Explainer
What an ext. 100% marking means on a current transformer
Short answer
Ext. 100% on a CT nameplate is a continuous thermal current rating factor of 1.0 under IEEE C57.13: the CT carries its rated primary current continuously at the stated ambient and nothing above it. The short-time and emergency ratings are separate, time-limited values, so the deciding quantity for a load is the permitted continuous primary current at the specified ambient and accuracy class.

On this page
- What does ext. 100% mean on a current transformer?
- Does ext. 100% allow double the rated current continuously?
- How does ambient temperature change what the rating factor allows?
- Is the 20-times short-time rating an overload allowance?
- How do you calculate the continuous and short-time limits for your CT?
- What do you check before accepting a CT for its actual load?
- When do you pick a higher rating factor instead of a larger ratio?
- Questions asked
An ext. It is not an extension to 200% of nameplate. IEEE C57.13, Standard Requirements for Instrument Transformers, 2016 edition, defines the electrical, dimensional and mechanical characteristics and certain safety features of instrument transformers, and the continuous thermal current rating factor is the quantity this marking prints in percent. The short-time rating and any emergency rating are separate, time-limited values. The deciding quantity for a load study is the permitted continuous primary current, rated primary current times the rating factor, at the stated ambient and accuracy class.
What does ext. 100% mean on a current transformer? #
Ext. 100% is a continuous thermal current rating factor of 1.0: the CT may carry its nameplate rated primary current continuously at the ambient the rating is stated for, and it carries no continuous margin above that value. 'Ext.' is the nameplate's short form for the extended rating, and the percent figure is the IEEE C57.13 continuous thermal current rating factor written in percent.
The standard defines that factor as the number by which the rated primary current is multiplied to obtain the maximum continuous current, so the conversion is trivial: one hundred percent divided by one hundred gives a factor of one. One manufacturer prints ext. 100% on the metal nameplate; another prints RF 1.0 on the data sheet for the same capability. Read the marking together with the ambient it is stated at, because the factor is a thermal statement: at that current, no part of the transformer exceeds its normal allowable maximum temperature in continuous service. If a model's data sheet defines its marking differently, that data sheet's stated continuous rating governs.
Does ext. 100% allow double the rated current continuously? #
No: the marking is the rating factor written in percent, so the continuous ceiling sits exactly at rated primary current, and 200% would require a factor of 2.0 that this marking does not give. The doubling misread comes from treating 'ext.' as extend-by, nameplate plus an equal amount on top. The standard's reading is the only one with a definition behind it: the factored current is itself the ceiling, and the rated-current limit applies to it, not beyond it.
Nothing enforces this for you. A CT does not trip when it runs above its continuous rating; winding loss rises with the square of the current, temperature passes its allowable maximum, and the ratio error grows past the accuracy class at the same time. A CT run past its continuous limit reports badly before it fails loudly, so the mistake can live in your meter data for months.
How does ambient temperature change what the rating factor allows? #
Every rating factor is tied to a stated ambient temperature: the factor holds at that reference condition, and manufacturers publish tables that reduce the permitted continuous current as the surrounding air gets hotter. IEEE C57.13 states each factor for a specified ambient, and the matching rating-factor-versus-ambient table or curve on the data sheet carries the adjustment. A hot outdoor site or a sun-loaded cubicle therefore trims the permitted continuous current even when the marking looks generous.
With this marking there is nothing to trim. The factor already sits at unity, so an ambient above the reference condition puts the continuous limit below nameplate, and the manufacturer's table gives the reduced figure to design to. Standard factors reach 4.0 on metering-class designs, with the 0.3 accuracy class the classic case, and those high factors exist so a single CT meters a feeder accurately from light load to seasonal peak.
Is the 20-times short-time rating an overload allowance? #
No: the 20-times figure is the short-time rating, good for 1 second through a fault, and it never raises the continuous ceiling that the rating factor sets for normal load. IEEE C57.13 states the short-time rating on a one-second basis, and its relaying accuracy classification adds what the CT must do during that second: a CT in the C classification delivers 20 times rated current with less than 10 percent ratio error at a standard burden. That is a statement about reproducing fault current for protection, not a thermal allowance for load.
The emergency rating is the third, separate number. Where a manufacturer publishes one, it is the current the CT can carry for a specified period without exceeding its emergency allowable maximum temperature, a stated duration on the data sheet, never continuous service. Three limits, three jobs: continuous for load, emergency for a stated period, short-time for the fault. A value never migrates between columns.
How do you calculate the continuous and short-time limits for your CT? #
Multiply rated primary current by the rating factor for the continuous limit and by 20 for the one-second short-time limit; a 600/5 A unit marked ext. 100% works out to 600 A continuous and 12,000 A for 1 s.
Hypothetical example, with every input stated:
- Feeder: 480 V, three-phase, 60 Hz.
- CT: 600/5 A, ratio 600 ÷ 5 = 120:1, with the data sheet stating the factor at a 30 °C average ambient that the cubicle matches.
- Expected maximum continuous primary current: 650 A, taken from the plant's metering records.
The arithmetic:
- Continuous limit: 600 A × 1.0 = 600 A on the primary; the secondary carries its 5 A.
- Short-time rating: 20 times rated current for 1 s, which is 12,000 A on the primary and 100 A on the secondary, sized for the fault and irrelevant to the load.
- Load check: 650 ÷ 600 ≈ 1.08, so the load sits 8 percent above the ceiling.
- Heating check: winding loss scales with current squared, (650 ÷ 600)² ≈ 1.17, about 17 percent more loss than the continuous design point, held indefinitely.
These are worked estimates from the standard's ratings; the CT's own data sheet and the governing installation code decide the final numbers.
What do you check before accepting a CT for its actual load? #
Compare the maximum continuous primary current you actually expect against the rating-factor current, confirm the ratio and accuracy class suit the metering job, and stop at the manufacturer's documented limit if the two disagree. Take the load figure from the plant's metering history, or from a clamp reading made under the site's electrical safety program: NFPA 70E, 2024 edition, the standard for electrical safety in the workplace, sets the shock and arc-flash risk assessment for work near energized conductors.
Before any panel or terminal box is opened, de-energize the circuit and verify absence of voltage, and confirm the procedure with the site's documentation and the authority having jurisdiction; an energized CT with an open secondary develops a hazardous voltage, so the secondary gets shorted at the approved shorting terminal before anything in that circuit is disconnected.
Then compare that current against the factor-multiplied limit only, never against the emergency or short-time values. Confirm the ratio and accuracy class fit the instrument: metering wants class accuracy at normal load, protection wants the C-class performance through faults, and for transformer jobs the ratio itself gets checked as shown in checking a 600/5 CT ratio for transformer protection. Record the complete nameplate, model, ratio and taps, accuracy class, and the marking exactly as printed, so the data sheet can settle any ambiguity. If the marking and the data sheet conflict, the CT stays out of service until the conflict is resolved in writing.
When do you pick a higher rating factor instead of a larger ratio? #
Pick the higher rating factor when the load outgrows the CT but the ratio must stay for metering accuracy or relay settings; pick the larger ratio when the whole operating range has moved up and the instruments can be retuned. Run the decision on the example. The 650 A load fails on the example unit, and two compliant fixes exist.
Keeping the ratio: the same 600/5 in an ext. 150% version permits 600 A × 1.5 = 900 A continuous, 250 A of margin over the load, with metering class and relay settings untouched. Changing the ratio: an 800/5 with the same marking permits 800 A continuous, also enough, but every meter multiplier and relay setting rescales.
Decision: keep the ratio and order the 150 percent factor when the instruments stay; take the larger ratio only when the load range itself has shifted upward and the retuning is already planned. Leaning on the emergency or short-time rating to cover a continuous load is not a third option: that path overheats the winding and corrupts the readings at the same time.
Questions asked
How do you convert an ext. percentage marking into a rating factor?
Divide the printed percentage by 100. A marking of 150 percent is a factor of 1.5, so a 600 A rated primary would carry 900 A continuously at the stated ambient. The marking style is the manufacturer's choice; the number always multiplies rated primary current to set the continuous ceiling.
Does the marking change the CT's ratio or accuracy class?
No. The ratio and the accuracy class are separate nameplate lines; the marking only caps continuous primary current. Accuracy holds while current stays within the rating-factor value, and past it the ratio error drifts beyond the class limit even before winding temperature becomes the bigger problem. A CT that is healthy electrically can still be the wrong CT thermally.
Why do some metering CTs carry rating factors of 2.0 or higher?
So one CT can cover a feeder accurately from light load to seasonal peak without a ratio change. The factor multiplies rated primary current to set the continuous ceiling at a stated ambient: a 4.0 factor on a 200 A rating permits 800 A continuous, and that is still a ceiling, not an overload allowance.
What should you record before asking the manufacturer about an unclear marking?
The complete model designation, ratio and tap list, accuracy class, the marking exactly as printed, voltage class, frequency, and the highest ambient expected around the cabinet. With that in the request the manufacturer can state the rating factor and its ambient basis in writing, and that statement becomes the documented continuous limit for the file.

