Troubleshooting
Motor protection relay trips at full load with service factor 1.0
Short answer
On the Multilin M60 motor protection relays reported here (model M60-C00-VFH-F8A-H5C-M8A-P6B, firmware version 3.44), a thermal trip two to three seconds after the injected current settles at 100% full-load current — with no trip at 95% or 105% and the motor service factor set to 1.0 — marks the thermal-model boundary calculation. Verify the current scaling, reproduce the full start-to-run injection sequence, then set the service factor to 1.01, which stopped the trip in the reported tests.
On this page
- Which trip element do you read before touching the starter?
- How do you verify the injected current against the CT ratio and the FLA setting?
- What do you de-energize before you inject test current?
- Why does the test need the full start-to-run sequence?
- What do the 95%, 100% and 105% results tell you?
- Why does the service factor setting reach the trip calculation?
- What is the fix, and what do you verify afterwards?
- Questions asked
A thermal trip that lands two to three seconds after the injected current settles at 100% of motor full-load current — with no trip at 95% or 105% — is not a worn contactor or a weak starter coil. On the Multilin M60 relays reported here (model M60-C00-VFH-F8A-H5C-M8A-P6B, firmware version 3.44, protecting a 4160 V motor starter), the trip reproduced on more than one relay and disappeared when the motor service factor setting moved from 1.0 to 1.01. That combination points at the thermal-model boundary calculation, not at the power circuit. Read the trip record, check the current scaling, reproduce the full start-to-run injection sequence, compare the three current points, then apply the service factor change and re-verify — leaving the overload settings themselves untouched.
Which trip element do you read before touching the starter? #
Read the relay's event record and element indications first: note the operated protection element, the per-phase currents the relay measured, and the thermal level at the trip, because a starter opening proves only that the trip chain worked, not which calculation requested it.
An opened starter proves the trip chain operated; the event record names the calculation that asked for it. Capture, before anything is changed:
- the operated element and the indication sequence in the seconds before the trip;
- relay model, firmware version, the active settings file, the configured motor full-load current, the service factor and the CT ratio;
- each phase current read from the relay's own metering, not only from the injection set display;
- the thermal level the relay reported, and whether the model was already hot from an earlier injected start.
If the thermal element operated and the trip follows the transition from starting current to running current, continue with current scaling. If another element operated — a ground, unbalance or start-supervisory function — work that pickup on its own path, the way why a 51N earth fault setting trips without a fault approaches an earth-fault element that trips healthy current. The boundary behavior described below was observed on the named model and firmware; other revisions were not tested, so read your own relay's records rather than assuming it shares the behavior.
How do you verify the injected current against the CT ratio and the FLA setting? #
Calculate the secondary test current from the configured CT ratio and the configured full-load current before you inject, then confirm the relay's own metering reads the same amperes, because a scaling error can turn an intended 100% test into a different point inside the relay.
Full-load current is the reference for the whole test, so the injection set and the relay must agree on what 100% means. Worked example, with illustrative inputs — take yours from the nameplate and the settings file: motor nameplate full-load current 320 A, relay FLA setting 320 A, current transformer 400:5.
- CT ratio: 400 ÷ 5 = 80
- 100% point: 320 A ÷ 80 = 4.0 A secondary
- start point, about five times full-load current: 320 A × 5 = 1,600 A, then 1,600 A ÷ 80 = 20.0 A secondary
- 95% point: 320 A × 0.95 = 304 A, then 304 A ÷ 80 = 3.8 A secondary
- 105% point: 320 A × 1.05 = 336 A, then 336 A ÷ 80 = 4.2 A secondary
The FLA value the thermal model uses comes from the nameplate; setting overload relays from motor nameplate full-load current walks that read-through. If the injection set and the relay disagree by more than the test set's stated accuracy, resolve the connections and the scaling before interpreting any trip, and if the phases differ, fix the injection first — an unintended unbalance feeds the relay's unbalance and thermal functions different numbers. Once the relay reads the intended current and the thermal element alone operates, move to the sequence test.
What do you de-energize before you inject test current? #
De-energize the starter, lock it out and verify absence of voltage before you open the cubicle, then connect the injection set to the relay's CT secondary circuit with the motor and the bus isolated so the test cannot energize anything beyond the relay.
Keep the trip contacts in their approved test arrangement so an operated relay cannot close the starter. Save the active settings before any edit. Record the initial thermal state, and between comparisons restore it by the documented procedure or by waiting out the model's cooling time — record which you did, because every comparison later in this sequence is meaningless unless each run begins at the same thermal level.
Why does the test need the full start-to-run sequence? #
Inject the whole sequence — starter closed, roughly five times full-load current, then a step down to the running value — because the thermal model carries the heating accumulated during the start into the running state, and a cold relay fed steady current is a different test.
- Save the active settings and record the initial thermal state.
- Apply the starter-closed status condition the relay uses to switch from its starting model to its running model.
- Inject about five times the configured full-load current — the reported tests used roughly that multiple — and hold it for the start duration your test plan specifies; the reported work does not state the duration, so it comes from your plan.
- Step the current down to the running value under test without touching any other input or status.
- Capture relay metering, the reported thermal level, the element indications and the time from the step-down to the trip.
- Before the next comparison, restore the same initial thermal state and record how.
Keep that sequence identical for every comparison. If steady-current injection alone also produces the fast trip, record it separately: it describes a different condition and a different decision.
What do the 95%, 100% and 105% results tell you? #
The signature is a fast thermal trip at exactly 100% full-load current with no comparable trip at 95% or 105% under identical settings and start history — a discontinuity at one operating point, not the longer trip times a healthy thermal curve gives as current falls.
| Observed result | What it points to | Next check |
|---|---|---|
| Thermal trip in 2–3 s at the 100% point, service factor 1.0 | Boundary behavior in the thermal calculation | Repeat from the same thermal state, then run the 1.01 comparison |
| No rapid trip at the 95% or the 105% point | A discontinuity at one operating point, not a simple increasing-current response | Confirm relay metering and repeat all three points |
| The same sequence trips a second relay | Shared settings or firmware behavior, not one damaged unit | Compare model, firmware, settings and injection set |
| Service factor 1.01 ends the trip | Sensitivity to the service factor boundary | Send both result sets to the manufacturer before the field change |
A healthy thermal element gives longer trip times as current moves toward pickup, the shape reading overload relay trip classes and curves describes: at the 95% point the model never reaches its boundary, and at 105% it sits just above it, so a genuine trip there takes the time the thermal time constant sets and can outlast your observation window. Note how long each non-tripping run lasted, because "ran forever" means "outlasted the window". The same initial state, the same start sequence, a fast trip at exactly 100% and different results on either side is the repeatability that makes the case; a hot model tripping quickly at running current by itself proves nothing, and a 105% non-trip is an observation result, not permission to run a service-factor-1.0 motor above its permitted load.
Why does the service factor setting reach the trip calculation? #
A thermal-model relay computes heating against an allowable level built from the full-load current and service factor settings, and at service factor 1.0 a current of exactly 100% sits on that boundary, the point where the predicted trip time tends toward unbounded.
These models follow the thermal characteristics described in IEC 60255-149, the standard covering functional requirements for thermal electrical protection relays; the relay manual documents its own implementation, and vendor application literature on motor thermal models treats the service factor as the current the model treats as continuously permissible. At exactly that value the model approaches its boundary asymptotically and never crosses it, so the predicted trip time grows without limit — and that is precisely the point where the reported relays returned a trip in seconds. The mechanism inside the calculation was not published, so treat the fast trip at the boundary as the observed fact and leave the internal arithmetic to the manufacturer. On this relay family the service factor setting spans 1.0 to 1.25, so 1.0 is an accepted entry, and the guidance the manufacturer gave in this case was to avoid it.
What is the fix, and what do you verify afterwards? #
Set the relay service factor to 1.01 for a motor whose nameplate reads 1.0 and leave the full-load current and thermal settings unchanged: the change moved the operating point off the degenerate boundary and restored normal behavior in the reported tests.
For a motor marked with a service factor of 1.15 or higher, none of this applies — enter the nameplate value. The one-percent shift moves the test point off the boundary and is far inside the tolerance a thermal model is set to, so the protection intent stands.
Rerun the three current points and the full start-to-run sequence from the same initial thermal state. Expect no trip at the 100% point within your observation window and unchanged long-time behavior at the neighboring points. If your test plan includes a genuine overload point, confirm it still trips, and still trips at the curve's time.
Leave every other setting alone. Loosening the thermal curve, raising the FLA setting or disabling a stage trades a settings problem for an under-protected motor: NFPA 70, the National Electrical Code, 2023 edition, sizes motor overload protection in 430.32 from full-load current — 125% where the motor is marked with a service factor of at least 1.15 or a temperature rise of 40 °C or less, 115% otherwise — and the relay's thermal model holds that role here. Confirm the edition your authority having jurisdiction adopts and any local amendments with that office and the motor documentation.
Send the manufacturer's technical support the paired results for this model and firmware — settings file, injection sequence, both service factor runs, event records — and ask whether a later revision corrects the boundary behavior before you standardize the changed entry across the fleet. Decision: a fast thermal trip only at the 100% point, reproduced on more than one relay and removed by the service factor change, is the thermal-model boundary — correct the entry, verify by injection, and leave the protection level untouched.
Questions asked
Does a service factor of 1.0 keep a motor from starting a heavy load?
No. Service factor is a continuous-running thermal margin at rated voltage and frequency, not a measure of starting ability. A 1.0 motor produces the starting torque and inrush of its design class and starts normally; what it lacks is permission to run continuously above nameplate current. Start sizing and starting protection are unchanged.
Do all motor protection relays misbehave at a service factor setting of 1.0?
The fast trip described here was reproduced on Multilin M60 relays of one model and firmware and is not a documented property of motor protection relays in general. Other models and revisions were not tested, so verify your own relay with the same injection sequence before assuming either behavior.
Can you enter a service factor below 1.0 to make the thermal model stricter?
On the reported relay the setting spans 1.0 to 1.25, so a stricter entry is not available. Tighter protection comes from the full-load current setting and the thermal time constant within the manufacturer's documented ranges, and from matching the nameplate, not from inventing a margin the motor does not have.
What records should go to the manufacturer with this problem?
Send the relay model and firmware, the settings file, the nameplate full-load current and service factor, the CT ratio, the injection sequence with its start duration, the initial thermal state, and the paired results at the three current points with and without the changed setting. Attach the event records, not only a summary.