Selection guide
Selecting a three-phase CT meter for load profiles and TOU
Short answer
Select the meter by its documented feature set, not its family name: the exact model must list three-phase CT-connected inputs, interval load-profile storage, time-of-use registers and panel or DIN-rail mounting. Resolve the transformer notation from the nameplate first; if it confirms a 300 kVA three-phase unit with a 208 V line-to-line secondary, rated secondary current is about 833 A — a screening number for the CT conversation, not the selection itself.

On this page
Buy this meter on its documented feature set, not on a family name or a tip from a colleague. The exact orderable model must show four functions on paper: three-phase CT-connected measurement, interval load-profile storage, time-of-use (TOU) registers, and panel or DIN-rail mounting. Before ordering, resolve the transformer shorthand — a 12,500/208 V, 300 kVA unit does not, by that notation alone, fix the secondary wiring or the CT size. If the nameplate confirms a three-phase transformer with a 208 V line-to-line secondary at that rating, the rated secondary current screens out at about 833 A, which starts the CT conversation without finishing it. Everything else — interval length, memory, retrieval path, clock — follows from the audit plan you set before the baseline starts.
What the datasheet has to show #
Options within one meter family differ more than the family names suggest: profile memory, register counts and CT input ratings are frequently option-dependent. Judge the orderable model number and its option codes against this list, using the datasheet plus the wiring and communication manuals.
- Three-phase, CT-connected measurement. The manual's wiring diagram must show an indirect connection — one CT per phase, with the meter's voltage elements referenced to the secondary bus. A direct-connect form will not read this switchboard through CTs.
- Interval load-profile storage. The manual must state which quantities the meter logs (demand, energy, per-phase or total), the selectable interval lengths, and how many records the memory holds.
- TOU registers. The datasheet must show configurable periods, a calendar with season and day-type handling, and how many registers the meter accumulates.
- Mounting. The mechanical drawing must show the panel cutout or the DIN-rail clip you intend to use; switchboard-mounted does not automatically mean DIN-rail mounted.
- CT input and ratio. The input must accept the secondary rating of the CTs you fit, and the ratio must be settable so the meter displays primary amps.
- Accuracy class. If the audit figures will be reconciled against utility billing, the metering accuracy class in the datasheet is the number that matters; confirm it rather than assuming it.
A meter that accumulates kWh but stores no interval history fails this audit, whatever else it does well.
Resolve the transformer notation before ordering #
The order shorthand — 12,500/208 V — reads most naturally as a 12,500 V primary with a low-voltage secondary, a common arrangement for a unit of this size feeding a switchboard. What the shorthand cannot tell you is the winding connection, and the connection decides the meter wiring. A secondary at this voltage is normally wye-connected, which provides roughly 120 V line-to-neutral for the meter's voltage elements; a delta winding provides no neutral and changes the diagram you follow. Read the nameplate and its connection diagram, and record the secondary line-to-line and line-to-neutral voltages before configuring anything. What each voltage element then sees also depends on the loads themselves — metering delta-connected motor loads on a wye service shows how delta loads on a wye secondary shift the per-phase picture.
If the nameplate disagrees with the shorthand — a different primary tap, a delta winding, a different kVA — stop and re-derive the screening current in the next section from the nameplate figures.
Screen the secondary current from the rating #
The rating gives a screening current, nothing more. For a three-phase transformer:
I = S / (√3 × V_LL)
Take the stated figures, S = 300 kVA = 300,000 VA and V_LL = 208 V:
I = 300,000 VA / (1.732 × 208 V) = 300,000 VA / 360.3 V ≈ 833 A
That screening current is the current at rated load. It assumes the rating is three-phase, the voltage is line-to-line, and the transformer actually runs at full load — an audit usually finds less, and overnight far less. It is an estimate; check it against the transformer nameplate and the governing documentation before it decides anything. It is the same arithmetic you would use to check a 2500 A incomer against a 1600 kVA transformer, and it buys you the first candidate range for the CT primary. The measured or expected running current finishes the selection.
Choose the CT ratio, then match the meter input #
A CT ratio is its full-load primary current to its secondary current: a CT marked 300:5 carries 300 A on the primary at 5 A on the secondary, and proportionally less below that. Two decisions follow.
First, the primary rating. Pick the ratio nearest the expected maximum running current, and check the accuracy the CT datasheet promises at the current the audit will actually see — a CT sized for 1000 A that meets a 200 A night shift reads that load coarsely. With the service running near rated load, ratios such as 800:5 or 1000:5 are the natural candidates; if the audit targets a lightly loaded feeder, step the primary down to hug the running current. Split-core CTs clamp over the conductors without disconnecting them, which matters in a retrofit; split-core current transformer selection for power meters walks through that choice.
Second, the secondary and the input. The CT secondary rating — 5 A in the example — must match what the meter input accepts, and the meter's configured ratio must equal the CT ratio, or every logged value comes out wrong by one constant factor. Land the secondaries on a shorting block and keep them shorted until the meter side is wired: a secondary circuit opened while the primary is energized can drive a hazardous voltage at its terminals.
The comparison that decides the order #
Put each candidate's datasheet and manual against this table, model number by model number, and disqualify on any row.
| Requirement | Verify on the exact model | What the audit loses without it |
|---|---|---|
| Three-phase CT-connected measurement | Wiring diagram shows one CT per phase plus a voltage reference | No measurement at all on this switchboard |
| Interval load-profile storage | Manual names the logged channels, interval choices and record count | No demand-over-time record to audit against |
| TOU registers | Datasheet shows configurable periods and calendar handling | Energy cannot be split into tariff periods |
| Memory against interval | Record count divided by channels covers the audit duration at the chosen interval | The profile ends mid-audit |
| Data retrieval | A documented local or communication path the audit workflow can read | Data recorded but never collected |
| Mounting | Mechanical drawing shows the panel cutout or the DIN clip | The meter does not fit the switchboard |
| CT input and ratio setting | Input accepts the CT secondary; ratio settable in the meter | Every logged value scaled wrong |
| Clock source | Manual documents how the clock is set and what survives an outage | Energy lands in the wrong TOU period |
Set it up, then prove the record #
- De-energize the switchboard, lock out and verify absence of voltage before any cover comes off — the sequence NFPA 70E, 2024 edition, requires for electrical work; confirm local requirements with the authority having jurisdiction and the equipment documentation.
- Copy the transformer nameplate: secondary line-to-line and line-to-neutral voltages, winding connection, rating. Reconcile it with the order shorthand before anything is configured.
- Fit the CTs over the correct conductors, mark polarity, and land the secondaries on the shorting block; keep them shorted until the meter side is wired.
- Wire the meter's voltage reference per the manual's diagram for the confirmed winding connection.
- Configure the CT ratio so the meter displays primary amps, then set the profile interval, the logged channels, the clock and the TOU calendar to the audit plan.
- Energize and check phase association: compare each displayed phase against a clamp meter or a known load, and confirm the kW direction — swapped voltage leads change three-phase kW readings in ways that still look plausible.
- Let at least one full profile interval elapse, retrieve the record, and check the timestamp spacing, the logged channels and the TOU register assignment before trusting anything else the meter reports.
If the retrieval workflow needs a host in or beside the switchboard, a fanless mini PC built for cabinet duty is the fitting choice for collecting and holding the profiles.
Five ways this purchase goes wrong #
- Buying the family instead of the model: profile memory and TOU handling are options on many meter series, so verify the orderable model number against all four functions.
- Trusting the shorthand: the order notation fixed nothing; the nameplate and its connection diagram fix the meter wiring.
- Choosing CTs from the rating alone: the screening current assumes full rated load. The primary comes from the running current, and the CT accuracy data at that current closes the choice.
- Assuming one feature implies the other: TOU registers without profile memory give period totals but no demand history; profile memory without a TOU calendar gives history with no tariff split. Confirm both run at once in the manual.
- Leaving the record unreachable: a retrieval path nobody can read, or a clock that slips after an outage, turns the baseline into guesswork. Set the clock from the source the manual documents and re-check it after any long outage.
The decision #
Read the nameplate first: if it shows a three-phase wye secondary at the rating on the order — the 12,500/208 V, 300 kVA as written — proceed; if it shows a delta winding, a different tap or a different rating, stop and re-derive the screening current from the nameplate figures. Screen the CT primary near the 833 A rated current — candidates such as 800:5 or 1000:5 — then finalize the ratio from the measured or expected running current and the CT accuracy data at that current. Order the meter only when its datasheet and manual show, for the orderable model number: three-phase CT-connected measurement, interval load-profile storage, TOU registers, panel or DIN-rail mounting, a CT input that accepts the secondary rating, and a retrieval path the workflow can read. Set the profile interval — 15 minutes is a workable default for a baseline audit — set the clock and the TOU calendar, and prove one retrieved record before the audit's first reading counts.
Questions asked
How long should the load-profile interval be for an energy audit?
Match the interval to the question and the memory. For example, 15-minute intervals store 96 demand readings per channel per day, enough for a baseline week or month, while 1-minute intervals resolve individual motor starts but use 15 times the memory over the same period. Whatever you choose, retrieve one record after commissioning and measure the timestamp spacing to confirm the meter logs at the configured interval.
What happens if a CT secondary is opened while the primary is energized?
A current transformer keeps forcing its share of the primary current through the secondary circuit, so an open secondary leaves that current nowhere to go and the terminal voltage can rise to a hazardous level, enough to damage the meter input or injure a worker. Short the secondary at the shorting block before disconnecting anything, and keep the CTs shorted whenever the meter side is open.
Does a CT-connected meter still need voltage connections?
Yes. The CTs scale the current only; every power and energy figure comes from pairing that current with a voltage measurement. Wire the voltage inputs to the secondary bus per the manual's diagram, confirm the input range covers the measured secondary voltage, and verify the phase mapping, because a meter with correct amps on all three phases can still report nonsense if its voltage leads are crossed.
Can one meter serve as both the audit logger and the permanent TOU billing point?
Only if the manual confirms both run simultaneously, with interval profile memory and TOU registers active at the same time, and only where the utility accepts a customer-owned meter at that point, which differs by utility; confirm with them before connecting anything on their side of the service. For a plant-side audit, a meter you control yourself avoids both questions.