How-to
TCC plot reference voltage for a 277 V branch breaker
Short answer
Enter 480 V, the system voltage, as the reference when you plot a single-pole 277 V branch breaker from a 480Y/277 V panel. The trip unit responds to current magnitude only and has one curve for the frame. If your curve software shifts the curve by a factor of 1.732 when you enter 277 V, the shifted plot shows coordination that does not exist and must be discarded.

On this page
If your curve software asks for a reference voltage while you plot a single-pole branch breaker from a 480Y/277 V panel, enter 480 V, the system voltage. The panel is one system with a line-to-neutral tap; the reference belongs to the system, not to the load voltage at the branch. The trip unit responds to current magnitude only, so the breaker has one curve regardless of which fault type produced the current. The one place a base-voltage entry can go wrong is the plot itself: some curve packages shift a curve entered on the wrong base by a factor of the square root of 3, which manufactures coordination results that do not exist. This article gives the checks, a worked example of the shift, and the replot procedure.
Take the reference voltage from the panel, not the branch load #
Read the voltage off the panelboard nameplate and its source transformer. A panel marked 480Y/277 V, three-phase, four-wire, is one system with two voltages: 480 V between lines and the line-to-neutral tap. The TCC reference is the system voltage, even though the branch breaker sees only the neutral-relative voltage across its poles in normal service. If the nameplate is missing or unreadable, stop and read the source transformer secondary nameplate and the one-line diagram before plotting anything. Most wrong entries come from copying the lighting-load voltage rating of the circuit into a field that asks for system voltage.
The trip unit cannot tell which fault produced the current #
A thermal-magnetic or electronic trip unit senses current magnitude. It has no input that distinguishes a phase-to-phase fault from a phase-to-ground fault on this panel, so it applies the same curve to both. The same holds for pole count: a 30 A single-pole breaker and a 30 A three-pole breaker of the same frame and trip type share one curve. This is the same current-only response that sets the Im instantaneous setting on an MCCB trip unit; voltage enters the trip decision nowhere.
On the plot, the axes are time and current. Voltage matters only when the software converts current between voltage bases, which it does when a transformer sits between two devices. Within one panel of this type there is no transformer between the feeder and the branch, so there is nothing to convert.
A worked example of the base-voltage shift #
Example inputs, illustrative throughout: a 20 A single-pole thermal-magnetic branch breaker in a 480Y/277 V lighting panel; the manufacturer's published curve for that frame spans an instantaneous band of 8× to 12× rating, that is 160 A to 240 A; the short-circuit study gives 25 kA of available current at the panel bus.
Plot the breaker on the system base and read the instantaneous pickup at 160 A (8 × 20 A). Now duplicate the plot with the base entered as the line-to-neutral voltage. If the software applies a voltage-ratio conversion between bases, that same curve point moves to 160 A × 1.732 = 277 A, or to 160 A ÷ 1.732 = 92 A, depending on which direction the tool applies the ratio. Overlay the two sheets and divide one pickup reading by the other: since 480 V ÷ 277 V = 1.733 and the square root of 3 = 1.732, a ratio of 1.732 between the curves identifies the conversion, and the shifted sheet is wrong. If the curves overlap, the tool ignores the base for same-system devices and either entry plots the same curve; standardize on the system base anyway, so every device on the sheet shares one reference.
Plot the branch breaker on the system base #
- Set the reference voltage of the plot to the system voltage for every device on the sheet, the branch breaker included. Mixing bases in one plot is the recurring error: a single curve entered on the neutral-voltage base can shift alone, and the overlap on screen stops representing real coordination.
- Select the breaker from the curve library by its exact catalog data, meaning frame, trip type, ampere rating and pole count, not by a similar-looking entry.
- Place the fault-current marker at the available current for the fault type being evaluated, taken from the short-circuit study at the panel bus; the choice between bolted and arcing values is covered in which bolted fault current to use for breaker duty and arc flash.
- Plot the upstream feeder device and every other protective device on the same base, then read the clearing time of each at the marker. Example read, illustrative: at the 25 kA marker the branch clears in 0.02 s and the feeder in 0.5 s, so the downstream device clears first with margin and the study result stands. If the plot shows the feeder clearing first, re-check the base voltage before re-coordinating anything.
- Spot-check the plotted curve against the manufacturer's published curve for the same catalog number at a few current points before you circulate the sheet.
The general craft of building and reading these sheets, including axis setup, legend handling and overlay discipline, is the same one described in plotting TCC curves for medium-voltage relay and breaker coordination.
Symptoms a wrong base leaves on the plot #
| Symptom | Likely cause | Fix |
|---|---|---|
| Branch curve sits a factor of 1.732 left or right of the others | Base entered as the neutral voltage and the tool applied a voltage-ratio conversion | Re-enter the base as the system voltage and replot |
| Branch appears to coordinate, or miscoordinate, with the feeder | Curve shifted by the base error | Replot every device on one base and re-read the margins |
| Fault marker for the branch disagrees with the study | Marker taken from a different bus or fault type | Use the study value at the panel bus for the fault type evaluated |
| Same-frame single-pole and three-pole curves differ | Different catalog entries selected in the library | Verify catalog number and trip type; the difference is not a voltage effect |
What the plot does not tell you #
A TCC carries current and time only. It cannot prove the breaker's voltage rating is adequate for the system, and a shifted curve proves nothing at all. Check the single-pole breaker's marking and datasheet for a rating suitable for 480 V line-to-line duty on a grounded neutral system, separately from the curve work. IEEE 242-2001, the IEEE recommended practice for protection and coordination of industrial and commercial power systems, describes the time-current curve method used here; the local authority having jurisdiction and the equipment documentation govern the installation. Plotting is desk work, but if the study's outcome sends you into the panel to replace or re-set a breaker, de-energize, lock out and verify absence of voltage first.
Questions asked
Does curve software set the reference voltage automatically?
Some packages set the reference voltage of the sheet to the system nominal voltage of the first reference device placed on it. Treat the automatic entry as a hypothesis, not as proof: replot the branch breaker on an explicit system base and confirm the two curves overlap before either sheet is used for a coordination decision.
Will a single-pole branch breaker see the same fault current as the panel bus?
Yes for magnitude: the breaker's line terminal sits on the panel bus, so the available fault current there is what the trip unit sees for both a phase-to-phase and a phase-to-ground fault. The only reduction is the impedance of the short run of branch conductor between the bus and the breaker, which is negligible at typical branch lengths.
What if the curve still moves after I enter the system voltage?
Stop using that sheet for any protection decision. Check the library entry for the breaker against the manufacturer's published data, then check the software's voltage-base settings against its own documentation. If the behavior remains unexplained, take the catalog number, the plot settings and both overlays to the software vendor's official support.