Current IntelPower LibraryShop main store

Explainer

Segmenting a long busway for arc flash studies

Electrical safety and codes Published 9 min read

Short answer

Segment a tapped busway into one model bus per tap with the published section impedance between taps. Bolted fault current drops along the run, and the lower arcing current can push an upstream breaker into a slower clearing band, raising incident energy at interior taps an endpoint-only model never checks. Sample head end, middle and far end first, then label the whole run at the highest calculated value.

On this page
  1. Why one bus cannot carry the whole run
  2. Build the model: one bus per tap
  3. Where the impedance numbers come from
  4. Worked example: one 480 V run, tap by tap
  5. Lower arcing current can mean more energy
  6. Sample three taps before trusting two
  7. Breaker duty changes along the run
  8. The impedance-grounded case that misbehaves
  9. Label the run at the governing value
  10. Questions asked

Model a long tapped busway as one study bus at every tap, with one section of busway impedance between neighboring taps: a 600 ft run with a tap every 20 ft becomes thirty study buses joined by thirty 20 ft sections of series resistance and reactance. The resolution earns its keep because bolted fault current steps down with distance from the source, and the lower arcing current at the far taps can drop the upstream breaker into a slower time-current band — longer clearing, more incident energy, at an interior tap that a two-endpoint model never computes. Get the impedance data from the busway manufacturer for the installed rating and metal, sample at least the two ends and the middle, then label the whole run at the highest calculated incident energy.

Why one bus cannot carry the whole run #

Every section between the source and a tap adds its own resistance and reactance in series with everything upstream, so the available bolted current steps down from tap to tap. A single lumped bus — one impedance standing in for the whole run — reproduces the fault current at exactly one point, wherever its lumped value happens to land. It cannot tell you what a breaker at the fifth tap or the eighteenth sees, and it cannot show where the arcing current crosses a protective device's pickup.

Folding the whole run into the feeder cable has the same limitation in a cheaper disguise: it lands on the far endpoint and misses the interior entirely. It also invites the wrong data, because feeder-cable impedance is not busway impedance — the two constructions space their conductors differently, and reactance follows spacing. The endpoint cases are worth computing; they are not the model.

Build the model: one bus per tap #

The build is mechanical. Create one study bus at each tap location. Connect neighboring buses with one section carrying the busway's line-to-neutral resistance and reactance scaled to the section length, so thirty sections of 20 ft close out the 600 ft of installed run. Place each tapped breaker, fuse and load at its own tap bus, because every device responds to the current at the point where it connects.

If the study software has no busway element, enter the section impedance into a cable-type element and record in the study file that the entered values are published busway impedance, not cable data. If the software's bus count stops the full model, split the run into two partial studies at a chosen tap, keep the same source model in both files, and let the joint tap appear in both so the results agree where they meet. Motor loads tapped along the run belong at their own buses; whether motor contribution raises arc flash incident energy at a given tap depends on how much of that contribution the upstream device sees there.

Where the impedance numbers come from #

Busway manufacturers publish line-to-neutral resistance and reactance for each ampere rating, conductor metal and construction, in milliohms per 100 ft, referenced to a stated conductor temperature — one current catalog states its values at 80 °C (176 °F). The design guides behind low-voltage sandwich-type runs (600 V, totally enclosed, non-ventilated construction is the common form) carry the same tables. Take the row that matches the installed rating and metal: aluminum of a given rating runs higher resistance than copper, while reactance changes little because it follows conductor spacing.

Do not substitute feeder-cable data because the software menu makes it easy. If a run is old and the manufacturer has no record, work from the rating stamped on the end caps and request the data; several legacy lines carried into successor catalogs still publish it. An unverified impedance guess defeats the whole segmentation, because every tap's result inherits it.

Worked example: one 480 V run, tap by tap #

All inputs below are example values, declared so the arithmetic can be rerun with your own. The system is 480 V, three-phase, 60 Hz. The upstream study gives 30.0 kA of three-phase bolted fault current at the head of the run — the same source-impedance arithmetic set out in calculating low-side fault current with source impedance. The busway's published table reads 1.5 mΩ line-to-neutral per 100 ft for this rating, an example value.

The main that clears a fault anywhere on the run is a 2000 A frame with a short-time pickup of 14.0 kA (a 7× setting) and a 0.10 s short-time delay; below the pickup its long-time band clears in 0.30 s at these currents, given here as example curve points. The arcing and energy figures come from the IEEE 1584-2018 arcing-current and incident-energy models as implemented in study software, run for a 32 mm gap in a box enclosure; the standard states the voltage and current ranges its equations are valid across, and both ends of a long run deserve that check.

Source impedance: Z = 480 V ÷ (√3 × 30,000 A) = 480 ÷ 51,962 = 9.24 mΩ line-to-neutral, with √3 the square root of three.

Section impedance: 1.5 mΩ × (20 ÷ 100) = 0.30 mΩ per tap interval.

Tap 15, halfway along the run: 9.24 + (15 × 0.30) = 13.74 mΩ, so I = 480 ÷ (√3 × 0.01374 Ω) = 20.2 kA.

Tap 30, the far end: 9.24 + (30 × 0.30) = 18.24 mΩ, so I = 480 ÷ (√3 × 0.01824 Ω) = 15.2 kA.

Adding the values as scalars is a deliberate simplification; the software sums resistance and reactance as complex quantities, which lands within a few percent of this for a run of this shape.

Tap Distance from source Bolted current Arcing current Clearing time Incident energy
1, head end 0 ft 30.0 kA 22.6 kA 0.10 s 3.1 cal/cm²
15, midpoint 300 ft 20.2 kA 15.5 kA 0.10 s 2.4 cal/cm²
30, far end 600 ft 15.2 kA 11.7 kA 0.30 s 8.9 cal/cm²

The bolted and arcing columns follow the arithmetic above; the incident-energy column is the illustrative output of the standard's model for those arcing currents, gap and enclosure, to be confirmed against the governing edition of the local code and the equipment documentation. The head end and midpoint both sit above the short-time pickup and clear in 0.10 s. The far tap's arcing current falls below the pickup, the main coasts down its long-time band and clears in 0.30 s, and the energy at that tap lands at 8.9 cal/cm² against 3.1 cal/cm² at the source end — 8.9 ÷ 3.1 ≈ 2.9, tracking the 3:1 clearing-time ratio with the weaker arc shaving a little off. The decision for this example: the far tap governs, and the run carries that value on its label even though the head end sees twice its fault current.

Lower arcing current can mean more energy #

The mechanism in that example is general. A device's clearing time is read from its time-current curve at the arcing current, not at the bolted current; when the arcing current at a tap falls below an instantaneous or short-time pickup, clearing moves from a few cycles into the long-time band, and incident energy scales directly with clearing time at fixed arcing conditions. That is how the far end of a run — the point with the least available current — can end up the hottest label on the job, and the same trap explains an upstream setting that never catches the arc, covered in why an upstream instantaneous setting may not cut arc flash. The decision rule: rank locations by their calculated incident energy, never by their bolted current.

Sample three taps before trusting two #

Two endpoints give two data points, and a time-current curve can bend between them. Sample the head end, the midpoint and the far end first: three points show whether incident energy is falling toward the far end, rising, or peaking in between, because the energy-versus-distance curve can climb from either end's value. If the midpoint exceeds both ends, or the clearing-time band changes between neighboring taps, the protective behavior is shifting somewhere the screen cannot place — model every tap and find the crossing. In the worked example the pickup crossing lies past the midpoint, so the full run gets modeled tap by tap. The decision: three taps to learn the shape, every tap when the shape bends.

Breaker duty changes along the run #

Even when the incident-energy label comes out the same everywhere, the available current does not, and each tapped breaker interrupts the current at its own bus. The bolted value a duty check uses is the one at that breaker's own location, not a run-wide average — which bolted fault current to use for breaker duty and arc flash sorts out the choices. Check each tapped device's interrupting rating against its own location's calculated current; a breaker applied above its interrupting rating undermines the study's conclusions in ways an energy label will not reveal, as how an overdutied breaker changes your arc flash study results lays out. The decision: one label may serve the whole run, but the duty check is per breaker, per tap.

The impedance-grounded case that misbehaves #

On a high-resistance or otherwise impedance-grounded system, a long run adds distributed capacitance, and the remote single-line-to-ground current can end up higher than the source-end value instead of lower. Compute the ground-fault current at both ends rather than assuming decay, and check the ground-fault protection settings against what the far end actually delivers. The incident-energy label still comes from the three-phase arcing calculation; why single line to ground fault current does not change arc flash covers why the ground-fault strangeness stays a relaying and duty question rather than a labeling one.

Label the run at the governing value #

NFPA 70E, 2024 edition, requires a label on equipment likely to be examined or serviced while energized, stating the available incident energy and working distance or the arc rating of the required PPE, along with the arc flash boundary; Article 130 carries the requirement, and the exact fields should be confirmed with the authority having jurisdiction and the equipment documentation. For a tapped busway run, one label at the highest calculated incident energy serves the whole run, and where the run hangs overhead, larger placards at the readable access points are a legitimate way to carry that value.

Keep the study record with the label: the impedance source and its stated temperature, the section length, the governing tap, and the arcing currents and clearing times behind the result. Recalculate after any breaker replacement or setting change, because the governing tap can move.

Placing labels or verifying tap spacing happens with the run de-energized and absence of voltage verified on each conductor; work near exposed energized parts is energized work under NFPA 70E and takes the permit and the PPE the label calls for.

Questions asked

My study software caps the number of buses in one file. Can I still resolve every tap?

Yes. Split the run into two partial studies at a chosen tap, enter the same source model and head-end available current in both files, and let the joint tap appear in both so the two results agree where they meet. The segmentation method does not change with the file boundary; only the number of taps each file holds does.

Can I add the busway length to the feeder cable instead of modeling sections?

That shortcut reproduces the far endpoint only, and only when the impedance you enter represents the busway construction rather than a different cable geometry. It discards every interior tap, so it cannot locate a governing point between the ends, and cable and busway reactance differ for the same length because their conductor spacing differs.

Does aluminum busway need different impedance data than copper?

Yes. At the same ampere rating and construction, aluminum bus has roughly 60 percent higher resistance than copper, while reactance barely moves because it follows conductor spacing. Use the published table for the installed metal and rating; entering copper figures for an aluminum run understates the impedance and overstates the fault current at the far taps.

Do tapped motor loads change the segmentation?

The segmentation itself does not, but the loads do. Each large motor tapped along the run feeds contribution into a fault at its own bus, raising the current its nearby protective device sees and possibly changing its clearing time. Model each significant motor as a contribution source at its tap, and record any decision to neglect small motor groups as a documented study assumption.

Keep reading

  • Explainer

    IEEE 1584-2018 fault current range limits above 600 V

    Above the 600 V band edge the IEEE 1584-2018 model was verified only to 65 kA of bolted fault current, so a 690 V bus at 70 kA sits outside the documented range by 5 kA. Run the range check, keep the IEEE result as a labeled out-of-range sensitivity case, cross-check the Ralph Lee method, and use the higher incident energy for PPE until an engineer signs the method decision.

    Electrical safety and codes

  • Explainer

    Why main-breaker settings can't protect switchboard line-side buswork

    A main breaker's trip settings cut calculated incident energy only for faults that stay on its load side. Credit them only when the main compartment is verified separated from line-side buswork front and rear; otherwise the study keeps the upstream clearing time, and an added barrier earns credit only with a documented manufacturer or qualified-engineer basis.

    Electrical safety and codes

  • Troubleshooting

    Checking a delta high leg arc flash calculation's numbers

    The 9.127 kA at the panelboard checks out against the 11.33 kA infinite-source terminal limit once utility impedance is counted. The 73 cal/cm² hinges on clearing time: the referred bolted current clears the 600 A primary breaker in 0.033 s, but IEEE 1584 sets device time from the arcing current, which falls below the 3,600 A pickup into the thermal band — so the label is credible until the study file shows otherwise.

    Electrical safety and codes