What a multimeter shows about three-phase motor winding resistance
Short answer
With the motor locked out and the star or delta links removed, measure U1-U2, V1-V2 and W1-W2. Three near-equal readings, continuity on every winding and no continuity between windings or to the frame pass the test. There is no fixed pass value in ohms: the correct resistance scales with the motor's size, so the comparison between the three readings decides.

On this page
A multimeter answers the three-phase motor question with three comparisons: every winding conducts, the three resistances match each other, and nothing conducts from a winding to the frame or to another winding. There is no fixed resistance value a winding must show — the correct figure falls as the motor's power rises — so the decision comes from equality between the three readings, never from one number on the meter. With the motor locked out, the supply leads off the terminals and the star or delta links removed, measure U1-U2, V1-V2 and W1-W2. Three readings that match within the meter's repeatability, continuity on every winding, and no continuity between windings or to the frame pass this test. One winding that stands apart, any cross-winding continuity, or any path to the frame fails it, and each failure has its own decision below.
What the meter proves and what it does not #
The meter finds four conditions: an open winding, a winding whose resistance stands apart from its siblings, continuity between windings that should be isolated, and a conducting path to the frame. It cannot grade insulation. Its ohms range tops out in the tens of megohms and it tests at a few volts from its internal battery, while an insulation resistance test applies 500 V DC or more from a purpose-built megohmmeter and reads millions of ohms. The split between what the two instruments can prove is set out in a comparison of megger and multimeter insulation testing, and the insulation test's connections on a machine are covered in insulation resistance testing from the switchgear vs the motor terminals.
| Measurement with the links removed | Healthy result | What a failure indicates |
|---|---|---|
| U1-U2, V1-V2, W1-W2 continuity | a low ohm reading on each pair | open winding or broken lead |
| The three winding resistances | near-equal readings | the winding that stands apart is the suspect |
| Winding to winding: U1-V1, U1-W1, V1-W1 | open, no continuity | inter-winding fault, usually burnt insulation |
| Each winding end to the frame | open on the highest ohm range | ground fault, do not reconnect power |
Lock out, then open the terminal box #
De-energize, lock out and tag the supply, then prove absence of voltage at the motor terminals with a tester proven on a known live source immediately before and after the check. NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers this practice; your site's energy-control procedure and the authority having jurisdiction set the details you must follow. If a drive feeds the motor, give the drive's DC bus the discharge time its manual publishes before working near it.
Then take the supply leads off the motor terminals. With the feeder, the contactor poles and the cable still in circuit, the meter reads them in parallel with the winding and sums what it cannot separate, so read the motor alone.
Remove the star or delta links #
With the links fitted, U1-V1 reads a network rather than a winding: on a star connection, two windings in series; on a delta, one winding in parallel with the other two. Neither result compares with anything. Photograph or sketch the link arrangement first so the motor goes back exactly as it came, then remove the links and hang every lead end clear of the frame and of each other — a dangling lead resting on the casting reads as a ground fault that does not exist.
The test sequence #
- Confirm the lockout and the absence of voltage, and take the supply leads off the motor terminals.
- Photograph and remove the star or delta links, and keep the lead ends off the frame and off each other.
- Select continuity mode and test U1-U2, V1-V2 and W1-W2. Each winding must show continuity; a pair that reads open is a broken winding or a broken lead.
- Switch to ohms and touch the probes together to read the leads' own resistance, often a few tenths of an ohm, because on small windings it rivals the winding itself.
- Measure and record U1-U2, V1-V2 and W1-W2 on one range, with the same firm probe pressure on clean, bright copper.
- With the windings now electrically separate, test U1-V1, U1-W1 and V1-W1. All three must read open.
- Test each winding end against a bare, unpainted spot on the frame on the highest ohm range. All must read open.
- Compare the three winding resistances against each other, leads zeroed, using the calculation below.
Worked example: one winding stands apart #
Take an illustrative 15 kW, 400 V, four-pole motor: links removed, leads zeroed, measured cold directly on the winding ends. The meter reads 1.12 Ω on U1-U2, 1.15 Ω on V1-V2 and 1.38 Ω on W1-W2.
The average is (1.12 Ω + 1.15 Ω + 1.38 Ω) / 3 = 1.22 Ω. The W winding deviates by 1.38 Ω - 1.22 Ω = 0.16 Ω from that average, and 0.16 Ω / 1.22 Ω × 100 ≈ 13 percent. The U and V readings differ by 0.03 Ω, about 2.5 percent of the average — the scatter a hand-held meter produces from contact and lead effects on a reading this small. The W winding sits far outside that scatter.
Because 0.16 Ω is within reach of a bad lug or a corroded terminal, re-measure directly on the winding ends with the lugs out of the path. If the spread survives clean, direct contact, the W winding carries an internal fault, most likely a high-resistance joint or a partially open conductor, and the motor goes to rewind or replacement. A winding reading well below its siblings points the other way, toward shorted turns, and gets the same decision. The percentage ranks the readings against each other; it is not a pass mark from any standard, and where the manufacturer's datasheet gives a per-winding resistance or a limit, that datasheet governs.
Why there is no fixed pass value #
A winding's resistance is set by its turns, the length of wire per turn and the wire's cross-section — turns times resistivity over conductor area. A larger motor carries more current through fewer turns of thicker wire, so its ohms fall as its kilowatts rise: a small motor can legitimately read several ohms per winding while a large one reads a fraction of an ohm, and the same frame in a different speed or voltage winding reads differently again. That is why the 0.5 Ω figure sometimes quoted as a winding pass value has no standing in any motor standard: the 1.1 to 1.4 Ω windings in the example above are healthy, a 90 kW motor reads a fraction of that, and no single number separates good from bad across sizes.
Temperature moves every winding the same way — copper's resistance rises about 0.4 percent per degree Celsius — so compare the three cold, or at least at the same temperature. Below roughly an ohm, where leads and contacts rival the winding, a four-wire micro-ohmmeter is the tool for a definitive number; the meter comparison still catches the opens, the gross mismatches and the fault paths.
The unbalance figures you may have met belong to a different test: ANSI/NEMA MG 1-2016 recommends keeping the supply voltage unbalance at a running motor's terminals within 1 percent and derating the motor beyond that, which says nothing about a cold winding comparison.
The frame check: what it can and cannot clear #
A winding end that reads ohms, or beeps, to the frame is a ground fault: do not re-energize, and move to insulation testing to locate and grade the fault. What this check cannot do is clear the insulation. A winding can look open on the meter's low-voltage ohms range and still break down at 500 V DC or at line voltage, and it can pass a megger test and still trip the breaker on start from a fault between turns — the pattern worked through in why a motor meggers good but trips the breaker on start. The low-ohm-to-frame symptom itself is worked through for a real machine in reading motor lead-to-ground ohms on a 480 V compressor. The resistance comparison and the insulation test catch different faults, and a motor returning to service wants both.
The decision for each result #
- All three windings continuous, the readings matched within a few percent of each other, nothing conducting between windings or to the frame: the motor passes this test. Refit the links as photographed, then verify insulation resistance and the supply before returning it to service — passing here clears opens, shorts and grounds, not the run.
- One winding open on continuity: check that winding's external lugs and lead first; if the winding itself is open, it is rewind or replacement.
- One winding apart from its siblings after clean, direct re-measurement: internal winding fault suspected — confirm with insulation tests and plan rewind or replacement.
- Continuity between two windings: their insulation has burnt through between them — rewind or replacement.
- Any winding-to-frame reading: ground fault — no re-energization until the fault is located and repaired.
- If the motor arrived as a will-not-run complaint, fold these results into the wider test sequence in the tests to run before replacing a three-phase motor that will not run.
Questions asked
Can I test the windings with the star or delta links still fitted?
You can, with arithmetic. On a star connection the meter reads two windings in series, so each winding is roughly half the line-to-line reading. On a delta connection it reads one winding in parallel with the other two in series, so each winding is about one and a half times the reading. The three pairs must still match each other, but a fault can hide in the parallel paths, so removing the links remains the reliable test.
Why do the readings change every time I measure the same winding?
Below about an ohm, the meter's test leads and the probe-to-terminal contact are the same order of magnitude as the winding itself. Re-seat the probes on clean, bright copper, use the same pressure and the same range, and zero the leads before each set. Scatter of a few hundredths of an ohm is normal; a reading that moves by tenths of an ohm points to a contact or lead problem, not the winding.
My motor has nine leads instead of six, which pairs do I measure?
Find the three lead pairs that show continuity to each other; each pair is one winding circuit, and on a dual-voltage winding it is two sections in series. Measure each pair the same way and compare the three results exactly as you would U1-U2, V1-V2 and W1-W2. The pairing and the connection for your supply voltage are on the motor's connection diagram, usually on the nameplate or inside the terminal box cover.