What a machine kVA nameplate means for VFD sizing
Short answer
A machine kVA plate is apparent power, not horsepower: divide kVA × 1000 by (1.732 × line-to-line volts) — 4 kVA at 220 V three-phase is 10.5 A per line, 11.5 A at 200 V. Check what the plate covers, size the drive from the spindle motor's own full-load current, and on single-phase input size the drive at about twice the three-phase rating where its manual allows and documents the derating.
On this page
A machine nameplate in kVA converts to line current, not horsepower. Divide kVA × 1000 by (1.732 × line-to-line volts): a 4 kVA plate at the 220 V end of its range draws 10.5 A per line, 11.5 A at the 200 V end. That number sizes the supply, not the drive. The drive is picked from the spindle motor's own full-load current, and the first job is establishing what the plate covers, because a tag on the control cabinet describes the cabinet only. On a single-phase supply, a three-phase drive runs the spindle only where its manual allows single-phase input, sized at about twice the three-phase rating.
What a machine kVA plate states #
kVA is apparent power: volts × amperes × 1.732 on a three-phase circuit. The plate figure is the maximum simultaneous demand of every circuit it covers — spindle, servo amplifiers, coolant pump, hydraulics, control panel, lights and heaters together. It is not a motor rating, and it never was horsepower.
Coverage is where readings go wrong. The plate at the main disconnect describes the whole machine; a tag bolted inside the control cabinet describes the cabinet alone, and used machines often carry both. A 4 kVA cabinet tag under a 15 kVA machine total is exactly the pattern that trips people up, so identify which assembly each plate belongs to before converting anything. European plates mark this rating with their own conventions — a guide to electrical cabinet kVA rating plates and transformer sizing walks through what the marking covers.
The plate also says nothing about the spindle by itself. A VFD is sized to the motor it feeds, and the spindle's own plate carries that motor's rating.
Converting kVA to line current #
For a three-phase load: line amperes = kVA × 1000 ÷ (1.732 × line-to-line volts). For a single-phase load of the same kVA, drop the 1.732: amperes = kVA × 1000 ÷ volts. At equal power a single-phase feed therefore carries 1.732 times the current of a three-phase feed — the same factor that returns in the single-phase derating step.
Convert at the lowest voltage on the plate, because the same kVA at lower voltage means more current. Treat the result as an estimate of demand and check it against the machine's electrical drawings and the drive manual before anything is bought or wired.
Worked example: converting a 4 kVA, 200–220 V three-phase machine plate #
Inputs, each with its source:
- Plate rating: 4 kVA, three-phase, 200–220 V — the tag on a small used machining center, the one routinely misread as 10.5 hp.
- Candidate drive: 3 hp, 9.6 A — the pairing a drive manual's rating table shows against a 4 kVA-class machine.
- Reported spindle: 7 hp at the shaft, from a machine listing that puts the machine total near 15 kVA.
- Assumed power factor: 0.8, a typical motor value used only for the horsepower cross-check; the current conversion needs no power factor.
The rules: three-phase line current = kVA × 1000 ÷ (1.732 × volts); single-phase current = kVA × 1000 ÷ volts.
The arithmetic:
- 1.732 × 220 V = 381.0 V. 4 kVA is 4000 VA, and 4000 VA ÷ 381.0 V = 10.5 A per line at the plate's high end.
- Worst case at the plate's low end: 1.732 × 200 V = 346.4 V, and 4000 VA ÷ 346.4 V = 11.5 A per line.
- Single-phase equivalent: 4000 VA ÷ 220 V = 18.2 A.
- The trap: 18.2 A ÷ 1.732 = 10.5 — a current, not a horsepower. The horsepower the tag could feed as one motor is 4 kVA × 0.8 = 3.2 kW, and 3.2 kW ÷ 0.746 kW per hp = 4.3 hp at most.
- The candidate drive: 10.5 A − 9.6 A = 0.9 A, and 0.9 A ÷ 10.5 A = 8.6%, so the drive sits about 9% short of the plate current before any derating.
- The coverage check: 7 hp × 0.746 kW per hp = 5.22 kW, and 5222 W exceeds 4000 VA even at unity power factor and 100% efficiency, so a 4 kVA tag cannot cover a machine carrying that spindle. On single-phase input the spindle alone would need at least 5222 W ÷ 220 V = 23.7 A before losses and power factor.
Result: 10.5 A per line at the high-end voltage, 11.5 A at 200 V, 18.2 A if the same kVA arrived on one pair of lines.
Decision: the tag sizes a 10.5–11.5 A three-phase supply and nothing more. The 3 hp, 9.6 A drive is out — short of the plate current even on three-phase input, and single-phase input raises the current the input stage must carry. If the 15 kVA machine total is the right figure, the supply requirement is 15,000 VA ÷ 381.0 V = 39.4 A per line at 220 V (43.3 A at 200 V), and the drive is chosen from the spindle motor's plate, never from the cabinet tag.
From plate to drive size #
- De-energize the machine, lock out and tag the disconnect, and verify absence of voltage before opening any panel to read plates or trace wiring.
- Find every plate — the main disconnect and any cabinet tags — and record kVA, voltage range, phase and full-load amps for each, noting which assembly it covers.
- Convert each kVA to line current at the plate's lowest voltage with the formula above.
- Read the spindle motor's own plate: output in kW or hp, rated voltage, full-load current. Choose the drive whose rated output current meets or exceeds that current. Drive makers tabulate output ratings against the motor full-load currents in NEC Table 430.250 (NFPA 70, National Electrical Code, 2023 edition; Article 430 covers motor circuits) — confirm branch conductors and breaker with your local authority having jurisdiction and the drive manual. The same nameplate current sets the overload: setting overload relays from motor nameplate full-load current covers that step.
- Establish whether the spindle circuit is separable from the machine's single-phase control power. If it is, feed the spindle motor only and rewire the start/stop circuit through the drive's control terminals — wiring start and stop pushbuttons when a VFD replaces a DOL starter shows the pattern.
- If the drive input is single-phase, first confirm the model is rated for single-phase input at all, then apply that manual's derating; the working rule is about twice the three-phase rating, and sizing a VFD for a three-phase motor on single-phase input works the same numbers end to end.
- Compare the required line current against the branch breaker and available service — machine total if the machine stays intact, spindle-only if you split it — then run the spindle through its full speed range with the axes moving and coolant on, because the plate assumes everything energized at once.
Single-phase input and the derating rule #
All the power arrives on one pair of lines, so the input current for a given output is 1.732 times the three-phase figure. A single-phase rectifier also replenishes the DC bus in two pulses per cycle instead of six, so the bus capacitors and input diodes carry more ripple current and run hotter. Manufacturers handle this by derating: one drive guide allows single-phase supply at 50% output derating and calls for an input line reactor in that service — choosing a line reactor or motor reactor for a VFD covers that component.
Fifty percent is where the size-double rule comes from: a 4 hp-class spindle gets a 7.5 hp-class frame. Two limits hold. The derating figure belongs to the manual in your hand — one maker's 50% does not transfer to another's rating table. And some models list three-phase input only; no single-phase entry in the rating table means the model is out, and the restriction appears more often as the frame grows.
When the whole machine needs three phase #
Most machines take one three-phase feed at the disconnect and transform and distribute it internally. Two paths follow. Split the spindle circuit out of the machine wiring and feed it from a VFD — real work, but the reliable path on single-phase power, with the controls left on their own single-phase supply. Or leave the machine intact, keep its spindle amplifier, and feed the whole nameplate from a rotating converter, sized by converter practice at roughly two to three times the motor horsepower and checked against the machine total in amps from the worked example above. Powering a 600 V three-phase machine from 240 V single phase works the whole-machine supply math.
Either way, no VFD feeds the controls. Servo amplifiers, the CNC and the panel expect fixed voltage and frequency; the drive output belongs on the spindle motor circuit alone.
Confirming the sizing before the machine runs #
Three checks, each against a limit already on paper:
- Input current: true-RMS clamp ammeter on each input leg during spindle acceleration, against the drive's rated input current and the branch breaker rating.
- Supply voltage: meter at the machine disconnect during a start, against the plate window — the worked plate's 200–220 V. Sag beyond the window returns later as bus undervoltage trips.
- Phase balance on a converter feed: phase-to-phase voltage across all three legs under load, against the tolerance in the machine manual.
If the drive trips anyway, read its fault history first and match the logged code against the fault table for that drive model. An overcurrent trip during acceleration points to an undersized drive or a skipped single-phase derating; a bus undervoltage trip points to supply sag or an undersized converter.
Questions asked
Is a drive's input current rating the same as its output current rating?
No, and the manual lists them on separate lines. Match the output rating to the motor's nameplate full-load current. Match the input rating to your supply, breaker and input conductors. On single-phase input the input current for the same output is higher than either three-phase figure, so the branch circuit is checked against the single-phase input line, not the output.
What happens when a drive is too small for single-phase input?
Expect nuisance overcurrent trips during acceleration and DC-bus undervoltage trips from the deeper ripple, plus shortened capacitor and input-rectifier life from the extra ripple current. An overload trip on a start the motor should easily handle usually means the drive is undersized for the feed or the manual's single-phase derating was never applied.
Can one VFD run the whole machine, including servos and controls?
No. A VFD produces variable-frequency power for one motor circuit. Servo amplifiers, the CNC and the control circuits need fixed voltage and frequency, and feeding them from a drive output damages or stalls them. The drive belongs on the spindle motor circuit alone; pumps, fans and controls stay on the fixed supply through the machine's control transformer.
Where do I find my drive's single-phase derating figure?
In the drive's installation manual, in the input rating section: look for a single-phase note under the three-phase rating table or a separate single-phase column. Manuals handle it differently — some document a derating figure such as 50% of the three-phase output, some allow single phase only at reduced voltage, and some prohibit it. No single-phase entry means the model is not rated for that feed.
Does a rotary phase converter need the same derating as a VFD?
Not the same way. Converter practice sizes the unit at roughly two to three times the largest motor it starts, because the manufactured third leg sags hardest at starting current, not because of a ripple derate. The check is voltage balance: measure phase-to-phase across all three legs under load and hold it inside the tolerance in the machine manual.