Explainer

What star and delta jumper bars mean on a motor terminal box

Motors and motor starters Published 8 min read By Current Intel engineering team

Short answer

One jumper bar joining the three winding ends is a star connection — the supply lands on the other three terminals. Three bars, each bridging one terminal to its neighbour, are delta. At 380 V in star, each winding sees about 219 V and the leads carry the plate's 2.7 A; delta needs a 220 V-class supply and about 4.7 A at the leads.

On this page
  1. Which jumper layout is star, and which is delta?
  2. Why does one bar tie all three winding ends together?
  3. What voltage lands on each winding in star and in delta?
  4. How do you calculate winding voltage and line current?
  5. How does the nameplate tell you which connection is built in?
  6. Which connection does the drive's output voltage call for?
  7. How do you land the leads and set the drive?
  8. What checks catch a wrong connection before the winding cooks?
  9. Questions asked

A motor terminal box with one jumper bar joining three terminals together is wired in star, and the three supply leads land on the other three terminals; three separate bars, each bridging one terminal to its neighbour, are delta. Both layouts use the same six winding ends — only the bar placement changes — and the bar placement sets how much voltage reaches each winding. That placement is the whole puzzle in a motor swap: the plate rating and the drive's output voltage decide which layout the new motor must carry, and reading the bars wrong shows up as an overcurrent trip at best and a cooked winding at worst.

Which jumper layout is star, and which is delta? #

One jumper bar joining the three winding finishes into one common point makes it a star (Y) connection, with the supply leads on the three terminals the bar leaves alone; three separate bars, each bridging a finish to a neighbouring start, make it delta.

Most boxes arrange the six ends as two rows of three, winding starts on one row and finishes on the other, usually marked U1, V1, W1 and U2, V2, W2. In the star layout one bar runs across a row and ties the three finishes together. In the delta layout three bars run one per column, each joining a finish to the start beside it, so the winding ends close into a loop. The supply lands on the same three terminals either way — the row the bars leave open in star, the three bar junctions in delta. Count the bars first: one is star, three is delta, and the diagram printed beside the voltage on the plate says which one the motor was built for.

Why does one bar tie all three winding ends together? #

That single bar creates the star point, the common node where all three winding finishes meet, so each winding hangs between one supply line and that point instead of directly across two lines as it would in delta.

The bar is not a short circuit. It joins winding finishes to each other, not line to line, and in balanced running the three winding currents add to zero at that node, so the bar carries almost no current. What it does electrically is fix where the voltage divides: with the finishes commoned, the line-to-line voltage splits across two windings in series around the loop, and each winding settles at its share. Delta has no such node — the three bars close the loop onto itself, and every winding faces a pair of lines on its own.

What voltage lands on each winding in star and in delta? #

In star the line voltage splits so each winding sees line voltage divided by the square root of three, while in delta each winding connects straight between two lines and sees the full line voltage.

The current relation runs the other way. Star shares the current: winding current and line current are the same. Delta multiplies it at the leads: each winding carries the winding current, and the line current is √3 times that. Voltage down, current up — which is why one winding set legitimately carries two plate ratings, a higher one against the star diagram and a lower one against the delta diagram.

Star (Y) Delta
Bars in the box one bar across the three finishes three bars closing finish to start
Voltage on each winding line voltage ÷ √3 the full line voltage
Line current at the leads the winding current √3 × the winding current
Plate voltage printed against it the higher rating the lower rating

How do you calculate winding voltage and line current? #

Work the numbers from the plate of the example motor — 380 V, 2.7 A, star diagram — and everything falls out of the two relations above, assuming a balanced supply at rated frequency.

These figures are estimates from the three-phase relations; the motor plate and the maker's documentation govern.

  • Winding voltage in star: 380 V ÷ √3 = 380 V ÷ 1.732 = 219.4 V, so about 219 V sits across each winding.
  • Winding current in star: equal to the line current, so each winding and each lead carries 2.7 A.
  • The same windings closed into delta on a 220 V supply: each winding sees the full 220 V, within half a percent of the 219 V the star connection gave it, and each winding still carries 2.7 A — while the leads now carry √3 × 2.7 A = 1.732 × 2.7 A ≈ 4.7 A.

Two results decide the swap: the voltage the bars put on the windings, and the current the drive must carry at the leads.

How does the nameplate tell you which connection is built in? #

The plate pairs each voltage with a current and a diagram: read the star diagram against the higher voltage, and the current printed beside it is the line current you will see at the drive — in star the line current and the winding current are one and the same.

A dual-voltage plate prints two rows, the higher voltage against star and the lower against delta, because the same winding set holds both ratings. A plate with a single row is a single-rating motor: its diagram is the connection it was wound and jumpered for, and the printed current belongs to that connection. That printed current is the line current at the leads, not the current inside the copper — Motor nameplate current is line current, not winding current works through that distinction — and in delta the two differ by √3.

Some motors reach the second connection through extra leads instead of jumper bars: dual-voltage machines built to the North American scheme do it with nine leads, and Wiring nine-lead dual voltage motor leads to a VFD walks that identification.

Which connection does the drive's output voltage call for? #

Match the connection to the drive's rated output voltage: at the plate voltage the star bar stays as delivered, while a drive rated for the lower, 220 V class calls for delta, which puts the design winding voltage back on each winding but multiplies the lead current by √3.

  • Drive output matches the plate voltage: leave the star bar in place, land the leads on the open row, enter the plate current in the drive. The motor runs as built.
  • Drive rated for the lower voltage class: delta is the electrically correct connection, and the drive must be sized for the higher lead current — about 4.7 A on this motor instead of the plate figure. Move the bars only when the plate itself lists the delta rating; when the plate shows star only, get the maker's data sheet to confirm the windings and the terminal hardware are delta-rated before jumping anything.
  • No delta rating anywhere in the maker's data: do not improvise the second connection — fit a motor whose plate matches the drive, or a drive whose output matches the plate.

The move that ruins motors is the reverse one: closing star-wound windings into delta on the higher supply puts √3 times the design voltage on every winding. The iron saturates, the current climbs past the drive's limit, and the job ends in a trip or cooked insulation. The same supply-versus-connection decision at a different voltage is worked through in Wye or delta winding for a 200 hp 480 V motor.

How do you land the leads and set the drive? #

With the box open and the power locked out, the leads land on the terminals the bars leave open — in star the row without the bar, in delta the three bar junctions — and the drive takes the motor data for the connection you chose.

  1. De-energize the drive, lock it out, and verify absence of voltage at the drive output terminals and inside the motor box, waiting the DC-bus discharge time the drive manual gives. NFPA 70E, the Standard for Electrical Safety in the Workplace, 2024 edition, covers verifying the absence of voltage before work that exposes energized parts; confirm the requirements that apply to you with the local authority having jurisdiction and the equipment documentation.
  2. Land the supply leads on the three open-row terminals for star or on the three junctions for delta, and torque the terminal hardware to the value in the motor documentation.
  3. Enter the motor data for the chosen connection: connected voltage, plate current, rated frequency, rated speed.
  4. Set the drive's base output voltage — the V/f setting that defines the output voltage at full output frequency — to the connected voltage, so the drive never puts more on the windings than the bars deliver.
  5. Run the drive's motor self-tuning routine if it offers one, then bump the motor at low speed and confirm rotation; swap any two supply leads to reverse it.

What checks catch a wrong connection before the winding cooks? #

Three equal resistance readings and a no-load current near a small fraction of the plate figure clear the connection; one pair reading far low points at a misplaced bar, and hum, heat at no load or an overcurrent trip at low speed points at the wrong winding voltage.

Measure resistance between each pair of the three supply terminals with the motor disconnected. A correct star or delta layout puts two windings in the path between any pair, so the three readings come out equal; a pair reading far below the others means a bar sits in the wrong place or a winding has shorted turns.

Then insulation: measure from the leads to the frame with a megohmmeter classed for the winding voltage, and judge the number against the motor maker's stated minimum — the way a low lead-to-ground reading gets weighed is shown in Reading motor lead-to-ground ohms on a 480 V compressor. On the first run, ramp slowly and watch the drive's output-current display against the plate current: a no-load draw far above a small fraction of the rating says the voltage on the windings does not match their rating, which means the bars or the base voltage setting is wrong.

Decision rule for the whole job: the bars follow the plate diagram, the plate diagram follows the drive's output voltage, and the drive's motor data follows the connection the bars make.

Questions asked

What happens if the three supply leads land on the jumpered terminals?

The bar ties those three terminals into one node, so closing the supply onto them connects all three lines together — a line-to-line fault that the drive trips out instantly, with no voltage across any winding and no rotation. Move the leads to the three terminals the bar does not touch.

Can a star-rated motor be closed into delta on the same supply?

No. Delta puts the full line voltage on every winding instead of the line voltage divided by √3 — a winding designed for about 219 V would see about 1.73 times that — so the iron saturates, the current climbs far past the plate figure, and the drive trips on overcurrent or the winding overheats until the insulation fails. Keep the star bars unless the plate lists a delta rating at the supply voltage.

What if the drive outputs 220 V and the motor stays in star?

Each winding sees only 220 V ÷ √3, about 127 V — barely half its design voltage — so the flux falls, torque collapses, and the motor stalls under load well before it reaches speed. The fix is the delta connection on that lower-voltage supply, provided the plate or the maker's data lists the delta rating; otherwise the motor is the wrong voltage class for the drive.

Why does the drive's motor-current setting have to match the connection?

The drive uses that number as its motor protection. Enter the plate current while the star bar is in place; after a delta rewire enter the delta line current, which is √3 times the winding value, because the drive sees the leads. A figure left over from the old motor either nuisance-trips below the true load or lets the new winding cook above it.

How do you find the winding ends if the terminal markings are missing?

With the motor disconnected, read resistance between every pair of leads. Three independent windings give three pairs of equal low readings and no continuity between different windings. Label each good pair as one winding's two ends, land them to match the bar layout you need, and let the equal-resistance check after assembly confirm the bars sit right.

Keep reading

  • Explainer

    Motor nameplate current is line current, not winding current

    The amps printed on a three-phase motor nameplate are line current: what a clamp meter reads in each supply conductor at full load in the plate's designated connection. In star, winding current equals line current; in delta, each winding carries the line current divided by 1.73 — about 14.5 A for a 25 A plate.

    Motors and motor starters

  • Explainer

    Why a 415 V delta motor cannot run on 240 V

    A plate that reads 415 V delta, with no second voltage-connection pair, describes single-voltage windings that need 415 V across each coil. On a 240 V supply the motor reaches about one third of rated torque in delta and about one ninth in star, so it will not serve as a full-rated rotary phase converter idler. Replace it with a motor whose plate reads 240 V delta or feed it through a step-up transformer.

    Motors and motor starters

  • Explainer

    Why star-delta starting on motors under 5 hp buys you nothing

    You can use a star-delta starter at any motor rating, but no standard requires it, and under 5 hp it buys you nothing: a 5 hp, 460 V motor draws 7.6 A full load, so its DOL inrush is small against a plant feeder. Choose DOL unless the utility or a weak supply forces reduced-voltage starting.