Selection guide
Measuring DC and AC motor current for a PLC without a VFD
Short answer
No. A fixed-speed motor that keeps its starter and overload relay gets PLC current feedback from a current transducer wired to an analog input, or from a communicating overload relay that reports over the network. A 12 V DC load needs a DC-capable Hall-effect transducer, because a current transformer cannot read steady DC.
On this page
- Do I need a VFD just to measure motor current in the PLC?
- What are the ways to get motor current into a PLC?
- What kind of PLC input does a current transducer need?
- How do I measure current on a device powered by 12 V DC?
- What current range should the transducer cover for the motor?
- How do I scale the signal into amps in the PLC?
- How is the transducer installed and wired?
- Does the current transducer replace the motor's overload relay?
- How do I prove the PLC reading is correct?
- Questions asked
No, you do not need a VFD to measure motor current for a PLC. A fixed-speed motor that keeps its contactor and overload relay gets current feedback from a current transducer feeding an analog input, or from a communicating overload relay that reports over the network. A drive earns its place by controlling speed; as a current meter it adds power-conversion hardware, a harmonics question and motor-cable constraints you never asked for. This article picks the sensing route, sizes the range, scales the signal into amps, and covers the 12 V DC load a current transformer cannot read at all.
Do I need a VFD just to measure motor current in the PLC? #
No. A motor that starts across the line and runs at full speed needs a sensing device, not power conversion: a current transducer feeding a PLC analog input, or a communicating overload relay, gives the current value without touching the motor-control method.
A VFD reports current because it must protect its own output stage while it converts frequency and voltage. That measurement comes bundled with hardware you would otherwise not buy: the power section, the input-filtering decision, the reflected-wave motor-lead limits and the commissioning time. For a motor that will always run at full speed, adding a drive purely to measure current is the long way around.
Keep the starter. Keep the overload relay. Add a sensor.
What are the ways to get motor current into a PLC? #
Three practical routes exist: a current transducer wired to an analog input, a communicating overload relay that reports current and trip data over a network, and a panel ammeter — which helps the PLC only if it has a retransmit output.
Separate three requirements before buying anything: local indication, a PLC measurement, and motor protection. A panel ammeter answers the first and only the first. The transducer answers the second. The overload relay already in the panel answers the third.
| Route | What the PLC receives | Protection included | Best fit |
|---|---|---|---|
| Current transducer, analog output | One conductor's current on a current loop or as 0–10 V | No | Fixed-speed motor keeping its existing overload relay |
| Hall-effect transducer | AC or DC current as an analog signal | No | The 12 V DC load, and mixed AC/DC duties |
| Communicating overload relay | Per-phase current, trip status and diagnostics over a fieldbus | Yes, when set from the motor nameplate | Panels where the overload relay is due for replacement anyway |
| Panel ammeter | Local reading only, unless fitted with a retransmit output | No | Operators who watch a gauge |
For the single-conductor AC case, the wiring details are laid out in measuring three-phase motor current for a PLC alarm input, which covers the transducer-to-channel path this article builds on.
What kind of PLC input does a current transducer need? #
An analog input channel — labelled AI on the module — configured to the transducer's output mode, which in practice means a 4–20 mA current input or a 0–10 V voltage input; digital inputs cannot read a proportional signal.
Identify the channel from the module markings and its documented signal ranges, not from the terminal count. Current mode and voltage mode are usually different terminal connections on the same card, so the channel configuration and the landing point must agree.
If the controller has no spare analog channel, the routes are an added I/O module, a communicating overload relay on the network, or adding a 4–20 mA sensor to a PLC without analog inputs through a signal converter. All three land the same number in the PLC; the choice is what your controller and cabinet already have room for.
How do I measure current on a device powered by 12 V DC? #
With a DC-capable transducer — a Hall-effect type (or a shunt with an amplifier): a current transformer cannot produce an output from steady DC, because a transformer only responds to changing flux, so the AC sensors above read nothing on that load.
Hall-effect transducers are active devices: they need an auxiliary supply, commonly 24 V DC from the same control-power source feeding the PLC, and the conductor passes through a window with no electrical connection to the 12 V circuit, which keeps the isolation intact.
Worked example, DC side. A 12 V DC load drawing 4 A at full duty, measured by a 0–10 A Hall-effect transducer with a current-loop output. At 4 A the signal is 4 mA + (16 mA × 4 A ÷ 10 A) = 4 mA + 6.4 mA = 10.4 mA, and the reverse conversion (10.4 − 4) × 10 A ÷ 16 mA returns 4.0 A.
The shunt alternative puts a series resistance in the 12 V circuit and amplifies its millivolt drop; it works, but it breaks the galvanic isolation the window sensor gives you for free, so use it only where isolation is already handled elsewhere.
What current range should the transducer cover for the motor? #
Pick the smallest commonly available range that exceeds twice the motor's nameplate full-load current: on a 460 V three-phase motor with 7.6 A full-load current, that means a 0–20 A transducer, with the running point at 38 % of span.
Twice nameplate current keeps the running point near mid-span, where load changes resolve cleanly and an overload trend is visible long before the signal clips. For the example motor — 5 HP, 460 V, three-phase — the nameplate full-load current is 7.6 A, matching the Table 430.250 value in NFPA 70, the National Electrical Code, 2023 edition; the nameplate governs whenever the two differ.
Then check the start against that range. Acceleration current runs roughly six times full-load current — about 6 × 7.6 A = 45.6 A on this motor — so the 0–20 A output saturates during every start. That is acceptable when you trend running current; verify the transducer's documented short-duration overload rating covers 46 A for the acceleration time before you rely on it, and choose a higher-range or peak-capable device only if you actually need the starting profile.
How do I scale the signal into amps in the PLC? #
Apply a two-point linear conversion between the configured signal endpoints and their currents; for a 0–20 A transducer on the standard two-wire loop this collapses to amps = (signal − 4 mA) × 20 A ÷ 16 mA, so 10.08 mA reads back as 7.6 A.
The general form is: amps = I_low + (signal − S_low) × (I_high − I_low) ÷ (S_high − S_low), where S_low and S_high are the configured signal endpoints and I_low and I_high are the currents they represent. Keep both endpoints in the same units — use raw PLC counts for both only if both are expressed in counts.
Worked example, motor side, with every input stated:
- Transducer input range: 0–20 A; output: current loop with a 4 mA live zero.
- Signal endpoints: S_low = 4 mA at I_low = 0 A; S_high = the loop's full-scale current at I_high = 20 A.
- Motor running at nameplate full load, 7.6 A: signal = 4 mA + (16 mA × 7.6 ÷ 20) = 4 mA + 6.08 mA = 10.08 mA.
- PLC conversion: (10.08 − 4) × 20 A ÷ 16 mA = 6.08 × 1.25 A = 7.6 A.
Set alarm thresholds in engineering units, not raw counts. An overcurrent alarm at 1.15 × full-load current is 1.15 × 7.6 A = 8.74 A, which the channel sees as 10.99 mA on that same scaling. Do the comparison in amps inside the PLC and leave the counts to the channel.
The conversion itself is exact arithmetic on the configured endpoints; the accuracy of the displayed amps is still bounded by the transducer's accuracy class and the motor nameplate, so treat the value as a monitoring estimate and take protective actions only from listed devices.
Prefer the current loop over 0–10 V wherever the channel allows: a broken wire or an unpowered transducer drives the signal below its live zero, which the PLC can flag as bad data instead of reporting zero amps on a motor that is actually running.
How is the transducer installed and wired? #
De-energize the circuit and verify absence of voltage before you open the panel or route conductors, then pass only the one conductor being measured through the window, power the transducer from the control supply, and run its output to the PLC on shielded twisted pair with the shield grounded at the PLC end only.
Only the measured conductor goes through the window. Passing the outgoing and return conductors of one circuit through the same window cancels their fields and the output collapses toward zero — the same physics ground-fault sensors exploit deliberately. On a three-phase motor, one transducer on one line gives that line's current, not phase balance; per-phase data needs three transducers or a three-phase unit.
For a DC Hall-effect sensor, follow the marked polarity: current in the wrong direction reads as a negative or offset value instead of the expected span. Verify the galvanic isolation between the measured circuit, the output and the auxiliary supply against the datasheet, and confirm the sensor's circuit-voltage rating covers what it surrounds even though it makes no direct connection.
Does the current transducer replace the motor's overload relay? #
No. The transducer is measurement, not listed motor protection, and NFPA 70, the National Electrical Code, 2023 edition — Article 430 covers motor circuits and their overload protection — still requires that protection no matter what the PLC reads; confirm the requirement with your local authority having jurisdiction and the equipment documentation.
Keep the existing overload relay and treat the PLC alarm as supervisory. If you want one device doing both jobs, a communicating overload relay does: set it from the motor nameplate full-load current as covered in setting overload relays from motor nameplate full-load current, and it reports per-phase current and trip data over the network you already have. Verify the exact relay, adapter and PLC combination against manufacturer documentation before committing the bill of materials.
Also know what any current-based device misses: the blind spots are laid out in what current-only motor protection can and cannot detect, and they apply to your new measurement channel just as they apply to the relay.
How do I prove the PLC reading is correct? #
Three checks settle it: with the motor stopped the channel must read its zero point (the live zero, not zero signal); at steady load a true-RMS clamp meter on the same conductor must agree with the PLC value; and a second load point must move both readings together.
The stopped check catches wiring and power problems before you touch software: if the output sits at zero signal with the motor off, the transducer has no supply, the loop is open, or the channel is in the wrong mode — fix that before applying any offset. The two-point check catches scaling errors a single match hides, because an offset or gain error can pass at one current and fail at another. Compare meter and PLC on the same conductor under the same load, in the same units.
Expect the start to clip. When the inrush passes through a 0–20 A range, the trend pins at 20 A for the acceleration and then recovers; that is saturation, not a fault. Judge the start from the duration of the clip and the recovery, not from the missing peak.
Questions asked
Can I pass all three phase conductors through one transducer window to get total motor current?
No — the magnetic fields of a balanced three-phase set cancel inside the window, so the output sits near zero. That cancellation is exactly what a ground-fault sensor exploits by passing every conductor of a circuit so only leakage shows. For per-phase motor current you need three transducers or a three-phase measuring unit.
Will a 0–20 A transducer be damaged by 46 A starting current?
Verify it against the datasheet's short-duration overload rating: the number that matters is the current the device tolerates for the acceleration time, not its measurement range. On the 7.6 A example motor, about 46 A passes during every start. The output clips at 20 A while it lasts, which is fine when you trend running current.
Can I wire a 5 A current transformer secondary straight into the PLC?
No. A CT secondary is a scaled AC current, not a conditioned DC signal, and a current transformer whose secondary is opened while the primary is energized can develop dangerous voltage across those terminals. Use a transducer, which packages the sensing element with its conditioning, and never lift its output wiring under load.
Why choose 4–20 mA instead of 0–10 V for the transducer output?
The live zero. A broken wire, a lost supply or a failed transducer drives the signal below its zero-flow point, which the PLC can alarm as bad data instead of displaying zero amps on a motor that is running. A current loop also ignores the voltage drop of long signal runs. Use 0–10 V only on short runs into voltage-mode channels.
The panel already has an ammeter showing motor current — can the PLC use it?
Only if its datasheet lists a retransmission output or a communication port; a meter without one is local indication and nothing more. Many digital panel meters offer a current-loop retransmit option. If yours has none, add a transducer around the same conductor and leave the meter doing its job.