Current IntelPower LibraryShop main store

Explainer

Motor nameplate current is line current, not winding current

Motors and motor starters Published 7 min read By Current Intel engineering team

Short answer

The amps printed on a three-phase motor nameplate are line current: what a clamp meter reads in each supply conductor at full load in the plate's designated connection. In star, winding current equals line current; in delta, each winding carries the line current divided by 1.73 — about 14.5 A for a 25 A plate.

On this page
  1. Is the current on a three-phase motor nameplate line current or winding current?
  2. What is the difference between line current and winding current in star and delta?
  3. How much current flows in each winding of a delta motor?
  4. Why do the six leads between a star-delta starter and its motor carry less current?
  5. Where do you measure current to compare it with the nameplate?
  6. Which current goes into the overload relay, the conductors and the breaker?
  7. What about dual-voltage nameplates and motors built to run in star?
  8. Questions asked

The amps printed on a three-phase motor nameplate are line current: what a clamp meter reads in each of the three supply conductors at full load, at the rated voltage and frequency, with the motor in the connection the plate designates. In star, winding current and line current are the same number. In delta, each winding carries the line current divided by 1.73. On a star-delta starter the rating belongs line side of the starter, and the six leads to the motor carry less during the delta run. Overload settings, conductor sizes and breaker picks all hang on that one reading, so this article gives the relationships, a worked example and the decisions for each case.

Is the current on a three-phase motor nameplate line current or winding current? #

It is line current — the rating applies to each supply conductor feeding the controller at full load, at the nameplate voltage and frequency, in the connection the plate designates, and that holds for IEC and NEMA plates alike.

The plate is written for the person wiring, protecting and feeding the machine, and every one of those jobs happens in the supply conductors. Current, power factor, efficiency and torque on the plate are stated at rated voltage and frequency; the winding currents inside the machine stay a design quantity in the manufacturer's drawing office. IEC 60034-1 and NEMA MG 1 both rate their machines at the terminals, which is why a plate from an IEC market and one from a NEMA market answer this question the same way. The winding figure matters to almost nobody on the installation side — but it does matter when a device physically sits in a winding, and the next sections say exactly when.

What is the difference between line current and winding current in star and delta? #

In star they are the same number; in delta the winding current is the line current divided by 1.73, so a delta machine with a 25 A plate runs about 14.5 A through each winding.

The geometry causes it. In star, each line conductor feeds one winding and nothing else, so the same amps flow in both. In delta, each winding sits across a pair of lines; the three winding currents combine vectorially at the junctions, and for a balanced load each line current comes out at the square root of three — 1.73 in round numbers — times the winding current. Neither connection changes what the plate states.

Connection Winding current vs line current What a 25 A nameplate means
Star (wye) I winding = I line The rated current in each line and in each winding
Delta I winding = I line ÷ 1.73 25 A in each line, about 14.5 A in each winding

Both rows assume a balanced three-phase load. Unequal line currents point to a supply or winding problem and get investigated as their own fault, not with these ratios.

How much current flows in each winding of a delta motor? #

Divide the line current by 1.73. Carried exactly with √3 = 1.732 the winding value comes out at 14.4 A per winding on the example plate; with the usual 1.73 rounding it comes out at 14.5 A — the two answers differ by rounding only.

Worked example, on an illustrative plate; the real machine's own plate governs:

  • Inputs: rated line current 25 A, connection delta, balanced three-phase load, motor at full load.
  • Formula: winding current = line current ÷ √3.
  • Arithmetic: √3 = 1.732, so 25 A ÷ 1.732 = 14.4 A; with the usual 1.73 rounding, 25 A ÷ 1.73 = 14.5 A.
  • Check: 14.5 A × 1.73 = 25.1 A, back to the plate within rounding.
  • Basis: the balanced-delta line-versus-winding relation. Treat the result as an estimate and let the plate and the machine's documentation set the real limits.

Use the winding figure only where a device actually lives in a winding — the inside-delta overload relay, or the ampacity check on the six starter-to-motor leads. Every supply-side number takes the line value.

Why do the six leads between a star-delta starter and its motor carry less current? #

During the delta run those six conductors are the windings themselves, so each carries winding current — about 0.58 times the line current, which is the winding value on the example plate — and the nameplate value still applies line side of the starter.

The factor is 1 ÷ 1.73 = 0.58. While the starter holds the motor in star, the same six conductors carry the full line current of that moment, because star winding current equals line current; the changeover to delta is where each lead's burden drops to the winding value, and the lead ampacity and the starter's contactors are chosen for both conditions. Overload protection splits the same way: a relay wired inside the delta carries winding current and is set to 0.58 of the rated line current, while a relay in the lines takes the full nameplate value. Where the relay belongs in this circuit, Overload relay placement in a wye-delta starter circuit walks the two positions, and where the breaker objects to the changeover itself, Fixing star-delta starter breaker trips at transition covers that fault.

Where do you measure current to compare it with the nameplate? #

Clamp each of the three incoming supply conductors at the controller while the machine runs at full load in its designated connection — that phase-by-phase reading is the one the plate compares with, and a clamp on one of the six starter-to-motor leads will not match it.

Use a true-RMS clamp meter; an average-reading instrument underreports distorted current, and distorted current is exactly what a motor fed through a drive or off a sagging supply can produce. Before you believe any comparison, confirm the terminal links or the starter's run state actually produce the delta or star that the plate pairs with the applied voltage — a supply voltage on its own, 400 V, 415 V or 480 V, never decides the connection; the pairing printed on that plate does. The divide-by-1.73 and the 0.58 relations are balanced-load arithmetic, so if the three line readings differ materially the comparison is meaningless until the imbalance is found.

One safety note: de-energize, lock out and verify absence of voltage with a proven tester before opening the controller or the motor terminal box. If the current check has to be made with the equipment energized, NFPA 70E, 2024 edition, governs it as energized work, with its risk assessment, protective equipment and approval steps.

Which current goes into the overload relay, the conductors and the breaker? #

Everything on the supply side works on line current: a relay in the line takes the full nameplate value, one wired inside the delta takes 0.58 times it, and conductors and the breaker are chosen on line current under NFPA 70, the National Electrical Code, 2023 edition.

For a single motor branch, Article 430 sizes conductors from the code's ampacity tables and the 125 percent rule rather than straight from the plate — conductor sizing under NEC 430.22 covers exactly that split. The line-side relay is the ordinary case and takes its setting from nameplate full-load current; Setting overload relays from motor nameplate full-load current walks that procedure. The short-circuit device works on line current too, and it must ride through inrush well above it: a supplementary specification to IEC 60034-1 for high-voltage machines without specific starting requirements declares locked-rotor current between 4 and 6.5 times rated current, and each specific machine's data gives its own multiple. Confirm the article, the edition and any local amendments with the authority having jurisdiction and the equipment documentation before you commit a size.

What about dual-voltage nameplates and motors built to run in star? #

The plate lists a current beside each voltage-and-connection pairing, all of them line currents, and a machine built to run only in star — medium-voltage motors are the common case — still states line current for that star connection.

An IEC six-lead plate typically pairs the lower voltage with delta and the higher with star, one factor of 1.73 apart — 230 V delta, 400 V star — and the two line currents come out nearly equal, because the same winding current delivers the same output in either connection. A NEMA nine-lead dual-voltage plate uses a two-to-one voltage pair such as 230/460 V, and the high connection draws half the line current of the low one. Read the current beside the voltage you are actually applying; never carry one pairing's figure to the other. For the connection decision on a particular machine, Wye or delta winding for a 200 hp 480 V motor works a real example.

The whole question in one line: the plate gives you line current in its designated connection, you measure line current at the controller, and you divide by 1.73 — or multiply by 0.58 — only when the device you are setting or the conductor you are checking physically lives inside the delta.

Questions asked

Is a 415 V measured supply a problem for a motor rated 400 V?

No. IEC 60034-1 allows continuous operation within a plus or minus 5 percent band around rated voltage, and 415 V on a 400 V motor is plus 3.75 percent (415 ÷ 400 = 1.0375). Stay inside the band the manufacturer documents, and watch the line current while you are at it, because many designs draw more of it as voltage rises.

What do the six motor leads carry while the starter still holds the motor in star?

Full line current, whatever the motor draws at that moment. In star the winding current equals the line current, so each of the six conductors carries the reduced starting current of the star connection; after the changeover to delta it settles near 0.58 of the rated line current at full load.

Does the line-current rule hold for other three-phase equipment such as transformers?

For motors the convention is uniform: IEC 60034-1 and NEMA MG 1 machines are rated at their terminals, so the plate states line current. Other equipment follows its own standard — a three-phase transformer plate gives current per terminal for its kVA and voltage — so check that class of gear directly instead of carrying the motor rule across.

Which figure applies when a plate shows a single current with no connection symbol?

The line current, same as any other plate. A single-voltage motor with three terminals may be delta or star inside, but with only three conductors leaving the terminal box no winding is reachable to measure, and no installation task needs the winding figure: relay setting, conductor sizing and breaker choice all run on the plate value at the supply conductors.

How do power factor and efficiency on the plate cross-check the current?

Multiply them into volt-amperes: 1.732 × rated voltage × rated line current. At 400 V and a 10 A plate that chain gives 6.9 kVA of input; times a 0.85 power factor, 5.9 kW of input power; times 0.90 efficiency, roughly 5.3 kW at the shaft. If the plate's kilowatt rating disagrees badly with this chain, suspect the readings, not the arithmetic.

Keep reading

  • Explainer

    Why a 415 V delta motor cannot run on 240 V

    A plate that reads 415 V delta, with no second voltage-connection pair, describes single-voltage windings that need 415 V across each coil. On a 240 V supply the motor reaches about one third of rated torque in delta and about one ninth in star, so it will not serve as a full-rated rotary phase converter idler. Replace it with a motor whose plate reads 240 V delta or feed it through a step-up transformer.

    Motors and motor starters

  • Troubleshooting

    Why an oversized soft starter may not suit a smaller motor

    An 18.5 kW soft starter can sometimes stay on a 9.5 kW motor, but only after three checks: the starter's documented minimum motor current, the adjustable overload setting span, and the short-circuit coordination. Swap the breaker alone and one of those usually fails.

    Motors and motor starters

  • Explainer

    Why star-delta starting on motors under 5 hp buys you nothing

    You can use a star-delta starter at any motor rating, but no standard requires it, and under 5 hp it buys you nothing: a 5 hp, 460 V motor draws 7.6 A full load, so its DOL inrush is small against a plant feeder. Choose DOL unless the utility or a weak supply forces reduced-voltage starting.

    Motors and motor starters