Troubleshooting
Why an autotransformer starter fails after a voltage sag
Short answer
A voltage sag deeper than the contactor's hold-in voltage and longer than its dropout time opens the starter while the run command stays on. The coil picks the contactor back in hundreds of milliseconds later, into a coasting motor whose residual voltage is out of phase with the restored supply. That reconnection transient through the autotransformer tap winding wrecks it; the fix is residual-voltage-supervised restart logic, not a new transformer.
On this page
An autotransformer reduced-voltage starter that dies after a storm was usually not killed by the sag itself. The sag pulled the contactor coil below its hold-in voltage, the contactor opened while the run command stayed on, and when the supply recovered the coil picked the contactor back in. But the motor had been coasting, electrically isolated, for hundreds of milliseconds, still spinning with a decaying residual voltage that no longer matched the restored supply in magnitude or phase. Closing into that residual voltage drives a transient through the autotransformer's tap connection far above anything a normal start produces, and the short-time-rated tap winding comes apart. The fix is restart supervision in the controls, not a bigger transformer.
The failure sequence: sag, dropout, coast, reclose #
Walk the event in order. The sag arrives and the coil voltage falls with it. Below the coil's hold-in level the armature releases within a few tens of milliseconds, opening the motor circuit. The run command, a maintained contact or a latched PLC output, is still true, so nothing in the sequence records a stop.
The motor is now open-circuit. Its flux decays at a rate set by the rotor circuit's open-circuit time constant, while a large compressor barely slows in half a second. The motor terminal voltage falls in magnitude but keeps a live phase relationship to the rotor position, drifting away from the supply as the machine coasts.
When the sag ends, the coil re-energizes and the contactor recloses after its pull-in time. The voltage across the circuit impedance at that instant is the vector difference between the restored supply and the motor's residual voltage. If the two are close to 180 degrees apart, the driving voltage is nearly their sum, and the current that follows passes straight through the start connection and the tap winding. Investigations of failed medium-voltage autotransformer starters consistently found the damage on the taps with the fewest turns, the section with the least impedance to limit that current, and the worst cases involved transitions forced while the motor was near locked-rotor conditions.
How deep and how long a sag must be to release the contactor #
The rule is simple: if the coil voltage sits below the hold-in level for longer than the dropout time, the contactor releases. Most AC-operated coils hold in down to roughly 65 to 75 percent of nominal coil voltage, so a sag below about two-thirds of nominal is already a candidate. A seven-cycle event at 60 Hz lasts 117 ms, several times a typical dropout time, which is why a short-looking utility dip can still open a medium-voltage starter.
The depth that matters is the depth at the coil, not at the utility meter. Read the starter's control drawings to find where control power comes from: a control transformer off two phases, or a three-phase coil. A sag reported on one phase depresses the coil only if the coil actually sees it. If a power-quality recorder captured the event, align its channels with the control circuit before you conclude anything.
That sag is usually the whole bus dipping under someone's starting current, and the arithmetic for how far it dips is the same as estimating voltage sag from motor inrush current. One more thing to check while you are in the drawings: at the 65 percent tap the motor sees 65 percent of rated voltage, so its torque is roughly 0.65 squared, about 42 percent of full-voltage torque. A heavily loaded compressor that barely accelerates on the tap drags the start sequence out and keeps the winding on long-duration duty, which is the cumulative-heating failure mode this article is not about.
Example: timing the reconnection after a seven-cycle sag on a 2300 V motor #
These are illustrative inputs; take the contactor timings from your starter's documentation and the time constant from your motor's test report.
- Supply: 2300 V, three phase, 60 Hz.
- Sag: below half of nominal for 7 cycles. Duration: 7 divided by 60 Hz equals 0.117 s, about 117 ms.
- Contactor dropout time: 50 ms. Since 117 ms is greater than 50 ms, the contactor separates roughly 50 ms into the sag.
- Contactor pull-in time: 350 ms. The supply recovers at 117 ms, so the contactor recloses at about 117 plus 350, or 467 ms.
- Motor open-circuit time from separation to reclose: 467 minus 50, about 417 ms, or 0.42 s.
- Assumed open-circuit time constant: 0.5 s, a typical order of magnitude for a medium-voltage machine but a value you must verify for your motor.
Residual voltage at reclose equals the pre-separation terminal voltage times e raised to the power of minus t divided by the time constant: e to the minus 0.42 divided by 0.5, which is e to the minus 0.84, about 0.43. So roughly 43 percent of rated voltage is still standing at the motor terminals. In the worst phase relationship the driving voltage is the sum: 1 plus 0.43, or about 1.43 per unit of rated, which is 1.43 divided by 0.65, about 2.2 times the voltage the tap connection sees in a normal start. Current scales with that driving voltage over the same circuit impedance, which is how a winding built for reduced-voltage starts gets destroyed in one closing.
Confirming the mechanism on your starter #
Before you open anything: de-energize, isolate and ground the starter per your medium-voltage switching procedure and verify absence of voltage at the terminals; in US plants that work falls under NFPA 70E, 2024 edition, and you should confirm the details with your authority having jurisdiction and the equipment documentation.
- Recover the sag recording. Establish whether the reported depth is phase-to-phase or phase-to-neutral and where the recorder sits relative to the starter.
- Read the control drawings. Identify the coil supply, which phases feed it, the run-command path, and whether a control-power interruption resets the start sequence.
- Time-align motor current, coil voltage, the run command, and every contactor auxiliary signal you have on one common time base.
- Look for the gap: a window of zero motor current between the sag and the reclose proves the motor circuit actually opened and the starter reconnected onto a spinning machine.
- If a recorder captured motor terminal voltage, read the residual magnitude and its phase relative to the restored supply at the closing instant. Auxiliary contacts tell you the mechanism moved; voltage and current records tell you what the closing did electrically.
- Inspect the failed winding. Deformation, displaced conductors, or damage concentrated at the tap section points to the reconnection transient; uniform browning points to accumulated thermal duty from long starts or repeated starts.
- Check the protection records. Distinguish a genuine trip from a dropout the controls never registered, because each calls for a different correction.
The fix: supervise residual voltage before any reclose #
Change the controls so that loss of the running contactor produces a definite stopped state: a maintained run request must never re-energize the start contactors on its own. Then choose the release criterion.
The robust choice is residual-voltage supervision. Measure the motor terminal voltage and block the restart until it has decayed below about a quarter of rated, which caps the worst-case vector sum near 1.25 per unit instead of the 1.43 per unit in the worked example. Set the final threshold with the motor and starter documentation and your protection engineer.
A time delay is the simpler alternative, but it must be sized to your machine: about five open-circuit time constants takes the residual below one percent, which for the assumed 0.5 s constant means roughly 2.5 s of inhibition. Use your motor's actual constant, and verify the decay once with a measurement after a controlled stop.
Control-power ride-through, a coil hold-in device or a UPS on the control circuit, can keep the starter closed through shallow sags, but treat it as an engineered modification: it only helps if the driven machine can keep running through the dip and the protection allows it. Where it cannot, blocking the restart is the correct outcome, not a defect.
Finally, after a confirmed transient event, inspect the autotransformer, the motor insulation, and the contactors before any re-energization, and check the transformer nameplate's start duration and starts-per-hour duty against your acceleration records. The transformer that failed was doing its rated job; the sequence around it was not.
Questions asked
How deep does a voltage sag have to be to drop a starter contactor out?
Most AC-operated contactor coils hold in down to roughly 65 to 75 percent of nominal coil voltage, and once the coil voltage falls below that the armature releases within a few tens of milliseconds. So any sag that pulls the coil supply below its hold-in level for more than about two cycles can open the motor circuit. Which phase feeds the coil decides whether a reported sag actually reaches it.
Why does the autotransformer fail instead of the motor?
The reconnection transient flows through the start connection, so the tap section takes it first. That section has the fewest turns and the least impedance to limit current, and the winding is short-time rated for a normal start only. Investigations of failed medium-voltage autotransformer starters found damage concentrated on the taps with the fewest turns. The motor stator can be damaged too, so inspect it before returning the machine to service.
Is a fixed restart delay enough to prevent this failure?
Only if the delay is longer than about five open-circuit time constants of your motor, which is where the residual voltage has decayed below roughly one percent. Read that time constant from the motor test report or measure the decay after a controlled stop. A generic delay picked from a handbook can still reclose on significant residual voltage, so residual-voltage supervision is the safer criterion.
Does a failure like this mean the autotransformer was undersized?
No. The winding is sized for the duty on its nameplate: a defined maximum start duration and a limited number of starts per hour. An out-of-phase reclose or repeated uncommanded starts through the tap exceed that short-time duty even on a correctly sized transformer. Check the nameplate duty against your acceleration records and event history before ordering any replacement.