete low-to-high transfer under representative load. This is energized work: NFPA 70E, 2024 edition, covers the electrical hazard controls for such work — confirm what your local authority having jurisdiction and the equipment documentation permit before you proceed.
- Read the trace against the thresholds above: a coil falling into its release band during pickup, phase current that interrupts and re-makes, or a making current far beyond the winding's own start each name a cause.
- Keep the recorder on every transfer for at least one full shift of production, because a fault that fires every few weeks does not necessarily show on the first start after a repair.
The trace decides the repair: a dipping coil is a supply fix, an overlap in the contact states is an interlock fix, and a clean coil with a proven sequence and a pole still melting at pickup is the only evidence that moves you to a frame change.
When a larger frame is actually the answer #
Three contactors failing the same way on a schedule is a systematic cause, not a defective device, so the frame change comes last and only on evidence. The number to match is not the running current but the making current the contacts see at pickup: in IEC AC-3 duty, the utilization category used for squirrel-cage motors, a contactor's making current is set at 2.5 times its rated operational current. Take the recorded making current and the transfer duty to the manufacturer's selection data for the specific device and check that the installed frame's making rating covers what the trace shows.
A size 6 selected that way is a sized remedy. A size 6 bought because the last one melted is the next failure in the making, because the coil's release point is a property of the coil, not the frame — chatter and an overlapping transition melt the larger device on the same schedule.
Questions asked
Can I hold the coil up through the dip instead of fixing the supply?
You can, but it treats the symptom. Ride-through on the coil circuit stops the chatter while the bus sags, yet it leaves an overlapping transfer unverified and can hold the poles closed through a condition they would otherwise interrupt. Fix the dip at the source or correct the interlock first; if ride-through is still needed afterward, coordinate it so the low-speed contactor still releases whenever the sequence calls for it.
Can I replace only the burned contact set?
New contacts restore the pole, but a pole that has melted can leave damage behind them: pitted pole faces on the magnet, a cracked shading ring, weakened contact-pressure springs and heat-stretched conductor ends. Inspect the whole pole assembly while the starter is isolated, or the fresh contacts run with reduced force and erode early. Replace the pole parts the inspection flags, not just the contact faces.
If the damage happens in seconds, why did failures come weeks apart?
Each bad closing removes a little contact material, and each arc leaves the face rougher, so the damage accumulates transfer by transfer until a pole can no longer carry running current without overheating. The weeks between failures measure how many damaging closings the pole survived, not a slow steady-state problem, and that is why the failure rate will not change until the closing event itself is corrected.
What instrument captures the coil voltage during a transfer?
A portable recorder or power-quality meter with at least two channels, voltage probes rated for the coil circuit's voltage and current clamps for the motor phases, sampling fast enough to resolve individual pickups and dropouts. A panel meter or a multimeter reading averages will show nothing, because the damaging events last milliseconds. Attach the voltage leads at the coil terminals themselves and keep the same setup for every trial.