Motors and motor starters Published 6 min read By Current Intel engineering team

Short answer

A three-phase generator reconnected in delta or double delta for single-phase output delivers roughly two thirds of its three-phase kVA: a 5.5 kVA machine yields about 3.7 kVA. The prime mover can still force the original kilowatts into the windings, so overload protection must be reset for the revised rating.

On this page
  1. How much output does a three-phase set give on single phase?
  2. Which connection makes single-phase output work?
  3. What happens if you just use two phases for a short time?
  4. How does the current arithmetic work out for a 5.5 kVA machine?
  5. Why does the prime mover still threaten the windings?
  6. What should you measure before putting the load on?
  7. Is running it as a single-phase motor the same question?
  8. Questions asked

A three-phase generator reconnected in delta or double delta for single-phase output delivers about two thirds of its three-phase kVA, so a 5.5 kVA machine becomes roughly a 3.7 kVA single-phase machine. The prime mover does not shrink: it can still drive its original kilowatts into the windings, so the overload protection must be reset for the revised rating before the machine runs. This article gives the arithmetic, the connection that makes it work and the protection decision.

How much output does a three-phase set give on single phase? #

Plan on about two thirds of the three-phase kVA, with the power factor moving to unity. A set rated 60 kVA at 0.8 power factor becomes a 40 kVA, 40 kW single-phase set; a 5.5 kVA, 5.5 kW machine becomes about 3.7 kVA and 3.7 kW. The kVA limit is set by winding current, and the reconnection changes how much of that current the load can draw without overheating any winding.

These two-thirds figures are published generator-manufacturer guidance for re-connectable sets, not a nameplate value. Your set's documentation gives the rating for the exact connection; use the two-thirds number as the expectation you check against.

Which connection makes single-phase output work? #

The double delta connection is the preferred reconnection, because it divides the single-phase load current equally among all three windings. In delta or double delta the current is equal in all three phases but out of phase with the induced voltage in two of them, which the winding tolerates within the revised kVA limit. If the required output voltage cannot be reached with delta or double delta, a zig-zag connection is the next arrangement to investigate, and only if the machine's leads and documentation support it.

Whether any of this is possible depends on the terminal arrangement. Count the leads and read the manufacturer's connection diagram: 12-lead and similar re-connectable windings support these reconnections, and a machine brought out with only three leads does not. Reconnecting is dead-work: isolate the machine, lock out the prime mover and its excitation or capacitor circuit, and test for absence of voltage before opening the terminal box.

What happens if you just use two phases for a short time? #

Two terminals without a reconnection concentrates the whole load current in part of the winding, so a load that looks comfortably below three-phase rating overheats one or two coils. A short period does not buy much: the thermal time constant of a stator winding is minutes, and the torque pulsation at twice supply frequency (100 Hz on a 50 Hz supply) is present in any single-phase arrangement. If you need single-phase output, do it with the correct reconnection and the revised rating, not with a partial connection and hope.

How does the current arithmetic work out for a 5.5 kVA machine? #

Worked example, all inputs stated: a three-phase asynchronous generator rated 5.5 kVA at 400 V, 50 Hz, unity power factor, reconnected double delta for 230 V single-phase output.

  • Three-phase line current: I = S / (√3 × U) = 5500 VA / (1.732 × 400 V) = 7.9 A per line.
  • Revised single-phase rating at two thirds: 5.5 kVA × 2/3 = 3.7 kVA, which at unity power factor is 3.7 kW.
  • Single-phase output current: I = S / U = 3700 VA / 230 V = 16.1 A.
  • In the double delta connection that 16.1 A divides among the winding pairs so no winding carries more than roughly its original design current; the revised kVA exists precisely to keep every winding inside its thermal limit.

The result is an estimate to be checked against the machine's documentation and the governing code. The decision: a machine of that size reconnected double delta serves about 3.7 kW of single-phase load, at 16.1 A on a 230 V output.

Why does the prime mover still threaten the windings? #

Reconnecting the stator changes the electrical rating, not the engine. A diesel or petrol prime mover sized for 5.5 kW still has 5.5 kW of mechanical power available, and in generator duty there is no motor-stall behaviour to back up the protection: when the load exceeds 3.7 kW the surplus simply becomes winding heat while the engine keeps turning. This is the same rule used when an overload relay is set from a motor's nameplate full-load current — the protective device must be sized from the rating of the thing it protects, in this case the revised single-phase rating.

Under NFPA 70 (the National Electrical Code), 2023 edition, Article 445 covers generator overcurrent protection and where the protective device may be located relative to the generator, and sets rated above 15 kW must additionally have a means to shut down the prime mover on sustained overcurrent. Confirm the exact requirement for your set with the authority having jurisdiction and the machine documentation. Protect the output for 16.1 A in the worked example, not for the engine's 5.5 kW, and make sure a sustained overload cannot keep being driven into the machine.

What should you measure before putting the load on? #

Verify the completed connection against the approved diagram, then bring the load up in steps. Measure output voltage and frequency, then current in each accessible winding or line with a clamp meter, and confirm none exceeds the revised rating as load rises. Watch winding temperature and mechanical behaviour: abnormal heating, vibration or pronounced torque pulsation means remove the load and return to the connection decision, because a stable output voltage alone proves nothing about winding current. Record the connection, voltage, load and currents for the next person who touches the machine.

If your set feeds a monitoring or logging station, the same revision applies to its data side: an industrial panel PC with the computer built in fits a power-monitoring display at the generator, sized for the voltage and environment at that panel.

Is running it as a single-phase motor the same question? #

No, and the answers do not transfer. The Steinmetz delta connection with a single capacitor can run a three-phase motor from a single-phase supply, but for a 5.5 kW machine the run capacitor is large and expensive and starting torque is poor, which is why that plan often dies on cost. For motor duty from a single-phase source, a rotary phase converter is usually the better path, and its behaviour, including the third-leg problems that can shut a machine down, is its own subject. Generator reconnection and motor conversion share only the machine; the ratings, connections and protection are different problems.

The decision, in one line: re-connectable three-phase sets give about two thirds of nameplate kVA on single phase through delta or double delta, and they run safely only with protection reset for the revised rating and a prime mover that cannot force the original kilowatts past it.

Questions asked

What overcurrent protection does a reconnected generator need?

Set the generator-side overcurrent device from the revised single-phase kVA and current, and confirm the arrangement against NFPA 70 Article 445 and your local authority having jurisdiction. Sets above 15 kW additionally require a means to shut down the prime mover on sustained overcurrent, so the engine cannot keep driving a fault or overload.

Can you reconnect the set back to three-phase later?

Yes, on a 12-lead or similar re-connectable winding the stator returns to its original delta or wye configuration, and the three-phase nameplate rating applies again. Mark every lead after the first reconnection, because unlabelled leads make the second change the risky one. Each conversion is a dead-work job: lock out, test for absence of voltage, and verify the finished connection against the manufacturer's diagram before energising.

Is the two-thirds figure a nameplate rating?

No. It is published generator-manufacturer guidance for re-connectable sets, an expectation you check against your set's documentation, which gives the rating for the exact connection and voltage. Size the protection and the load from the documented single-phase rating, not from the three-phase nameplate or from the two-thirds rule alone.

Keep reading

  • Explainer

    Running a 690 V 50 Hz motor on a 415 V supply

    The nameplate connection decides. Star at 415 V leaves a 690 V star winding near 240 V, so torque drops to about 36% and a loaded motor stalls; the documented 400 V delta connection sits about 4% over its rating, inside the IEC band, and is the correct connection. With no delta listed, feed 690 V or run a drive with a base frequency near 30 Hz.

    Motors and motor starters

  • Explainer

    Running a three-phase motor on single-phase 208 V

    Yes — a spinning three-phase motor fed across two terminals regenerates the third leg, but winding heating caps it near 30-40% of rated horsepower, so it is a bench trick, not a supply. For real loads, use a rotary phase converter with an idler at least the next size above the largest motor, or a single-phase-input VFD for motors only — never a drive for amplifiers or power supplies.

    Motors and motor starters

  • How-to

    Why a stored vintage motor needs megger and winding tests before a VFD

    Yes, and before any drive is bought; a motor stored for twenty years needs a 500 V DC insulation test and three lead-to-lead resistance readings. The pass marks are 1.22 MΩ minimum for a 220 V winding per IEEE 43-2013, a polarization index of 2.0, and phase resistances within 5 percent. Pass, and either a 1 hp single-phase-input drive or the 5 hp rotary converter runs it; fail, and the motor is replaced, not repaired.