How-to
Sizing an MCCB for ten single-phase motors on 380 V
Short answer
A 30 A three-pole MCCB is the correct upstream rating for ten 3 A single-phase motors split three-three-four across a 380 V supply, provided the starts are staggered and the feeders are sized for 30 A protection: staggered starting puts 27 A on the worst pole, while four motors starting together put 72 A there — 2.4 times the rating — and the manufacturer's time-current curve decides that case. Size each motor breaker per NEC Table 430.52 and keep a running overload at every motor.
On this page
Fit a 30 A three-pole MCCB upstream of this panel, run 10 AWG copper from it, and stagger the motor starts. Ten single-phase motors at 3 A each, split three-three-four across a 380 V three-phase supply with neutral, put running loads of 9 A, 9 A and 12 A on the three poles — 40% of the rating on the worst pole, thermally comfortable forever. Running load is not what decides the frame, though: the worst start the installation permits does. One motor starting while its three neighbors on the same pole run puts 27 A there, which an inverse-time breaker holds without warming toward its curve. All four starting together put 72 A on it, 2.4 times the rating, and the manufacturer's published time-current curve says whether that holds. The steps below run the voltage check, the starting check, the conductor size and the per-motor protection.
Confirm the supply and the pole split #
Connect each motor phase-to-neutral and check what the supply actually delivers there. A 380 V three-phase wye system divides by 1.732: 380 ÷ 1.732 = 219.4 V pole-to-neutral. That sits 4.6% below the motors' 230 V nameplate, inside the ±10% band NEMA MG-1 builds general-purpose motors to meet. Measure the terminals rather than trusting the label — a sagging or wrongly tapped transformer moves the whole calculation, and the motor documentation carries the exact tolerance it accepts.
The nameplates read 1/2 HP, 230 V, 3 A. Three motors on two of the phases and four on the third give 3 × 3 A and 4 × 3 A per pole: 9 A, 9 A and 12 A of running load. The group breaker's ampere rating applies to each pole in full — a three-pole frame gives every phase conductor its own trip level and never shares one rating across three phases.
Why the running load does not settle the size #
A breaker feeding motors does two jobs: carry the running load indefinitely, and ride through every start the installation permits while still protecting its conductors. A thermal-magnetic MCCB trips on heat over seconds and on magnetism within cycles, and motor inrush lands exactly in the band between — long enough to heat the thermal element, clear only if the multiple stays modest. The number that picks the frame is therefore the largest current any pole can see during starting, not the largest running load. That is why the comfortable 40% running figure cannot approve the candidate rating on its own.
Run the starting check against the curve #
Worked example, with one assumed input: suppose each motor's documentation gives a locked-rotor current of 18 A, six times its running current. Fractional-horsepower capacitor-start motors commonly land between four and seven times running current, so substitute the real figure from the nameplate or the maker's data sheet before acting on these numbers.
Interlocked starting, one motor after another: the heavy pole already carries 9 A from three running motors, and one starting motor adds 18 A, for 27 A total. That is 0.9 times the frame rating — below it — so an inverse-time breaker holds the combination continuously and the staggered scheme stands with margin.
All four starting together: 4 × 18 A = 72 A on that pole, 2.4 times the rating. No magnetic element trips at a multiple this modest; the thermal element sets the time instead. Whether it holds 72 A for the seconds a 1/2 HP motor needs to accelerate is decided by that specific breaker's published time-current curve — read the curve at 72 A and compare it with your longest measured acceleration time. Where the curve will not hold, the fixes are interlocking the starts or stepping up one frame to a 40 A MCCB with its conductors resized for the larger protection.
The check repeats downward: the group breaker's magnetic trip should sit above what the per-motor breakers let through, so a fault at a motor clears at that motor's breaker and the rest of the panel keeps running. How low-instantaneous coordination keeps every feeder protected walks the feeder side of that reasoning.
Size the conductors the breaker protects #
NFPA 70 Article 430.53 allows several motors on one circuit only where the conductors meet the ampacity rules, and 430.24 sets that minimum: the sum of every motor's full-load current plus 25% of the largest motor in the group. On the heavy pole that is four motors' full-load currents plus a quarter of one motor's current, 12.75 A.
The group breaker also protects every conductor downstream of it, and those conductors must be protected at the 30 A rating. 10 AWG copper, at its 35 A ampacity in the 75°C column of Table 310.16 (NFPA 70, National Electrical Code, 2023 edition), clears both the group minimum and protection at the rating with margin; terminal temperature ratings decide which ampacity column applies, so confirm the finished ampacity with your authority having jurisdiction and the equipment documentation. The pairing of a motor-circuit conductor with its overcurrent device — including why an undersized conductor with an oversized breaker fails the rule — is worked through in how a motor branch conductor pairs with its breaker, and the same group arithmetic applied to three motors behind one feeder breaker on a 208 V system is in sizing a feeder breaker for three motors on one 208 V feeder.
Give every motor its own breaker and its own overload #
Table 430.52 sets the per-motor branch device: an inverse-time breaker at 250% of full-load current gives 250% × 3 A = 7.5 A, rounded up to the next standard size listed in 240.6(A), which is 10 A. Where a motor needs more to accelerate, Article 430 permits raising an inverse-time breaker to 400% for ratings of 100 A and less — 12 A here, which is still the 15 A standard frame.
Those per-motor devices are miniature breakers, not second molded-case units, and the two classes differ in interrupting capacity, adjustment and intended duty; the MCB-versus-MCCB comparison of breaker classes sets out where each one fits.
Breakers, group or individual, protect conductors and wiring against short circuits and ground faults. Running overload protection is a separate layer that must respond to each motor's own current: an overload relay, or the integral thermal protector or impedance protection Article 430 accepts for small motors when the marking shows it. Skip that layer and a stalled fan or jammed load cooks the windings while no breaker ever trips — the failure documented in why motors burn up with no overload trips.
The sizing procedure, start to finish #
- Plan the split from the drawings, then de-energize the panel, lock it out and verify absence of voltage before opening anything. Any later live measurement follows the safe-work practices of NFPA 70E, 2024 edition — rated meter, arc-rated PPE — and your authority having jurisdiction confirms local amendments.
- Measure the phase-to-neutral voltage at the terminals and compare it with the 219.4 V calculation and the nameplate tolerance band.
- Tabulate which motors land on which pole — three on two phases, four on the heavy pole — and record each pole's running current.
- Pull each motor's locked-rotor current from its nameplate or the maker's data sheet, and fix how many motors may start together.
- Run the starting check: the staggered case holds below the frame rating on its own; the simultaneous case goes to the published time-current curve, and where the curve will not hold it, stagger the starts or step up to the 40 A frame.
- Set the group breaker at 30 A and run 10 AWG copper feeders, whose 35 A ampacity covers both the 30 A protection requirement and the 12.75 A group minimum.
- Fit a 10 A inverse-time breaker at each motor — the 7.5 A calculation rounded up to the next standard size — moving to the 15 A frame only where the 400% starting allowance is genuinely needed, and confirm a running overload at every motor.
- Energize-test the worst permitted combination: run the starting sequence, record the three pole currents, and confirm neither the group breaker nor any motor device trips unintentionally.
The decision #
Fit the 30 A three-pole MCCB, feed it with 10 AWG copper, put a 10 A breaker and a running overload on every motor, and interlock the starts so the heavy pole never has two motors accelerating at once — that combination carries every permitted operating state, and each figure remains an estimate to confirm against the governing code edition and the equipment documentation. If the four-motor pole must be able to start together, one check decides: 72 A at 2.4 times the rating against the manufacturer's published curve. Hold it longer than the longest acceleration and the frame stands; miss it and the group breaker moves to 40 A with conductors resized to match.
Questions asked
How much current does the neutral carry with the three-three-four split?
About 3 A in the neutral. Adding the three pole currents as phasors 120 degrees apart, the components of the two 9 A groups cancel each other and 12 − 4.5 − 4.5 = 3 A remains. Size the neutral for the maximum unbalanced load anyway, and recalculate before any motor moves to a different phase.
Do the numbers change when you use NEC table currents instead of nameplate data?
Where the NEC governs, motor calculations use Table 430.248, which lists 4.9 A full-load current for a 1/2 HP single-phase motor at 230 V. Four motors on the heavy pole then total 19.6 A running — still well inside the upstream rating — but redo the per-motor breaker sizing, the conductor check and the overload settings with 4.9 A before finalizing the design.
What if the measured phase-to-neutral voltage is not close to 219 V?
Act below roughly 207 V. General-purpose motors hold rated performance within ±10% of nameplate, which for a 230 V winding means about 207 to 253 V. Under-voltage cuts torque and pushes running current up, eroding the margin this sizing relies on, so a persistent low reading calls for a transformer tap change or a buck-boost transformer before the motors go into service.