Current IntelPower LibraryShop main store

Explainer

Why an induction motor draws heavy current at starting

Motors and motor starters Published 8 min read

Short answer

An induction motor draws five to eight times full-load current at starting because at standstill, with slip at 1, the rotor load resistance term R2'(1-s)/s is zero and only winding leakage impedance limits the current. The motor behaves as a transformer with a shorted secondary until slip falls near rated speed, and only starting methods that change voltage or frequency reduce it.

On this page
  1. What the equivalent circuit shows at slip 1
  2. Rotor frequency and why the current is mostly reactive
  3. Reading the locked-rotor number from the nameplate
  4. What the start does to the bus and the windings
  5. The fixes that work change voltage or frequency
  6. What does not fix it
  7. The decision
  8. Questions asked

An induction motor draws heavy current at starting because at standstill it is electrically a transformer with a shorted secondary. Slip is 1, so the rotor's load resistance term R2'(1 - s)/s is zero, and the only impedance left in the circuit is the leakage reactance and resistance of the stator and rotor windings. Locked-rotor current typically runs five to eight times full-load current and stays near that value until the rotor approaches rated speed. That current is a property of the machine, not a fault, and only starting methods that change the applied voltage or frequency reduce it.

What the equivalent circuit shows at slip 1 #

In the per-phase equivalent circuit the stator contributes resistance R1 and leakage reactance X1, the magnetizing branch carries the flux-producing current, and the rotor branch (referred to the stator) carries R2', X2' and a speed-dependent resistance R2'(1 - s)/s that stands for the power converted to shaft power. At the instant of energizing, speed is zero and slip is 1, so that resistance is zero, nothing converts to mechanical power, and no speed-generated back-EMF opposes the supply. What remains is a transformer with a shorted secondary, and the locked-rotor current is:

I_start ≈ V_phase / √((R1 + R2')² + (X1 + X2')²)

A common explanation says the stationary rotor presents a high impedance. The opposite is true: standstill is the motor's lowest-impedance operating point, which is exactly why the current is highest there. As the rotor accelerates, (1 - s)/s grows and back-EMF builds, the effective impedance climbs, and line current falls toward the rated value.

Rotor frequency and why the current is mostly reactive #

The rotor circuit sees frequency f2 = s · f1. At standstill on a 60 Hz supply that is a full 60 Hz: the induced rotor EMF is at its maximum, the bars carry a large induced current, and the stator must supply the matching reflected current on top of its own magnetizing current. As slip falls, rotor frequency and induced EMF fall with it — illustratively, at 3% slip, f2 = 0.03 × 60 Hz = 1.8 Hz.

Standstill power factor is low, so most of that large current is reactive and delivers little torque per ampere until the motor climbs toward its pull-up and breakdown region. The current stays near the locked-rotor value through most of the acceleration and collapses only near rated speed, so the acceleration time — set by the driven inertia and the net accelerating torque — is how long the supply and the windings carry it. With the rotor held at five to six times full-load current, I²R losses in the windings run 25 to 36 times normal.

Reading the locked-rotor number from the nameplate #

The number for a specific motor comes from its nameplate: locked-rotor current, an Is/In ratio, or a NEMA locked-rotor kVA code letter from the scheme defined in NEMA MG-1. NFPA 70, the National Electrical Code (2023 edition), lists the band of locked-rotor kVA per horsepower for each letter in Table 430.7(B); confirm the marking and how you apply it against the motor documentation and the local authority having jurisdiction.

The letters run from A (0 - 3.15 kVA/hp) and B (3.15 - 3.55) up through J (7.1 - 7.99), K (8.0 - 8.99) and L/M (9.0 - 11.19), and small frames carry the higher letters: typical markings are L or M for 1.5 - 2 hp, K at 3 hp and J at 5 hp, with kVA per horsepower falling as horsepower rises in those rows. Convert the letter to amps for a three-phase motor:

I_start = (kVA/hp × hp × 1000) / (√3 × V_line)

Illustrative worked example — every input stated: a 3 hp, 460 V, three-phase motor, code letter K, nameplate full-load current 4.8 A.

  • Band low end: 8.0 kVA/hp × 3 hp = 24.0 kVA, so I_start = 24,000 VA / (1.732 × 460 V) = 24,000 / 796.7 = 30.1 A.
  • Band high end: 8.99 kVA/hp × 3 hp = 26.97 kVA, so I_start = 26,970 / 796.7 = 33.9 A.
  • Ratio to full load: 30.1 / 4.8 = 6.3 at the low end, 33.9 / 4.8 = 7.1 at the high end.

Use the high end when you check breaker instantaneous settings or voltage dip. Take the number from the nameplate rather than from a live measurement: a motor deliberately held at full voltage and standstill is being operated in a fault condition, and anything that opens the terminal box starts with lockout and a verified absence of voltage.

What the start does to the bus and the windings #

Two quantities decide whether a start is acceptable: the voltage on the motor and nearby buses while it lasts, and the heat deposited in the machine per start. The dip follows the start current against the impedance of the whole path:

ΔV = I_start × Z_path (per phase: source, transformer and cable)

The arithmetic with real source impedance is the one walked through in the motor starting voltage dip calculation on an 11 kV bus, and a start that lands on an already loaded feeder combines both motors' currents as in the second motor starting voltage drop calculation. For predicting how deep the sag will run from a known inrush, the method is estimating voltage sag from motor inrush current.

At constant frequency, torque scales with the square of the voltage ratio, so a deep dip slows the acceleration and the high current flows longer — the dip makes the heating worse. The motor's torque must exceed the load torque at every speed point between standstill and rated speed, not only at breakaway.

The fixes that work change voltage or frequency #

Every reduced-current method buys lower line current with torque or complexity, so compare methods against the load's torque demand, not only the current limit.

Method Line current during start Starting torque What to watch
Direct on line Full locked-rotor current Full Voltage dip and mechanical shock
Star-delta About one third of DOL About one third of DOL Six accessible terminals and a winding rated for delta at line voltage; current spike at changeover; not enough breakaway torque on loaded starts
Soft starter Set by the current limit and voltage ramp Falls with the square of the voltage ratio Torque shortfall on high-torque loads; long ramps heat the motor
VFD Set by the drive's current limit, near rated current if needed High torque at low frequency under V/f or vector control Drive and braking sizing, harmonics; torque at zero speed depends on the control mode

A soft starter ramps voltage only; a drive ramps frequency and voltage together, and holding the V/f ratio keeps the air-gap flux roughly constant — which is why a drive can produce useful torque at low slip while a voltage-only starter cannot. That difference decides whether a soft starter is adequate or a drive is justified. On a stiff utility bus, cutting the motor's current barely moves the bus voltage, as why a soft starter barely improves utility bus voltage dip shows; reduced-voltage starting pays off on a weak supply. When you choose the current limit, convert the starter's kVA rating to amps before comparing it with the motor's numbers — see converting a soft start kVA limit to starting current.

What does not fix it #

Adjustments that treat the current as a fault leave the cause in place:

  • Raising the overload or instantaneous setting hides the symptom and strips protection from a genuinely stalled rotor. Protection rides through the start by curve selection — trip class and a magnetic setting above the inrush peak — not by being desensitized for running current; why raising a magnetic overload setting won't fix a hard start works through that failure. A high-inertia load is the case that needs a longer trip class, never a higher setting: setting overload relays for high-inertia motor starts covers the choice.
  • Upsizing the motor. A larger frame draws more locked-rotor amperes; the ratio to its own full-load current stays in the same band, so the supply sees a bigger event, not a smaller one.
  • Upsizing only the cable. Lower cable impedance trims one slice of the voltage drop, but on a weak supply the transformer and source impedance dominate, and the winding and rotor heating are untouched.

The decision #

Commit per case, with the numbers in hand:

  • DOL stays if the calculated dip keeps every bus above the hold-in needs of its contactor coils, control-power supplies and running drives, and the protection coordinates through the inrush. The current is normal; nothing needs fixing.
  • If the dip is too deep and the load torque is low at low speed — an unloaded start, a fan, a centrifugal pump — fit a soft starter, set its current limit, and verify that torque at the reduced voltage still exceeds load torque at every speed point.
  • If the load demands high breakaway or constant torque, use a VFD. Star-delta's one-third torque will not break it away, and the changeover transient can rival the DOL event you were removing.
  • If the only symptom is nuisance tripping, change the curve, not the motor: a trip class that tolerates the acceleration time and a magnetic setting above the inrush peak — above 33.9 A in the worked example — while the running protection stays matched to the full-load current.

Questions asked

Is the first-cycle spike the same thing as locked-rotor current?

No. The locked-rotor current is the symmetrical current that persists while slip stays high. On top of it, the first few cycles carry an asymmetric offset set by where on the voltage wave the contactor closes, and it decays within a few cycles. Set a breaker's instantaneous element above the asymmetrical peak, not just the rms locked-rotor value, and use the high end of the code-letter band when the peak is unknown.

How long does the motor keep drawing near locked-rotor current?

Until slip falls to a few percent of rated speed. Current sits close to the locked-rotor value through most of the acceleration and collapses quickly near rated speed, so the duration equals the acceleration time set by load inertia and net accelerating torque. Check the permitted locked-rotor time and the starts-per-hour limit in the motor documentation, because repeated starts bank heat faster than the frame sheds it.

When is high starting current a fault symptom instead of normal?

When it lasts too long or refuses to fall near speed. Compare the start against the nameplate code-letter band and the documented acceleration time. A start that drags, a current that stays flat as speed builds, or a motor that hums without turning points to undervoltage, a single-phased supply, mechanical binding or an overloaded shaft, not to a motor that needs a bigger breaker.

Why does star-delta cause a second current spike at changeover?

At the transition the rotor is spinning below rated speed with residual air-gap flux whose phase no longer matches the line. When the delta contactor closes, the supply meets that internal voltage out of phase and the transient can rival a direct-on-line start. Closed-transition starters bridge the gap with resistors; open-transition designs do not, which is why the spike appears on the trace.

Can I measure locked-rotor current instead of calculating it?

Yes, with a blocked-rotor test at reduced voltage following the manufacturer's procedure; the measured leakage impedance scales to full voltage. It is a heating test by nature, since the rotor is deliberately held at standstill while losses run far above normal, so the procedure's voltage and duration limits are hard limits. For protection and dip checks, the nameplate calculation is normally sufficient.

Keep reading

  • How-to

    Estimating voltage sag from motor inrush current

    Do not divide the motor's asymmetrical first-cycle peak by √2; screen the dip with RMS locked-rotor current as dip % = transformer Z% × I_start ÷ I_rated. On a 750 kVA, 480 V, 6% transformer, a 50 HP motor at 395 A locked-rotor dips the bus about 2.6%, to roughly 467 V — start it across the line.

    Motors and motor starters

  • Troubleshooting

    Fixing AC contactor chatter on a loaded 80 HP motor start

    Chatter with the motor connected but a clean pull-in with the motor disconnected is the supply sagging under locked-rotor current; the 750 VA and external-outlet tests already cleared the control transformer. At 6x the 81 A label the start draws about 486 A on a 271 A transformer, so limit the start to roughly 270 A with a soft starter and verify the coil holds above 102 V.

    Motors and motor starters

  • How-to

    Motor starting voltage dip calculation on an 11 kV bus

    A starting medium-voltage motor dips the bus in proportion to its locked-rotor kVA against the source's short-circuit strength. Screen it as dip ≈ 100 × S_start/S_sc at the point of common coupling, then refine with ΔV = I_start(R cosφ + X sinφ) per phase. In the worked 11 kV, 1.5 MVA chiller example a direct-on-line start gives 3.6% at the PCC and 4.0% at the plant bus, failing a 3% limit; a 65% tap autotransformer or a soft starter limited to 3× rated current holds both points under 2%.

    Motors and motor starters