Troubleshooting
Why an oversized soft starter may not suit a smaller motor
Short answer
An 18.5 kW soft starter can sometimes stay on a 9.5 kW motor, but only after three checks: the starter's documented minimum motor current, the adjustable overload setting span, and the short-circuit coordination. Swap the breaker alone and one of those usually fails.
On this page
- Can you keep the existing soft starter on the smaller motor?
- What minimum motor current does a soft starter require?
- Does the overload setting reach the smaller motor's current?
- Does swapping the MCB for a smaller rating finish the job?
- Example: does a 16.9 A motor sit inside a 38 A starter's permitted band?
- What else changes when the motor halves?
- When must the starter be replaced?
- Questions asked
The project changed one motor from 18.5 kW to 9.5 kW, and the specified soft starter was sized for the larger machine. Replacing the branch breaker and leaving the starter in place is tempting, but the starter's own documentation decides that, not the kW on the schedule. Check its permitted motor-current range, its adjustable overload span and the short-circuit coordination before you sign the change.
Can you keep the existing soft starter on the smaller motor? #
Sometimes, but only if the smaller motor's nameplate current falls inside the starter's documented permitted motor-current range and its protection can be set to that current. The starter's top rating is not the question; its minimum is. Swap the breaker alone and you may satisfy the conductors while leaving the motor without usable overload protection.
Soft starters work by controlling the voltage during the start, so the semiconductor stack cares about current, not nameplate kilowatts. The original unit passing the smaller motor's running current is thermally comfortable, but many starters specify a minimum motor current below which their measuring circuits and protective functions are not claimed to work. That minimum is where most reuse attempts fail.
What minimum motor current does a soft starter require? #
Read the permitted motor-current range from the starter's own technical data for the exact order number on the device. As a documented example, Schneider's FAQ for the Altistart ATS480 states the starter supports motors from 40% to 130% of the starter's rated nominal current — a range of that shape is what you need for your unit, and the exact percentages come from its datasheet.
If your starter's documentation states no minimum motor current, that absence is not permission; ask the manufacturer or its authorized distributor for a written application limit before approving the reuse. A selection decision built on silence is an assumption, not engineering.
Does the overload setting reach the smaller motor's current? #
The overload function must be adjustable down to the smaller motor's nameplate current, and it must be a device or function that actually protects the motor. A starter sized for the original machine may have a motor-current setting floor above the smaller motor's full-load current, in which case the motor has no effective overload protection and the starter must be replaced or external protection added.
Read the replacement motor's nameplate and record rated voltage, rated current, frequency, connection and duty — never infer the current from the kW figure. Efficiency and power factor move full-load current by tens of percent between motor designs of the same kW. If you are setting a separate overload relay from that nameplate value, the method is the same one used for any starter; see Setting overload relays from motor nameplate full-load current.
Under NFPA 70, the National Electrical Code, 2023 edition, motor circuits need separate short-circuit and ground-fault protection for the conductors and separate overload protection for the motor; confirm the exact Part III and Part IV sizing rules with your authority having jurisdiction and the equipment documentation, because editions and local amendments differ.
Does swapping the MCB for a smaller rating finish the job? #
No. A smaller general-purpose breaker protects the conductors; it does not give the motor overload protection, and dropping it in proportion to the kW reduction can cause nuisance trips on start without protecting anything. The breaker must be sized to the code rule for the new motor and must also meet the starter manufacturer's listed protective-device requirements and the available fault current.
Short-circuit protection and motor-overload protection are different functions with different devices. The term MCB tells you neither which function the breaker performs nor whether it coordinates with the starter's semiconductor fuses or internal protection. Check the proposed device against the starter's instructions and the fault level at the panel — the per-unit method for the available secondary fault current is worked through in How to calculate transformer secondary fault current in per-unit. Also note that motor starting peak currents are not comparable to instantaneous breaker settings; the reasons are in Why motor start peaks don't compare to instantaneous breaker settings.
Example: does a 16.9 A motor sit inside a 38 A starter's permitted band? #
Yes in this illustrative check — the motor current is 44% of the starter rating, above a 40% floor but below the overload setting's reach, which is exactly the marginal case worth calculating before ordering anything. This is a worked example, not your installation; substitute your own nameplate and datasheet values.
Inputs: 9.5 kW three-phase motor, 400 V line-to-line, 50 Hz, assumed efficiency 0.90, assumed power factor 0.85, starter rated 38 A (typical for an 18.5 kW / 400 V unit), permitted motor-current range 40% to 130% of starter rating.
- Full-load current: I = P / (√3 × V × η × cosφ) = 9500 W / (1.732 × 400 V × 0.90 × 0.85) = 9500 W / 530.1 V·A ≈ 17.9 A. (With η and cosφ folded into one 0.765 factor: 400 × 1.732 × 0.765 = 530.1.)
- Ratio to starter rating: 17.9 A / 38 A = 0.47, or 47% — inside a 40% to 130% band.
- Minimum motor current at 40%: 0.40 × 38 A = 15.2 A. The motor's 17.9 A clears that floor by 2.7 A.
- Overload check: the adjustable setting range must include 17.9 A. If the starter's motor-current setting floor is, say, 20 A, the reuse fails at this step regardless of the range check.
Decision for this example: the range check passes and the overload check decides. If the overload setting cannot reach 17.9 A, replace the starter; if it can, and the short-circuit coordination holds, the reuse can proceed.
What else changes when the motor halves? #
The driven load and the start settings, not just the electricals. A reduced-voltage start tuned for the original motor may leave the 9.5 kW machine unable to accelerate the same load; a motor sitting at low speed while drawing elevated current overheats even though its kW is well under the starter's rating — the mechanism is the same one behind Why a large motor stalls when the soft starter hits current limit.
Run this checklist before the first start:
- Confirm the smaller motor meets the machine's breakaway, running and acceleration torque requirements.
- Record every existing starter setting — initial voltage, ramp time, current limit if fitted — as a baseline before changing anything.
- Set the new starting parameters only within the ranges printed in the starter's instructions, and prefer an initial voltage around 50% of nameplate with a 3 to 5 second ramp over a tight current limit.
- Check the starting duty (duration, starts per hour, load inertia) against the starter's documented duty limits for its rating.
- Verify conductor size, terminations, protective bonding and the control circuit against the revised schematic.
- Update the drawings, motor schedule and setting record to name the smaller motor and its actual protection.
De-energize, lock out and verify absence of voltage before opening the starter or motor terminal boxes.
When must the starter be replaced? #
Replace it when any one check fails: the motor's nameplate current falls below the starter's documented minimum, the overload setting cannot reach that current, the starting-duty limits are exceeded, or the short-circuit coordination with available devices cannot be documented. A starter that fails one limit fails the reuse; a smaller unit matched to the new motor is the correct outcome, and the selection logic is the same as any first-time choice — see Matching a soft starter current range to its power structure.
If every check passes, keeping the starter is a legitimate engineering change: document the permitted range, the overload setting, the protective device and the fault level, and record them with the revised motor data. If the reason for the motor change was that the original 18.5 kW machine was oversized for its load, it is also worth quantifying what the smaller motor saves; the approach is laid out in the motor downsizing savings calculator for oversized motors.
Questions asked
Why can't the soft starter's own electronics protect the smaller motor?
The starter's semiconductor and trip protection are scaled to its own rated current, which was chosen for the original, larger motor. A fault or overload on the smaller motor sits near or below the starter's minimum response band, so the starter may never see it as a problem. The motor needs its own overload device set within a range that actually includes the motor's nameplate current.
Does derating matter if the panel runs hotter than 40 C?
Yes. One vendor's guidance derates a soft starter's current capacity by roughly 2% for every 1 C above 40 C ambient, so a starter in a 50 C cabinet carries about 20% less current capacity than its 40 C rating. The smaller motor may still fall inside the permitted band after derating, but recalculate the range with the derated value before approving the reuse.
What settings should I record before changing anything on the starter?
Photograph or log every adjustable parameter before touching them: initial voltage, ramp time, current limit if fitted, and any motor-current setting used by the starter's protection. Note the values against the old motor. That gives you a traceable baseline, and it lets you return to the previous configuration if the new motor's start behaves badly on the first try.
Is the current limit the right way to reduce starting current on the smaller motor?
Not on its own. Experienced practitioners set the initial voltage around 50% of nameplate with a 3 to 5 second ramp and leave the current limit at a high setting, because a tight current limit can stall the motor before it accelerates. A stalled motor at reduced voltage still draws elevated current and heats quickly, which is worse than a higher but shorter inrush.