Troubleshooting
Three-phase motor will not run: tests before replacement
Short answer
Before replacing a three-phase motor that will not run, prove the fault with four measurements: balanced phase-to-phase voltage at the terminals during the start command (keep imbalance at 1 percent or less), continuity and balanced resistance through every winding, and an insulation resistance reading above rated kilovolts plus 1 megohm. Open windings, unbalanced resistance or a failed megger condemn the motor; everything else points upstream.

On this page
- What should I check before replacing a three-phase motor that will not run?
- Is voltage at the motor terminals proof the supply is good?
- How do I test the motor windings for continuity and balanced resistance?
- What should a megger read on a 460 V motor before you scrap it?
- Why does the reversing relay click but the motor still not run?
- Should I reset the overload relay and start the motor again?
- When is the verdict a dead motor instead of a circuit fault?
- Questions asked
A three-phase motor that sits silent with the contactor pulled in is not yet a proven bad motor, and voltage showing at its terminals does not make it one. The click from the reversing relay is the coil's armature moving; it tells you nothing about the power poles. Replace the motor only when the measurements say to: balanced phase-to-phase voltage at the terminal box during the start command, continuity through every winding, resistance that matches leg to leg, and an insulation reading above the standard's floor. The sections below run those tests in the order that splits a motor fault from a circuit fault fastest, with the numbers to judge each result against.
What should I check before replacing a three-phase motor that will not run? #
Run five checks before you order a replacement: terminal voltage during the start command, continuity through every winding, balanced winding resistance, an insulation resistance test to frame, and a hand-turn check on the shaft — voltage present at quiet terminals proves none of them.
Start from the nameplate, because rated voltage, full-load current and the connection arrangement are the reference every later reading is judged against. Find the connection diagram in the manufacturer's documentation before touching a lug: a reversing-duty motor of the kind that drives a tap changer or a valve often brings out more than three power leads. The sequence:
- Phase-to-phase voltage at the motor terminal box on all three pairs, contactor pulled in and start command held — then the drop across each contactor and reversing pole while the starter stays energized.
- Continuity between every pair of motor leads, with the motor isolated from the circuit.
- Resistance balance across those same pairs.
- Insulation resistance from winding to frame with an insulation tester at the correct DC test voltage.
- Shaft rotation by hand, plus a look and a smell for cooked insulation.
Opening the terminal box with the circuit live is energized work your site's electrical safety program governs; NFPA 70E, 2024 edition, is the standard for electrical safety in the workplace and covers verifying an electrically safe work condition, so confirm the required practice with your program and the authority having jurisdiction. Checks two through five run only on a de-energized, locked-out motor with the absence of voltage verified.
Is voltage at the motor terminals proof the supply is good? #
No — read the three phase-to-phase voltages while the contactor is pulled in and the motor is connected, then compute percent imbalance as the largest deviation from the average divided by the average: a healthy feed keeps that figure at 1 percent or less.
Read with the motor connected and the starter held in, not on quiet leads: a pitted pole or a loose lug shows full voltage when no current flows, then collapses when the motor's inrush — roughly six to eight times nameplate current on a standard NEMA Design B machine — hits the weak point. ANSI/NEMA MG 1, the 2016 edition with its 2018 revision, defines percent voltage imbalance as 100 times the largest deviation from the average of the three phase-to-phase readings, divided by that average, recommends keeping it at or below 1 percent, and lets a motor run successfully on a supply within 10 percent of rated voltage.
Worked example: a 460 V motor commanded to start, meter at its terminal box, reads 465 V between L1 and L2, 462 V between L2 and L3 and 468 V between L1 and L3. The average is (465 + 462 + 468) / 3 = 465 V. The largest deviation is 3 V. The imbalance is 100 × 3 / 465 = 0.65 percent, inside the recommendation — the feed passes.
Decision: three balanced readings held through the command prove the supply as far as the terminal box, so the question moves to the windings. A reading that sags or tips out of balance only when current flows points to a connection or pole upstream, and the pole test later in this article finds it. If a voltage monitor raised the alarm rather than your meter, setting voltage imbalance limits on a 480 V phase monitor covers the settings that matter.
How do I test the motor windings for continuity and balanced resistance? #
De-energize, lock out and verify absence of voltage, disconnect the motor leads, then measure resistance between every pair of leads: all three readings should match within about 5 percent of each other, and any pair that reads open is a failed winding.
Isolate before the meter comes out: disconnect every lead from the circuit so contactors, cable and neighboring components cannot mask a reading, and clean the lugs first, because a dirty connection reads exactly like a failing winding. Measure with the same instrument at the same temperature — copper changes resistance roughly 0.4 percent per degree Celsius, so a hot figure and a cold one do not mix.
Worked example: the same 460 V, 2 hp motor, three leads, wye-connected inside. T1 to T2 reads 18.6 Ω, T2 to T3 reads 18.4 Ω, T1 to T3 reads 18.5 Ω. The spread is 0.2 Ω, about 1.1 percent, so the balance check passes; a wye motor shows two windings in series between any pair of lines, so one winding is 18.5 / 2 = 9.25 Ω. On a delta motor the line-to-line figure is two-thirds of the winding value, so multiply the reading by 1.5 instead.
Decision: an open pair fails outright, and a spread beyond about 5 percent fails the balance check — treat that figure as a working service benchmark and confirm it against the manufacturer's per-winding numbers before condemning copper, because a broken lead or a bad lug produces the same open and costs a splice, not a motor.
What should a megger read on a 460 V motor before you scrap it? #
IEEE Std 43-2000 sets the bar at rated kilovolts plus 1 megohm at 40 °C, so a 460 V winding must read at least 1.46 MΩ, tested at 500 V DC because the winding is rated below 1000 V.
IEEE Std 43-2000, the recommended practice for testing insulation resistance of rotating machinery, supplies both numbers. It sets 500 V DC as the test voltage for a winding rated below 1000 V and the minimum reading at rated voltage in kilovolts plus 1 megohm, taken at 40 °C, for most windings built after about 1970. Expect the reading to fall roughly by half for every 10 °C the winding is warmer, so test at a known temperature and compare like with like. Test at the motor terminals rather than from the switchgear, so the cable's leakage does not count against the winding — insulation resistance testing from switchgear vs motor terminals covers that trade-off. Disconnect anything electronic from the winding before the test, and discharge the winding to frame afterward before touching the leads.
Worked example: the same motor. Its rated voltage is 0.46 kV, so the floor is 0.46 + 1 = 1.46 MΩ. With the three leads tied together, an insulation tester at the standard's DC voltage reads 85 MΩ to the frame — pass, with more than fifty times the floor. A dry motor that reads 1.2 MΩ fails: the needle moved, but the value sits under the floor.
Decision: above the floor, ground insulation is not the reason the machine will not run, and the verdict moves on. Below it, do not energize — dry a damp winding with warm air, retest, and replace the motor if the reading does not recover.
Why does the reversing relay click but the motor still not run? #
A click proves the coil moved the armature, nothing about the power poles: measure across each pole with the starter energized — a made pole shows almost no volts, and line voltage across any pole means that pole is open and the motor is single-phasing.
To run the pole test, put one probe on the line side and one on the load side of the same pole with the starter held in: a pole that is making drops a fraction of a volt, and a pole with the full branch voltage across it is open, which single-phases the motor. Reversing contactors swap two phases to change direction, so one bad pole in the commanded direction starves the machine as completely as a dead winding. Work down the rest of the path too: a mechanical interlock stuck between the forward and reverse contactors can hold an armature at half travel with the coil energized; a phase-sequence relay in the control circuit blocks the run on its own when the sequence is wrong — why a phase sequence relay blocks a motor reverse start covers that case; and a spring-applied brake that is not releasing locks the shaft and mimics a seized motor, so hand-turn with the brake released only as the documentation allows.
Decision: line voltage across any pole is the fault, found, and it lives in the starter rather than the motor. Near-zero across every pole with the command held proves the current path, and the verdict returns to the windings.
Should I reset the overload relay and start the motor again? #
One reset after you have found and fixed the cause, never a repeated one: if the overload trips again with balanced terminal voltage and a shaft that turns freely, measure the running current against the nameplate full-load current before you touch the dial.
Reset once, then clamp all three lines during the next commanded start and read the current against the nameplate full-load current. Four patterns decide the case:
- Trips well under a second with balanced resistances and a passed insulation test: suspect a lead-to-lead short in the terminal box — a dropped strand or pinched insulation — or the wrong connection arrangement for the supply; check the diagram before anything else.
- Hums through its trip class and then trips on unbalanced current: a phase is missing or weak upstream, and the pole test from the reversing section finds it.
- Trips on balanced current above nameplate full-load current: the machine is overloaded, and with the driven mechanism already uncoupled that means the brake, the bearings or a dragging rotor — spin it by hand.
- Runs balanced at nameplate current and still trips: the setting is wrong, not the motor, and setting overload relays from motor nameplate full-load current walks the dial.
The dial's job is protecting the winding, so leave it at nameplate and fix whatever the trip is reporting.
Decision: the trip is a symptom with four distinct causes, and the clamp reading rather than another reset picks between them.
When is the verdict a dead motor instead of a circuit fault? #
Nameplate voltage held balanced at the terminals through the start command, three equal resistance readings, an insulation reading above the IEEE 43 floor and a shaft that turns by hand all point upstream; an open winding, an unbalanced resistance set or a failed megger points at the motor.
Read the results together, and each case closes with a call:
- Every test passes and the shaft is free: the motor is sound — fix the pole, the interlock, the sequence relay or the brake you found upstream, and run it.
- Voltage collapses or tips out of balance only when current flows: circuit fault, upstream of the terminal box.
- Any winding open, or a resistance spread beyond the benchmark: motor fault — replace or rewind.
- Insulation under the floor: insulation fault — dry and retest if moisture is plausible, otherwise replace, and keep the motor disconnected in between.
- Hums on two live phases: single-phasing, a circuit fault upstream, however dead the motor sounds.
- Every electrical check passes and the shaft still will not turn with the brake released: bearings or rotor drag — replace the motor.
Both halves must agree before you order copper: healthy windings without proven terminal voltage acquit a guilty contactor, and proven voltage with a failed winding acquits a perfectly good starter. When two tests disagree, a lead, a lug or a missing diagram is still in the way — resolve that, then close the case.
Questions asked
The motor has six or more leads and no diagram. How do I find the windings?
With the motor isolated, use an ohmmeter to pair the leads: the pairs that show continuity are the two ends of one winding. Tag each pair before you move anything, then measure the resistance of each pair for the balance check. The series or parallel arrangement, and which leads jumper together for your supply voltage, must come from the manufacturer's connection diagram or its support channel, because guessing the arrangement can put full voltage across half a winding.
The motor hums but will not turn. Is it a dead motor?
Usually not. A three-phase motor fed with only two live phases has no starting torque: it sits and hums while the healthy windings heat fast, and the overload should trip within its class time. That pattern points upstream to a missing phase - a bad contactor pole, a failed fuse in one leg or a loose lug - not to the windings. Verify which phase is missing at the terminal box with the starter commanded, then fix the connection.
The megger reading is fine. Doesn't that clear the windings?
No. An insulation resistance test measures leakage from copper to frame only: it says nothing about an open circuit in one winding, a shorted turn inside the slot or a high-resistance joint at a lug. A motor can pass the megger test and still refuse to run or trip the overload. That is why the continuity and resistance-balance readings carry half the verdict, and why a suspected turn fault goes to a repair shop for a surge comparison test before you order a replacement.
How long do I hold the megger test before reading it?
Hold the test voltage for 60 seconds and take the reading at that point; IEEE Std 43-2000 treats the one-minute value as the spot reading you compare with the minimum. If the reading keeps climbing past 60 seconds, the winding is drying as you test, which usually means dirt or moisture rather than cracked insulation; a reading that sags points the other way. Discharge the winding to frame after the test before you touch the leads.