What decides ground fault CT sizing on a transformer primary
Short answer
Size the ground fault CT from the current that actually passes through its window, not from the available fault current at the bus. On a resistance-grounded system limited to about 5 A, a 2000:5 CT delivers only 12.5 mA to the relay; a low-ratio CT into a sensitive ground input picks that fault up reliably.

On this page
A ground fault CT on a transformer primary is sized from two numbers: the ground current that will actually pass through its window, and the relay input it feeds. The 2000 A available fault current at the bus does not decide the ratio, because a resistance-grounded system deliberately limits ground current to a few amperes. On a 480 V system with a 55.4 ohm grounding resistor, the limited ground current is about 5 A, and a 2000:5 CT turns that into 12.5 mA at the relay. A CT with a low primary ratio, for example 75:1 or 100:1, feeding a sensitive ground current input, turns the same fault into a signal the relay can measure and trip on. That is the whole decision; the rest of this article shows the arithmetic and the checks around it.
Why the available fault current is the wrong input #
The available fault current at the transformer primary describes a bolted phase-fault condition at that point in the system. A ground fault protection scheme on a resistance-grounded system is designed for a completely different quantity: the small, controlled current that returns through the grounding resistor. High-resistance grounding practice, as laid out in a published low-voltage design guide from a major grounding equipment manufacturer, selects the resistor to limit single line-to-ground current to a set maximum, commonly 5 A or 10 A.
If you pick a CT ratio to suit the 2000 A figure, the CT sees almost no current during the fault it exists to detect. The ratio error specifications that cover relaying accuracy describe performance at 1 to 20 times rated secondary current, per IEEE C37.110-2023, the guide for applying current transformers to relaying. At the milliampere signals a ground fault produces through a high-ratio CT, you are far below the range the class guarantees, and the relay may see nothing at all. The same reasoning applies to any ground fault sensing decision, including the motor and feeder relay settings covered in Motor vs non-motor ground fault relay settings explained.
The current that actually passes through the window #
A CT responds to the net current enclosed by its core. Before choosing any ratio, mark the CT location on the one-line and trace the conductor through it.
- A CT around the transformer grounding conductor carries only the ground fault return current for faults on the transformer winding side it protects.
- A CT on the neutral grounding resistor connection measures the resistor current, a different conductor and a different protection function.
- A zero-sequence or core-balance CT around all three phases measures the vector sum of the phase currents and sees ground current without any grounding conductor in its window.
These are not interchangeable by assumption. The original question is about the CT on the transformer primary ground, not the grounding resistor CT; confirm which conductor your CT surrounds before any ratio arithmetic. Sizing for core-balance sensing follows its own logic, covered in Why a 50:5 zero-sequence CT fits an 800 A motor.
The worked example #
Take a 480 V system resistance-grounded through a 55.4 ohm resistor, typical of the designs that limit ground current to a few amperes:
- Ground fault current: I = V / (sqrt(3) x R) = 480 V / (1.732 x 55.4 ohm) = 480 V / 95.95 ohm = 5.0 A.
Now test two CT choices for the transformer primary ground, with the same 5.0 A fault current through the window:
- A 2000:5 CT: secondary current = 5.0 A x (5 / 2000) = 0.0125 A, or 12.5 mA. Most relay ground inputs cannot pick up reliably on a signal this small, and the ratio error at such a low multiple of rated secondary current is not covered by the accuracy class.
- A 75:1 CT into a sensitive ground input rated 1 A: secondary current = 5.0 A / 75 = 66.7 mA, roughly five times more signal into an input built for small currents. A 100:1 ratio gives 50 mA.
If the CT window instead carries the full grounding resistor current and the relay is a dedicated device expecting that range, a low ratio such as 5:5 or 10:10 is common; the published high-resistance grounding design guide uses a grounding current transformer of that magnitude. The pickup decision then belongs to the relay setting, not the CT ratio.
This calculation only translates current by ratio. It does not replace the burden, saturation and coordination checks that follow.
Ratio and relay input are one decision #
There is no inherently sensitive secondary rating. Sensitivity is a property of the CT-plus-relay combination: primary ratio, connected burden, lead length, and the relay input's minimum usable pickup. A 1 A input is not automatically better than a 5 A input; a 75:1 CT into a 1 A sensitive ground input works because the ratio matches the expected fault current to the input's range.
So read the relay documentation before ordering the CT. Confirm whether the relay has a dedicated sensitive ground input and what its minimum pickup and burden are, then choose the CT ratio so the expected ground fault lands comfortably above that pickup with margin. If you change the relay later, re-check the ratio: a CT selected for a 0.25 A sensitive input will not serve a conventional 5 A phase input, and the reverse.
Checks before the protection goes in service #
De-energize and verify absence of voltage before opening any panel or terminal compartment to work on CT circuits.
- Confirm on the one-line and physically that only the intended grounding conductor passes through the CT window, and that polarity is marked and wired per the relay manual.
- Get the minimum and maximum ground current for that conductor from the grounding design and a fault study, not from a bus fault value.
- Verify the CT secondary rating, the relay input type and range, and the connected burden including lead resistance.
- Calculate the secondary current at the minimum fault current and confirm pickup margin; calculate at the maximum and confirm the relay and CT tolerate it.
- Coordinate pickup and timing with upstream and downstream devices using the actual relay curves, including transformer inrush where a primary-side device is involved.
- Commission with the approved primary or secondary injection test: inject a known current, compare relay indication against the injected value and ratio, and confirm the trip output operates the intended breaker.
If the relay fails to pick up at the required test current, the mismatch is in ratio, wiring, input range, burden or setting. If it trips in normal operation, investigate the current path, polarity and coordination rather than simply raising the pickup; the fault-locating readings covered in Locating a ground fault on a resistance-grounded 480 V system help separate a real fault from a wiring error.
The decision #
For ground fault duty on a transformer primary in a resistance-grounded system: find the limited ground current (here 5.0 A through a 55.4 ohm resistor on 480 V), select a CT whose ratio puts that current well above the relay input's minimum pickup, and use a sensitive ground input when the ratio is low. Do not justify a high ratio from the 2000 A available fault current; a 2000:5 CT leaves 12.5 mA at the relay and the fault goes undetected. Reserve high-ratio CTs for phase overcurrent duty, where the bus fault current is the right input, as in the fault current calculations covered in Available fault current vs secondary short-circuit current.
Questions asked
Can I choose a 2000:5 CT because the available fault current is 2000 A?
Not for ground fault duty. The available fault current describes a phase-fault condition at the bus, not the current in the grounding conductor. On a resistance-grounded system the ground current may be a few amperes, so a 2000:5 CT delivers milliamperes to the relay. Work from the limited ground current and the relay's minimum pickup instead.
Is a 5 A secondary CT more sensitive than a 1 A input?
Neither secondary rating is inherently more sensitive. Sensitivity comes from the combination of ratio, burden and the relay's usable pickup range. A low primary ratio such as 75:1 feeding a 1 A sensitive ground input produces far more secondary signal at a 5 A ground fault than a 2000:5 CT at the same fault, which is what matters.
Why measure the grounding conductor current instead of the voltage across the resistor?
Voltage across the grounding resistor confirms that a ground fault exists somewhere on the system, but it cannot tell you which feeder carries the fault current. Current measurement, on the grounding conductor or on individual feeders with zero-sequence CTs, gives both detection and location.
Does the accuracy class matter at these low currents?
Relaying accuracy classes describe performance at 1 to 20 times rated secondary current, well above the milliampere signals a ground fault produces on a high-ratio CT. At low multiples the ratio error is not guaranteed by the class, so pick a ratio that puts the expected ground fault signal in the relay's specified operating range rather than trusting the class at the low end.