Current IntelPower LibraryShop main store

Troubleshooting

Soft starter overload trip when a generator fails

Motors and motor starters Published 6 min read By Current Intel engineering team

Short answer

The overload trip is the starter's thermal protection responding to real motor heating caused by the voltage sag, extended acceleration or a mechanical reload, not a starter fault. Find and fix the supply disturbance and load condition; raising the setting removes protection the motor still needs. Most starters store trip events, not voltage records, so capture the disturbance with a power-quality recorder.

On this page
  1. What the LED pattern does and does not tell you
  2. What a sag does to the motor
  3. Worked example: heating during a sag to 80 percent voltage
  4. Checks before you touch the settings
  5. Correcting the cause
  6. Questions asked

When a soft starter trips on overload during a generator failure, the overload indication is almost always correct: the motor really did overheat, because the sag cut its torque, it slowed and drew elevated current while the compressor kept demanding torque. The starter did its job. The mistake to avoid is treating the trip as a nuisance and raising the setting; the fix is to find what the supply actually did and how the compressor was loaded, then correct that cause and coordinate the restart.

One caution before anything else: de-energize the starter and the motor feeder, lock out and test for absence of voltage before opening the enclosure or the motor terminal box, and use appropriately rated instruments and qualified personnel for any energized measurement.

What the LED pattern does and does not tell you #

A typical pattern on a starter that trips this way is a red overload indication on, a green device-status indication on, and the failure indication off. Read against the operating instructions for the installed model, that means the thermal overload function reached its operating threshold and the electronics report themselves healthy. It does not tell you:

  • what the supply voltage, frequency or phase balance did during the generator failure
  • whether the motor was accelerating, running loaded or reloading when it tripped
  • how long the high-current period lasted
  • whether repeated starts had already consumed the motor's thermal margin

Most soft starters store a fault history: the trip category, a counter, sometimes the current at trip. They generally do not record a voltage trace of the network disturbance. If you need the input-voltage history, capture it yourself with a power-quality recorder on the motor feeder; the starter's indication LEDs are a status report, not a voltage record. For the reset-side reading before you clear anything, see diagnosing a soft starter fault or alarm before resetting it.

What a sag does to the motor #

A soft starter controls motor voltage during the start to limit current and torque. It is not a voltage regulator and cannot restore a collapsing network. Induction motor torque falls roughly with the square of the voltage, so a deep sag cuts accelerating torque sharply. Three things follow:

  1. If the compressor still demands torque, the motor slows and its slip and current rise.
  2. If the sag hits during acceleration, the reduced torque stretches the high-current acceleration period, and the thermal model accumulates heating faster than a normal start would.
  3. If the motor is already hot from a recent start, a short disturbance can be enough to trip.

Voltage unbalance from uneven loading on the remaining generation makes it worse, because unbalanced phase voltages produce disproportionately unequal phase currents and extra heating. Overload protection evaluates accumulated heating, which scales closely with current squared and with duration, so it judges the whole event, not one instantaneous peak.

Worked example: heating during a sag to 80 percent voltage #

These are illustrative example inputs, not ratings of any particular starter or motor.

Inputs:

  • Motor full-load current from the nameplate: 60 A, used here as the 100 percent current basis
  • Sag depth on the motor terminals: 80 percent of rated voltage, an example value for a network that loses one generator
  • Measured stator current during the sag after the motor slows: 72 A, an example measured value
  • Duration at that current before the supply recovers: 20 s

Rule: heating in the stator scales with current squared, so the heating rate relative to rated full-load heating is (I / FLC) squared.

Arithmetic: 72 A divided by 60 A is 1.2, and 1.2 squared is 1.44. The motor heats at 144 percent of its normal full-load rate during those 20 seconds, so the thermal model accumulates the heating of roughly 29 seconds of full-load running (20 s multiplied by 1.44) in that interval. If the motor started the disturbance already warm from a recent start, that extra accumulation can close out the remaining thermal margin and trip the overload.

Decision: any event that pushes sustained current meaningfully above the nameplate value for tens of seconds will trip a correctly set overload, and it should. If your recorder shows exactly this pattern, the protection is right and the correction belongs on the supply recovery or the load, not the dial.

Checks before you touch the settings #

Work this list in order and record each result before changing anything, so one change at a time can be evaluated.

  1. Record the protection basis. Write down the motor nameplate full-load current, the connection (wye or delta), and every overload-related setting on the starter. The configured protection must match the nameplate and the manufacturer's application instructions. The method is the same as for setting overload relays from motor nameplate full-load current.
  2. Identify the operating state at trip. Determine from the compressor controls whether the machine was accelerating, running loaded, unloading or attempting a restart when the generator failed, and note the time relationship.
  3. Record the electrical event. Fit a power-quality recorder on the motor feeder and capture all three phase voltages, frequency and phase currents through the whole event, including recovery. Healthy running should show balanced currents near the nameplate value with no unexplained phase disparity; if running current sits above the nameplate value even without a disturbance, see motor running over nameplate amps after soft starter bypass.
  4. Check the compressor load path. Inspect the unloading sequence, pressure demand and mechanical condition. The machine must not reload the compressor during acceleration; unintended loading under reduced voltage is a common trip maker.
  5. Inspect the power path. Check feeder connections, protective devices and switching equipment per your site maintenance procedure for loose connections or an interrupted phase that would explain the current rise.

Correcting the cause #

With the record in hand, classify the initiating condition. If the recorder shows voltage or frequency leaving the permitted band before motor current rises, the problem is generation capacity and network recovery: shed load or delay the compressor's restart through the plant control system until supply conditions are acceptable. If the supply readings stay acceptable while current rises, look at compressor torque demand, mechanical condition and acceleration time.

Coordinate the restart deliberately. Where the network cannot sustain the compressor through a disturbance, inhibit the starter on supply disturbance and release restart only after voltage has recovered and stabilized, with the compressor unloaded. Avoid repeated restart attempts while the network is still recovering; each one draws starting current against a weak supply and burns thermal margin. Do not select a slower trip response just to suppress trips: any adjustable characteristic is chosen from the motor's thermal limits and the starter's instructions, and if the dial has drifted, see what the thermal overload relay current setting dial shifts before returning it to the nameplate basis.

The decision in one line: an overload trip during a generator failure is the motor's protection reporting real sag-driven heating, so fix the supply recovery, the load state or the restart scheme, leave the overload set to the nameplate full-load current, and use a power-quality recorder for the voltage history the starter does not keep.

Questions asked

Does a soft starter keep a record of the input voltage during a trip?

Most soft starters store a fault history: the trip category, a counter and sometimes the current at trip, readable from the display or a parameter group in the operating instructions. They generally do not record a voltage waveform or a voltage-versus-time trace of the supply disturbance. To see what the network actually did during the generator failure, install a power-quality recorder on the motor feeder and correlate its timestamped record with the generator and compressor events.

Can I just turn up the overload setting so the compressor rides through?

No. The trip is reporting genuine motor heating from elevated current during the sag or an extended acceleration. Raising the setting delays or removes the protection the motor depends on and can let it cook during the next, longer disturbance. Correct the cause first: the supply recovery, the compressor load state or the restart coordination. If the protection configuration disagrees with the motor nameplate full-load current or the documented duty, correct it to match the nameplate, not to suppress the trip.

Why does the overload LED come on instead of a supply or failure fault?

A soft starter watches its supply terminals against fixed thresholds, but a slow sag that stays inside the undervoltage window never crosses them. The motor, meanwhile, slows and draws elevated current, and the thermal model accumulates that heating until it trips. The overload indication is then accurate: the protection that responded is the motor thermal one. The supply event behind it is visible only on an external voltage record.

Keep reading

  • Troubleshooting

    Why an autotransformer starter fails after a voltage sag

    A voltage sag deeper than the contactor's hold-in voltage and longer than its dropout time opens the starter while the run command stays on. The coil picks the contactor back in hundreds of milliseconds later, into a coasting motor whose residual voltage is out of phase with the restored supply. That reconnection transient through the autotransformer tap winding wrecks it; the fix is residual-voltage-supervised restart logic, not a new transformer.

    Motors and motor starters

  • Troubleshooting

    Diagnosing a soft starter fault or alarm before resetting it

    Record the exact fault or alarm text, the values shown with it, and whether it appeared during start, run, or stop, before you reset, because a reset clears the diagnostic context. Then check the supply, the starter's documented ratings, the configured motor data, and the load: most trips trace to one of those four, not to a failed starter.

    Motors and motor starters

  • Troubleshooting

    Motor starters trip when MCC doors are closed

    The trips are real protection, not nuisance: a thermal overload relay without ambient compensation responds to enclosure air temperature, so doors open plus a fan suppresses trips while motor heating continues. A 10-12 V spread on 480 V is 1.0% to 1.7% voltage unbalance, above the NEMA MG 1 limit of 1.0%, and a 60-70 A current spread is severe. Close the doors, pull the fan, and fix the upstream supply that survived the chiller and MCC replacement.

    Motors and motor starters