Current IntelPower LibraryShop main store

Troubleshooting

What the Im setting on an MCCB trip unit means

Protection: breakers, fuses and SCCR Published 9 min read By Current Intel engineering team

Short answer

Im is the instantaneous magnetic pickup of an MCCB trip unit — the current above which the breaker trips with no intentional delay. Set the dial so the worst starting transient stays below the pickup's lower tolerance bound, the minimum fault current sits above the upper bound, and the frame's interrupting rating covers the available fault current; the worked example lands at 5 × In, or 1250 A.

On this page
  1. What the Im marking means
  2. The rule that produces the dial position
  3. Worked example: a 100 hp motor feeder on a 250 A sensor
  4. Check the fault current from both directions
  5. Troubleshooting a breaker that trips on start
  6. The decision for each case
  7. Questions asked

Im is the instantaneous pickup of an MCCB trip unit: the current above which the breaker opens with no intentional delay, the steep band at the right of the time-current curve. The marking names a function, not a value — the dial gives a multiple of a reference current, and the ampere result depends on that reference and on the tolerance band published on the breaker's own curve sheet. The rule behind the dial position is fixed even though the number is installation-specific: hold the worst legitimate transient below the pickup's lower tolerance bound, keep the upper bound below the minimum fault current the function must clear instantaneously, and confirm that the frame's marked breaking capacity covers the maximum available fault current. The worked example below takes a 100 hp, 460 V motor feeder to a dial position, and the closing section gives the decision for each case.

What the Im marking means #

On most adjustable MCCBs, Im marks the magnetic instantaneous pickup. The same trip unit's documentation marks the settings alongside it: Ir for the long-time overload pickup, Isd or tsd for the short-time pickup and its delay, and Ii for the instantaneous function on many electronic units. The letters are manufacturer conventions, and identical letters can mark different functions in different families, so read the legend on the breaker face and the trip unit's own curve sheet before treating any dial as an instantaneous pickup.

A dial position is neither an ampere value nor a clearing time. Published settings are multiples of a reference current, usually In, the sensor or rating-plug rating; one manufacturer's published curve table lists an instantaneous pickup adjustable from 2 to 15 × In, and other families scale from different references. Above pickup the mechanism releases within milliseconds, and total clearing adds contact parting and arcing time. A breaker with no dial prints a single ampere value on its label: that fixed pickup is verified, not set.

The rule that produces the dial position #

One position on the dial has to pass three checks that pull in opposite directions, which is why a value copied from another panel rarely fits.

  • Ride-through: the lower tolerance bound must sit above the worst legitimate RMS transient the circuit produces — a motor's locked-rotor current, transformer energization, or several loads connecting together. If the envelope reaches the band, the breaker trips on a healthy circuit.
  • Detection: the upper tolerance bound must sit below the minimum bolted fault current assigned to this function, normally the fault at the feeder's far end on the weakest supply arrangement. A fault landing between the two bounds is not guaranteed to trip instantaneously; it drops onto the short-time or long-time band and clears more slowly.
  • Interrupting duty: the breaking capacity marked on the breaker — Icu and Ics under IEC 60947-2 (2016 edition, with later amendments), the product standard covering low-voltage circuit breakers of this kind, or the kA value printed on a UL 489-listed breaker's label — must equal or exceed the maximum available fault current at its line terminals. No dial position changes this.
  • Coordination: check the manufacturer's selectivity tables for the exact pair of devices. Backup, where an upstream device helps interrupt a fault beyond its own rating, is not selectivity, and an eyeball comparison of two curve lines proves neither.

Manufacturers publish the pickup with a tolerance band on the curve sheet — ±20% is the band many adjustable magnetic families print — and the design uses the band your own sheet shows, not a borrowed one. The envelope to compare is RMS: the first-cycle asymmetrical peak reads far higher than the RMS value, and holding that peak against a dial setting is the comparison dissected in why motor start peaks don't compare to instantaneous breaker settings.

Worked example: a 100 hp motor feeder on a 250 A sensor #

Every input here is illustrative: a hypothetical magnetic-only MCCB with a 250 A sensor, an Im dial of 2–10 × In and a published ±20% tolerance, protecting a 100 hp induction motor at 460 V, three-phase, 60 Hz together with a separate overload relay, plus an example fault study. The method is the point; your dial range, tolerance and fault numbers come from your own curve sheet and study.

Quantity Example value Basis
Motor full-load current 124 A NFPA 70 (National Electrical Code), 2023 edition, Table 430.250, 100 hp at 460 V
Locked-rotor multiplier 6.5 × FLA code letter G spans 6.29–7.09 kVA per horsepower (NEC Table 430.7(B)); the example takes 6.5
Starting envelope, RMS 806 A 6.5 × 124 A
Sensor rating In 250 A example breaker's rating plug
Pickup tolerance ±20% example breaker's published curve sheet
Im dial range 2–10 × In example breaker's face legend
Ride-through floor 1008 A 806 A ÷ 0.8, rounded up
Chosen dial position 5 × In = 1250 A next position above 4.03 × In
Lower bound and margin 1000 A, 24% above the envelope 1250 × 0.8
Upper bound 1500 A 1250 × 1.2
Code ceiling 1364 A 1100% of 124 A, NEC 430.52
Minimum fault current at the motor terminals 2400 A example study, weakest supply arrangement
Available fault current at the MCC bus 25 kA example study
Marked breaking capacity Icu = Ics = 36 kA at 460 V example breaker marking, IEC 60947-2

The full-load current is a table value: NFPA 70, the National Electrical Code, 2023 edition, lists 124 A for a 100 hp, 460 V three-phase motor in Table 430.250. Code letter G places locked-rotor demand between 6.29 and 7.09 kVA per horsepower (Table 430.7(B)); taking 6.5 gives an RMS starting envelope of 6.5 × 124 A = 806 A.

Ride-through: the −20% tolerance means the dial must land at or above 806 A ÷ 0.8 = 1008 A. In dial positions that is 1008 A ÷ 250 A = 4.03 × In, so the dial moves to the next position, 5 × In = 1250 A. At that position the lower bound is 1250 × 0.8 = 1000 A, a 24% margin over the envelope, and the upper bound is 1250 × 1.2 = 1500 A.

Code ceiling: NEC 430.52 lists instantaneous-trip motor protection at 800% of full-load current — 992 A here — and permits 1100% where starting demands it, so the ceiling is 1100% × 124 A = 1364 A and the chosen setting sits inside it. The dial position is an estimate from table and example values; check it against the code edition in force, your AHJ's local amendments and the breaker's documentation.

Check the fault current from both directions #

Detection needs the minimum fault current and interrupting duty needs the maximum, and they are different numbers from the same study. Cable impedance and a soft source can pull the bolted fault at the motor terminals far below the bus value; the example study gives 2400 A there. Against detection: 2400 A ÷ 1500 A = 1.6, so terminal faults sit well above the upper bound and inside the instantaneous band. Which bolted current serves breaker duty and which serves arc flash is its own question, taken up in which bolted fault current to use for breaker duty and arc flash.

The same study gives 25 kA available at the MCC bus, and the example breaker marks Icu = Ics = 36 kA at 460 V, so the frame covers the location. The dial never moves this number: if the current available at the line terminals ever exceeds the marked breaking capacity, the cure is a different breaker or a rated assembly arrangement, not an adjustment. How the available value relates to the calculated fault current on the load side is worked out in available fault current vs secondary short-circuit current, and applying the same arithmetic to rating choice for both momentary inrush and interrupting duty is the subject of selecting MCCB ratings for momentary and interrupting duty.

Troubleshooting a breaker that trips on start #

De-energize, lock out and test for absence of voltage before opening terminal covers or the trip-unit access flap; NFPA 70E, 2024 edition, governs the narrow set of energized diagnostic tasks, and your AHJ and the breaker manual set the work rules. When the trips fall on starting, work the list in order and touch the dial only at the end:

  • Read the trip indication before anything else. An overload flag, an earth-fault flag and an instantaneous flag send the investigation to different places; where the breaker gives no flag, compare the event duration with the curve bands instead of diagnosing from the handle position.
  • Capture the starting envelope with a true-RMS recorder that spans the whole start; a clamp reading taken after the motor is running never sees the event. For trips that hit some starts and not others, the closest walkthrough is troubleshooting intermittent instantaneous motor start trips.
  • Convert the dial to amperes with the documented reference, In or Ir from the face legend, then apply the printed tolerance band. Reading a multiple against the wrong reference shifts the real pickup by the ratio of the two references.
  • Compare the captured envelope with the band's lower edge. Envelope inside the band: a ride-through failure, so raise the dial by the worked example's arithmetic. Envelope below the band on a breaker that trips anyway: suspect the mechanism or the trip unit itself, and test or replace it rather than raising the setting over a fault.
  • Rebuild the envelope for group events. Several motors restarting after a voltage dip, or a transformer energizing on the same feeder, produce a combined transient the pickup must ride through; the single motor's number is not the test.

The decision for each case #

  • Trips on healthy starts with the captured envelope inside the band: raise the dial to the next position whose lower bound clears the envelope, exactly as the worked example's arithmetic does, and record the ampere value beside the dial position. If no position clears the envelope while detection still holds, the circuit needs a soft starter or a protector with a higher pickup range, not a compromise dial.
  • Trips with the envelope below the band: stop adjusting. Chase connections, insulation and the reference current first, and test the trip unit; a raised setting over a real fault only moves the damage.
  • Minimum fault current below the upper tolerance bound: the instantaneous function cannot be guaranteed for those faults. Leave the dial where ride-through requires it, confirm in a protection study that the slower band clears them acceptably, or add a function or zone — raising the dial moves detection the wrong way.
  • Available fault current above the marked breaking capacity: this breaker is the wrong breaker for the location, and no dial position fixes interrupting duty.

Set the dial from your breaker's curve sheet and your own fault study, and write both the ampere value and the dial position into the panel record once the checks hold.

Questions asked

Is Im the same thing as Ii on an electronic trip unit?

They do the same job — instantaneous tripping — but the reference often differs. On many electronic trip units the instantaneous pickup is labelled Ii and scales from Ir, the long-time setting, while a magnetic dial labelled Im usually scales from In, the sensor or rating-plug rating. Read the legend on your trip unit before converting a position into amperes: applying the wrong reference moves the real pickup by the ratio of Ir to In.

What if the MCCB has no Im dial at all?

A fixed magnetic or thermal-magnetic breaker has its instantaneous pickup built in and printed on the label as one ampere value. There is nothing to set. Verify the application instead: the printed value, with its tolerance band applied, must sit above the circuit's worst legitimate transient and below the fault currents the function is meant to clear. If it does not, the answer is a different breaker.

How should I capture the starting current?

Use a true-RMS power-quality meter or motor-start recorder set to log RMS across the entire start, not a clamp reading taken once the motor is running. The first cycles also carry asymmetrical peaks above the RMS envelope, and curve sheets plot pickup bands as RMS values, so compare RMS against RMS; reading the first-cycle peak against an RMS band wrongly condemns a breaker that behaved correctly.

Does raising Im improve coordination with downstream breakers?

Coordination comes from the manufacturer's selectivity or cascade tables for the exact device pair, not from the dial alone. Raising Im to reduce cascade risk also moves the ride-through margin and can let healthy starts through. Above the current-limiting region, published tables exist because overlapping curve lines do not decide the outcome.

Keep reading

  • Troubleshooting

    Why motor start peaks don't compare to instantaneous breaker settings

    The 1,111 A record is a probe-shaped peak from successful starts; the 900 A dial is the sinusoidal RMS of a magnetic element, and the two tripped starts were never recorded. Multiplying 900 A by √2 gives 1,272.8 A, valid only for a clean sinusoid, which a start never is. Record the next start with a DC-coupled probe on all three phases before touching the setting.

    Protection: breakers, fuses and SCCR

  • Explainer

    Checking a 2500 A incomer against a 1600 kVA transformer

    The corrected running load is 2196 A at 415 V, so the 2500 A incomer holds it with 304 A of margin, but the 1600 kVA transformer's rated secondary current is about 2226 A — 98.7 percent loaded. Accept both only after the long-time pickup is set at or below the transformer rating, every permitted start fits the trip curve, and the fault study clears the 100 kA withstand.

    Protection: breakers, fuses and SCCR

  • Selection guide

    Stopping breaker trips on 25 kVA transformer inrush

    Set a breaker with a programmable electronic trip unit so its instantaneous pickup sits above the transformer's inrush peak, and the energization trips stop with no added power hardware: for a 25 kVA, 400 V primary that is 36 A rated current and up to about 540 A first-cycle inrush. A motor soft starter is the fallback only if its documentation permits a transformer magnetizing load; resistor pre-insertion is the engineered option when the supply itself cannot tolerate the dip.

    Protection: breakers, fuses and SCCR