Current IntelPower LibraryShop main store

Explainer

Reverse current injection with a CT: burden voltage decides

Protection: breakers, fuses and SCCR Published 7 min read

Short answer

A CT multiplies current only into a burden that is nearly a short circuit. Into 1,200 Ω, 100 mA forces 120 V and 12 W at the output, which reflects as 75 MΩ and 30 kV on the 250-turn winding, beyond any 400 µA source and any CT core or insulation. Lower the burden to ohms or less, where secondary injection is standard practice, or drive the load from a 60 Hz source that supplies the voltage and power directly.

On this page
  1. Why can't a 250-turn CT turn 400 µA into 100 mA?
  2. What voltage and power does a 1,200 Ω burden need at 100 mA?
  3. What does that burden look like from the 250-turn winding?
  4. Example: what changes when the burden drops from 1,200 Ω to 0.4 Ω?
  5. Can a small CT core carry 120 V on a single turn at 60 Hz?
  6. Is a GFCI sensing transformer suitable for reverse power duty?
  7. What load makes reverse injection standard practice?
  8. What source actually delivers 100 mA into 1,200 Ω?
  9. Questions asked

Your turns ratio is right and your power check is right — only the setup is wrong. A CT multiplies current only into a burden that stays close to a short circuit. Into 1,200 Ω, 100 mA RMS forces 120 V RMS and 12 W at the output, which reflects as 75 MΩ and 30 kV on the 250-turn winding. No 400 µA source gets there, and no CT core or winding is built for it. Reverse injection is real, everyday commissioning practice, but only into burdens of ohms or less. The decision is binary: lower the burden until the voltage is volts, or drive the kilohm-class load from a 60 Hz source that supplies the voltage and power directly.

Why can't a 250-turn CT turn 400 µA into 100 mA? #

It can — but only into a burden that is close to a short circuit: the turns ratio sets the current, the burden sets the voltage, and a resistive kilohm-class load asks the driven winding for tens of kilovolts that nothing in the circuit can develop.

Your power check is the correct physics. A transformer trades volts for amps at constant power, minus losses; it never adds watts. The ratio holds only while two conditions stay true: the core remains unsaturated at the voltage the burden demands, and the source can develop that voltage while holding its set current. A current source regulates only up to its compliance voltage — the voltage it can produce while still delivering the commanded current. Past that point the output sags or the waveform clips, which is what your bench and simulator both showed.

What voltage and power does a 1,200 Ω burden need at 100 mA? #

At 100 mA RMS the burden takes 120 V RMS and dissipates 12 W, and every watt of that has to arrive through the transformer from the driving source.

  • V = I × R = 0.100 A × 1,200 Ω = 120 V
  • P = I² × R = (0.100 A)² × 1,200 Ω = 12 W

Measure or read the burden impedance at 60 Hz, including the leads and the receiving device, before anything else; if it is not resistive, its impedance and waveforms set the voltage demand instead. Everything here uses RMS amplitudes — if your current figure is a peak value, the voltages are peaks too and the average power halves.

What does that burden look like from the 250-turn winding? #

Reflected through the square of the ratio, the burden becomes 75 MΩ, so the driven winding must stand 30 kV to carry the ideal 400 µA — the number your own estimate already reached.

  • Z = (250 ÷ 1)² × 1,200 Ω = 75,000,000 Ω
  • V = (250 ÷ 1) × 120 V = 30,000 V

The product of winding voltage and winding current equals the burden power, as conservation requires: the ratio trades volts for amps, never watts. Reflecting an impedance across a ratio by its square is the same mechanic that sets fault current through a power transformer, worked through in calculating transformer secondary fault current in per-unit. When a source hits its compliance limit, measure the delivered winding current instead of trusting the setpoint.

Example: what changes when the burden drops from 1,200 Ω to 0.4 Ω? #

Everything: with the same 250:1 transformer and the same 400 µA drive, a 0.4 Ω burden needs only 10 V on the driven winding, because the required voltage scales directly with burden resistance.

Illustrative case, sinusoidal, 60 Hz, RMS, resistive burden:

  • Burden voltage: 0.100 A × 0.4 Ω = 0.040 V
  • Winding voltage: 250 × 0.040 V = 10 V
  • Reflected impedance: 250² × 0.4 Ω = 25,000 Ω
  • Source check: 0.000400 A × 25,000 Ω = 10 V, and 10 V × 0.000400 A = 4 mW — equal to (0.100 A)² × 0.4 Ω = 4 mW at the load

The burden fell 3,000-fold, so the voltage fell 3,000-fold; the current ratio never moved. And 0.4 Ω is the realistic order of a CT secondary circuit — a relay current coil plus its lead run — which is exactly the class of load reverse injection serves.

Can a small CT core carry 120 V on a single turn at 60 Hz? #

No: holding that voltage on one turn at 60 Hz needs about 0.3 m² of core cross-section at 1.5 T peak flux density — four orders of magnitude more core than a ground-fault sensor's window contains.

Faraday's law for a sine wave gives V = 4.44 × f × N × A × B, with f in hertz, N the turns, A the core cross-section in square metres and B the peak flux density in tesla. Solve for the area the burden voltage would need:

  • A = 120 V ÷ (4.44 × 60 Hz × 1 turn × 1.5 T) = 0.30 m²

Now run it forward for an illustrative sensor core of 25 mm², that is 2.5 × 10⁻⁵ m² (hypothetical; read your part's drawing):

  • V per turn = 4.44 × 60 × 2.5 × 10⁻⁵ × 1.5 ≈ 10 mV
  • Full 250-turn winding: 250 × 10 mV ≈ 2.5 V before saturation

Silicon steel saturates around 1.5 T; a ferrite sensing core saturates well below that, so the real limit is worse. Below saturation the magnetizing branch still takes excitation current before any reaches the reflected load — the ideal model budgets it zero. Past saturation the excitation current spikes, the waveform distorts and the ratio collapses.

Is a GFCI sensing transformer suitable for reverse power duty? #

No: a ground-fault sensor is documented to produce millivolt-level signals for its own detector, and nothing in its datasheet rates the winding insulation, thermal rise or excitation for power-transformer duty, so it fails on paper before it fails in hardware.

For injection work, choose a transformer with published ratio, burden and insulation ratings — a ratio-test CT or the test set's own output transformer — and drive it inside those numbers. One mechanical detail for any one-turn output: route the test lead so its return path does not pass back through the core window, or its ampere-turns cancel the turn you wanted.

And leave the protective device out of it: driving a sensor winding toward the voltages the resistive case demands, or lifting a sensing coil out of a GFCI in service, is not a legitimate way to build a test supply — altering that sensing circuit changes the protection it provides. De-energize and verify before opening any CT terminal.

What load makes reverse injection standard practice? #

Current-driven loads of an ohm or less — relay current coils, metering elements, CT primaries under ratio test — where the burden voltage is volts and the test set's compliance is never the binding limit.

This is everyday commissioning work: the InterNational Electrical Testing Association's Acceptance Testing Specifications (NETA ATS, 2021 edition) cover commissioning tests for protective relays, including secondary injection, in which the test set drives the CT's multi-turn secondary winding through a test switch or test block and the multiplied current appears on the primary bar or a one-turn lead. Shorting links keep the CT shorted whenever the relay is out of the circuit.

IEEE C57.13-2016, the standard requirements for instrument transformers, defines CT accuracy against standard secondary burdens between 0.1 Ω and 8 Ω, and its strongest relaying class, C800, is defined by delivering 800 V at twenty times rated current into an 8 Ω standard burden with at most 10% ratio error — the standard itself says a CT is a low-voltage, low-burden device. IEC 61869-2:2012 says the same thing in VA. Confirm the test procedure your site applies with the relay documentation and the authority having jurisdiction, since editions and local amendments differ.

What source actually delivers 100 mA into 1,200 Ω? #

A plain 60 Hz source rated for the burden voltage and at least 15 VA — a relay test set's current channel with compliance above that voltage, or an isolation transformer on a suitable tap — delivers it directly, with no CT in the path.

The decision, case by case:

  • Burden fixed at 1,200 Ω: drive it with that source. The transformer question disappears; the voltage and current involved are ordinary instrument work.
  • Burden genuinely reducible: reverse injection works with a transformer documented for injection duty, but budget two ceilings first. Source compliance caps the burden at compliance voltage ÷ (ratio × output current): a driver reaching 12 V allows 12 V ÷ 250 ÷ 0.100 A = 0.48 Ω. Core saturation caps it again: the illustrative sensor core's 2.5 V winding limit allows 2.5 V ÷ 250 ÷ 0.100 A = 0.10 Ω.
  • No third case exists: no turns count, core or cable turns a low-compliance source into a 12 W supply, because watts cross a transformer unchanged.

Pick the burden first, then the transformer, then the source — at a kilohm-class burden the correct transformer is none.

Questions asked

Does adding more turns to the driven winding fix the voltage problem?

No. More driven turns buy current ratio only by demanding more voltage: winding voltage grows with the turns count and reflected impedance with its square, so the source's job gets harder while the load's power demand stays the same. Turns only help while voltage, flux and compliance limits still hold, which is why the turns count is never the fix.

Why must a CT secondary never be left open?

With no burden to hold it down, secondary voltage climbs until the core saturates every cycle, producing distorted peaks that can stress insulation, and the current ratio is lost. That is why test blocks short the CT circuit before a relay is withdrawn, and it is the same burden-voltage mechanism that limits the resistive case in this article.

What does a CT burden rating in VA actually mean?

It is the power the CT can deliver into its secondary circuit at rated current while staying inside its accuracy class. IEC 61869-2:2012 expresses it in VA: a 2.5 VA, 5 A CT is built for roughly 0.1 Ω of total secondary impedance, since 2.5 VA divided by (5 A) squared gives 0.1 Ω. IEEE C57.13-2016 states its standard burdens directly in ohms, and both documents say CT circuits are low-impedance by design.

Why would an ideal simulation multiply the current when the bench will not?

An ideal transformer model has no magnetizing branch, no saturation and no compliance limit, so it transforms power for free. Add a magnetizing inductance, winding resistance and a voltage-limited source, and the simulation fails the way the hardware does. A model that reproduces the failure is the useful one, because it shows which limit binds first.

How do I check whether the source is really delivering its set current?

Read the driven winding with a true-RMS meter or a shunt, not the setpoint display. A source at its compliance limit still reports the commanded value while actual current sags or the waveform flattens. Compare winding current against burden current through the ratio: a shortfall that grows with burden voltage points at compliance; a distorted waveform points at core saturation.

Keep reading

  • How-to

    Calculating Transformer Interrupting Current From Impedance

    Use the impedance's own base: 10.2% is stated on the 8,333 kVA self-cooled (OA) rating, so rated current at 5.04 kV is 1,653 A and the transformer-limited secondary fault current is 1,653 ÷ 0.102 ≈ 16.2 kA. That figure sizes a breaker on the secondary bus; a primary breaker's interrupting rating is set by the upstream available fault current, not by the transformer.

    Protection: breakers, fuses and SCCR

  • How-to

    How to calculate transformer secondary fault current in per-unit

    Yes — use one MVA base for the whole study, and the transformer rating is the convenient one: with 16.091 kA available at 230 kV and a 24 MVA, 8.8%Z, 230/13.2 kV transformer, the source impedance is 0.003744 pu, the total is 0.091744 pu, and the secondary fault current is about 11.44 kA at 13.2 kV. The infinite-bus figure, 11.93 kA, is the ceiling to rate against when the primary source is ignored or unknown.

    Protection: breakers, fuses and SCCR

  • Selection guide

    Setting 50 and 87 functions on a fused medium voltage motor starter

    On a NEMA Class E2 fused starter the current-limiting fuses are the short-circuit interrupter, so the phase 50 element defaults to alarm-only or disabled unless the coordination study and the contactor's interrupting rating support tripping. The 87 element follows the same test through its differential zone. Ground fault is separate: on an HRG 4.16 kV system with a core-balance CT and about 25 A or more of available ground-fault current, set 50G.

    Protection: breakers, fuses and SCCR