Explainer
Ungrounded double wye capacitor bank unbalance protection
Short answer
On an ungrounded double-wye bank, use neutral unbalance sensing between the two isolated wye points to detect internal fuse operation, and a neutral-displacement voltage relay to detect system ground faults. A phase or residual overcurrent element will not detect either reliably, because ground-fault current on an ungrounded delta is limited by system charging capacitance.

On this page
An ungrounded double-wye capacitor bank needs two separate detection schemes, and neither of them is a phase overcurrent relay. Internal fuse operation (an unbalance inside the bank) is detected by measuring the voltage or current between the two isolated wye points. A system ground fault is detected by neutral-displacement voltage, because on an ungrounded delta the available ground-fault current is only the system charging current, far too small to pick up any conventional phase or residual overcurrent element. This article uses a real bank as the worked example: 1,200 kVAR total, six internally fused single-phase 200 kVAR units rated 1,386 V, two units per phase, connected to an ungrounded 2,400 V delta system through a 400 A vacuum contactor, switched rarely rather than cycled daily.
Why the two jobs must stay separate #
A blown internal fuse and a cable ground fault both look like "something is wrong with the bank" at the contactor, but they need different detectors:
- Internal unbalance. A fuse clears one series group or one unit. The three phase currents of one wye section are no longer equal, so a small current flows between the two wye neutrals. This is a differential measurement inside the bank and says nothing about the rest of the system.
- System ground fault. On an ungrounded delta, a fault on one phase returns through the capacitance of the other two phases to ground. The current magnitude depends on the connected cable length and equipment capacitance, not on the fault itself, and it is usually a few amps. No 50/51 or residual 50N/51N element set above load current can dependably see it.
The practical consequence: if you fit only phase overcurrent and unbalance relaying, you will catch a failed capacitor unit, but a genuine ground fault on the feeder or in the bank can persist undetected while the unfaulted phases sit at line-to-line voltage. Ground-fault detection on this system belongs at the bus level, watching voltage, not at the bank watching current.
The worked example: 1,200 kVAR, six 200 kVAR units at 2,400 V #
Inputs. Bank rating 1,200 kVAR three-phase (nameplate of the bank); system voltage 2,400 V line-to-line, ungrounded delta (stated system); six single-phase units, 200 kVAR each, rated 1,386 V, internally fused (unit nameplates); two units per phase, one per wye section per phase; vacuum contactor rated 400 A.
Rule. Three-phase kVAR equals the square root of three times line voltage in kV times line current in amperes, so line current equals kVAR divided by 1.732 times kV. A single-phase unit's current equals its kVAR divided by its voltage rating in kV.
Arithmetic.
- Total bank line current: 1,200 kVAR divided by (1.732 x 2.4 kV) = 1,200 / 4.157 = 288.7 A.
- Current per 600 kVAR wye section: 600 / (1.732 x 2.4) = 144.3 A.
- Current per unit: 200 kVAR / 1.386 kV = 144.3 A, which confirms the two figures agree, since each unit carries its section's full phase current.
- Unit terminal voltage: 2,400 V / 1.732 = 1,385.6 V, matching the 1,386 V unit rating.
Result and decision. The bank draws 288.7 A continuous, well inside the 400 A contactor rating, and each unit operates at its rated voltage, so the bank is correctly applied for continuous duty on this bus. Set the bank backup overcurrent above 288.7 A with coordination to the contactor fuse curve, and expect roughly 144.3 A of steady current through each wye point's sensing path when the bank is healthy.
Unbalance detection between the two wye points #
IEEE C37.99, the IEEE guide for shunt capacitor bank protection (2012 edition), describes neutral unbalance protection for ungrounded double-wye banks: the bank is split into two equal wye sections whose neutrals are not connected to ground, and the relay measures either the current flowing between the two neutral points or the voltage appearing across them. On a healthy bank this spill is near zero, apart from third-harmonic current and manufacturing tolerance; when a fuse operates in one section, the section impedances differ and a measurable unbalance appears.
Practical points that decide whether the scheme works:
- Keep the two neutrals isolated from each other and from ground. Do not bond them into a common point; the measurement depends on the difference. Routing the neutral sensing leads away from phase conductors and shielding them reduces false pickups from switching transients.
- Get the unbalance magnitude from the manufacturer, not from a generic setting. The capacitor supplier calculates, for this exact series-parallel arrangement, what neutral voltage results from one failed element, and what overvoltage that puts on the healthy units. Set the alarm below the level that would sustain overvoltage on healthy units and above the measured healthy-bank unbalance, then confirm with IEEE C37.99's guidance on alarm and trip stages.
- Add time delay. Several seconds of delay rides through inrush and nearby switching; unbalance from a blown fuse is steady and will still be there after the delay.
- Verify in service. With the bank de-energized, locked out and verified dead, confirm the neutral circuit topology; then with the bank energized and all units healthy, record the actual spill current or neutral voltage and set the alarm above that measurement.
A plain voltage relay or a modern multifunction relay's unbalance element both work; the induction-disk voltage relays common in older switchgear can serve for the neutral-displacement function, but an electromagnetic unbalance relay will not give you the alarm-versus-trip staging the guide expects, so budget for at least a two-stage static relay on the unbalance measurement.
Ground faults: detect with voltage, at the bus #
On this ungrounded delta, a ground fault anywhere displaces the system neutral: the faulted phase collapses toward ground potential and the healthy phases rise toward line-to-line voltage. A neutral-displacement relay (device 59N in IEEE C37.2 device numbering) connected to the secondary of a wye-open voltage transformer set on the bus, or to a voltage transformer connected between the artificial neutral of a three-phase wye set and ground, sees this displacement as tens of percent of normal voltage, easily detected.
What this tells you and what it does not:
- It tells you a ground fault exists somewhere on the delta system, and roughly on which phase.
- It does not tell you whether the fault is in the capacitor bank or on a feeder. Coordinate by tripping feeders first, or by checking which feeder's protection responds when the bank contactor is opened.
- The fault current is small, so the fault does not clear itself; leave the displacement relay enabled continuously, not only when the bank is in service, because the fault can exist with the bank switched out.
Do not try to make the bank's neutral connection do double duty as a ground detector. Interconnecting the two wye points to form a quasi-differential ground scheme has been tried and is explicitly identified as troublesome: it destroys the unbalance measurement and still leaves ground-fault current too small to operate overcurrent elements reliably.
Other protections this bank still needs #
- Phase overcurrent. Backup to the internal unit fuses and the contactor fuses, set above 288.7 A for this bank, coordinated with the fuse curve so the contactor fuses clear a heavy fault the contactor cannot interrupt.
- Bank overvoltage. Capacitor units tolerate about 110 percent of rated voltage continuously per IEEE 18; a bank voltage relay with a short-time trip above that protects against sustained system overvoltage, which matters more on a bank that runs continuously.
- Switching discipline. Because the bank runs continuously, do not leave the full 1,200 kVAR connected when the medium-voltage bus is lightly loaded; overcompensation raises voltage and can interact with harmonic sources. Harmonic amplification between capacitor banks and drive loads on a shared bus is covered in detail in our article on why VFD harmonics and capacitor banks resonate on the same bus, and fuse blowing from that interaction in why a VFD and a capacitor bank blow fuses on a shared bus.
- Wye vs delta topology. The choice between grounded and ungrounded bank construction and how each shapes the protection scheme is set out in wye vs delta medium voltage capacitor bank protection.
Before any work inside the bank enclosure or the neutral circuit, de-energize the bank, open and lock out the disconnect, wait for the units to discharge through their discharge resistors and verify absence of voltage at each phase and at the neutral points; capacitor units can hold a lethal charge after the feeder is opened.
The decisions for this bank #
- Unbalance: two isolated wye neutrals, each to a sensing input of a two-stage unbalance relay; alarm stage above measured healthy-bank unbalance, trip stage at the manufacturer's one-element-failure unbalance level, several seconds of delay.
- Ground fault: neutral-displacement voltage relay on the bus, enabled continuously; no reliance on phase or residual overcurrent for ground faults.
- Overcurrent: phase backup set above the bank's 288.7 A continuous current, coordinated with the 400 A contactor's fuses; overvoltage relay at the IEEE 18 continuous limit.
- Topology check first: confirm the two wye points are truly isolated before buying CTs or reusing old relays, and measure healthy-bank spill current before finalizing any setting.
Questions asked
What current does a 1,200 kVAR bank draw at 2,400 V?
For a three-phase bank, line current equals the three-phase kVAR divided by the square root of three times the line voltage in kV. That is 1,200 divided by 1.732 times 2.4, which is about 288.7 A. Each 600 kVAR wye section carries half of that, about 144.3 A, which is also the current through each 200 kVAR unit at its 1,386 V rating. Use the nameplate kVAR and voltage of your own bank; a bank rated at a different voltage draws proportionally different current.
Why won't a 50/51 relay detect a ground fault on an ungrounded delta system?
On an ungrounded delta, the only path for ground-fault current is the distributed line-to-ground capacitance of the connected system: cables, surge capacitors and the healthy phases of the bank itself. That charging current is typically a few amps to tens of amps, far below the pickup of any phase or residual overcurrent element set above load current. Ground faults on such a system are detected by voltage, not current: a neutral-displacement relay watching the bus or the delta's artificial neutral.
What pickup should the unbalance relay use?
There is no generic pickup. Start from the manufacturer's data for one failed element: it states the resulting neutral unbalance voltage or current for this exact series-parallel arrangement. Set the alarm above measured healthy-bank unbalance (typically well under 1 V of neutral displacement on a healthy bank) and below the level that leaves sustained overvoltage on healthy units, with a time delay of several seconds to ride through switching transients. Then confirm against IEEE C37.99 and your capacitor supplier's application sheet.
Can the two wye points be interconnected and run as a differential scheme?
No. Interconnecting the two neutrals of a double-wye bank turns the pair into one effective wye for unbalance purposes and destroys the spill-current measurement, while any circulating third-harmonic and switching-transient current between the points causes nuisance pickups. Keep the two wye points electrically separate, each connected to its own sensing input, and measure the difference between them. That is the standard arrangement for ungrounded double-wye banks.