Current IntelPower LibraryShop main store

How-to

Wiring nine-lead dual voltage motor leads to a VFD

Variable frequency drives Published 7 min read

Short answer

On a 230 V drive, pairs T1-T7, T2-T8 and T3-T9 land on the three output terminals and T4-T5-T6 are joined and insulated; on a 460 V drive, T1, T2 and T3 land on the outputs with 4-7, 5-8 and 6-9 joined. No winding lead is ever grounded — the motor frame and drive chassis carry the equipment-grounding conductor.

On this page
  1. Which motor leads go to the VFD output terminals?
  2. What do leads T4, T5 and T6 connect to?
  3. Does any winding lead carry the ground?
  4. How do I know if my motor needs the low- or high-voltage connection?
  5. How do I identify the leads after the cable was changed?
  6. What settings go into the drive before the first start?
  7. What do I check on the first run?
  8. What is the final wiring decision for each case?
  9. Questions asked

On the low-voltage connection of a nine-lead dual-voltage motor, T1 joins T7, T2 joins T8 and T3 joins T9 — one pair on each of the drive's three motor-output terminals — while T4, T5 and T6 are tied together, insulated and connected to nothing else. Grounding is a separate job: the equipment-grounding conductor bonds the motor frame and the drive chassis. If the cable was cut up and re-tasked along the way, jacket colors prove nothing, so every conductor gets identified by continuity with the circuit locked out before the drive sees power.

Which motor leads go to the VFD output terminals? #

T1 tied to T7, T2 tied to T8, and T3 tied to T9 — one pair per output terminal U, V, W. That is the low-voltage (parallel-wye) connection of a nine-lead dual-voltage motor, and it is the one a 230 V-class drive calls for.

A nine-lead dual-voltage motor has two half-windings per phase. On the low-voltage connection the two halves of each phase sit in parallel, so both of their line-end leads land on the same output: T1 with T7 on one terminal, T2 with T8 on the second, T3 with T9 on the third. Drive outputs are usually marked U, V, W; some drives print U/T1, V/T2, W/T3, and that /T1 marking has nothing to do with the motor's T-numbers.

Which pair goes on which terminal is a free choice — any assignment gives a symmetric three-phase connection, and rotation is settled at first run.

What do leads T4, T5 and T6 connect to? #

Nothing but each other: T4, T5 and T6 are joined in one insulated connector and land on no drive terminal, no ground bar and no frame stud.

On the low-voltage connection that three-lead tie completes the winding star point, which the motor needs but the drive never sees. The junction is live: it sits at winding potential and carries charging current from the drive's switching output, so it gets insulated like a phase lead and secured where it cannot touch the frame or a lug. It is not a neutral, and it never leaves the terminal box.

Does any winding lead carry the ground? #

None of them — no winding lead is ever a grounding conductor. The motor frame, the drive chassis and the cable armor or conduit bond through the equipment-grounding conductor, and all nine numbered leads stay on the power path.

A drive output is not a grounded circuit. Land a winding lead on the grounding conductor and the drive sees an output-to-earth fault the moment it runs: it trips if it detects one, and current flows through places it was never meant to if it does not. NFPA 70, the National Electrical Code, 2023 edition, covers equipment grounding and bonding of frames and enclosures in Article 250; confirm the details with your authority having jurisdiction and the equipment documentation. The T4-T5-T6 tie is equally off-limits as a ground — it is part of the winding.

How do I know if my motor needs the low- or high-voltage connection? #

Match the connection to the drive's output voltage, which follows its supply: a drive fed at 208-240 V takes the low-voltage connection, and the high-voltage connection belongs to the other class of supply.

A drive's output voltage tracks its supply voltage within its rating; it cannot raise 230 V to feed a series connection. So the supply decides:

Motor connection Drive output class Land on U, V, W Join together, insulate
Low voltage (parallel wye) 208-240 V T1 + T7, T2 + T8, T3 + T9 T4 + T5 + T6
High voltage (series wye) 460 V T1, T2, T3 T4 + T7, T5 + T8, T6 + T9

That table is the wye arrangement, which nearly all nine-lead dual-voltage motors of this class use; the connection diagram printed on the nameplate is the deciding document, and a delta diagram is followed as printed. Reading the two voltage-and-current pairs off a nameplate is its own skill — see reading a dual voltage frequency spindle motor nameplate.

How do I identify the leads after the cable was changed? #

By continuity with the circuit dead, never by jacket color: lock out the disconnect, let the drive's DC bus discharge for the interval on its label, verify zero voltage, then ring out every conductor end to end.

The lockout-and-verify sequence is not optional: NFPA 70E, 2024 edition, covers de-energizing and verifying absence of voltage before conductors are touched, and a drive's DC bus holds charge after the display goes dark. With the circuit dead and verified, work the altered cable end to end:

  1. Open and lock the disconnect feeding the drive, and tag it.
  2. Wait the bus-discharge interval stated on the drive's warning label or in its manual, then verify absence of voltage at the drive terminals with a tester rated for that voltage.
  3. Open the motor terminal box and match each lead's T-number to the nameplate diagram. If the numbers are gone from the leads, stop and get the connection data from the motor manufacturer — resistance readings alone will not assign all nine.
  4. Ring out each cable conductor from drive end to motor end and write down the mapping. Inspect the clipped conductor and whichever conductor was used as ground; if insulation, lugs or strain relief are damaged, replace the cable rather than patch it.
  5. Reserve green and green/yellow insulation for the equipment-grounding conductor; phase conductors get any other color.
  6. Land T1 + T7, T2 + T8 and T3 + T9 on the three output terminals; join T4, T5 and T6 in one insulated connector.
  7. Bond the motor frame and the drive's ground terminal with the equipment-grounding conductor.
  8. Tighten every termination to the torque in the equipment documentation, confirm no exposed copper, and close the boxes.

If an insulation-resistance test is wanted, disconnect the motor leads from the drive first: a megger's test voltage through the drive's output stage destroys it.

What settings go into the drive before the first start? #

The motor's nameplate values at the connection voltage: 230 V, the nameplate frequency, the nameplate speed, and the full-load current printed beside 230 V — for a motor nameplated 3.4/1.7 A that parameter is 3.4 A, not 1.7 A.

Every drive asks for motor nameplate data before it protects anything: rated voltage, rated current, base frequency and rated speed, plus the electronic thermal (overload) setting — the exact parameter numbers and names are in the manual for your drive model.

Worked example (illustrative nameplate): a 1 hp motor nameplate reads 230/460 V, 3.4 A/1.7 A. On the low-voltage connection with a 230 V drive, the halves are in parallel and the line current doubles: the voltage ratio is 2, and 1.7 A × 2 = 3.4 A. The drive's motor-rated-current parameter takes 3.4 A, and its overload protection follows that number. Treat any computed current as an estimate to check against the nameplate — the printed value governs.

Power-side wiring is half the hookup; the start and stop circuit is its own job, covered in wiring start and stop pushbuttons when a VFD replaces a DOL starter.

What do I check on the first run? #

Rotation and current: the motor must turn the load's required direction and stay at or below the connection's nameplate current — 3.4 A in the worked example — with no fault displayed on the drive.

Guards on, tools and hands clear. Start unloaded and read direction, current and any fault code. An independent current reading needs an instrument that tolerates a drive's switched output waveform — see measuring VFD and soft starter current with the right meter. Bring the load on in steps, watching current against the 3.4 A nameplate value and motor temperature; stop on odd noise, vibration or fast-rising heat.

If rotation is wrong, stop and lock out, then swap any two drive-output conductors — or change the drive's rotation setting where the manual puts it — and leave the ground untouched. An overcurrent trip on the first start sends you back to the lead mapping and the T4-T5-T6 tie, with the drive's fault history read per its manual before a cause is assigned.

What is the final wiring decision for each case? #

On a 230 V-class drive: T1-T7, T2-T8, T3-T9 on the outputs and T4-T5-T6 joined; on a 460 V-class drive: T1, T2, T3 on the outputs and 4-7, 5-8, 6-9 joined — and in both cases the grounding conductor lands on the frame, not on any numbered lead.

  • 230 V-class drive (208-240 V supply): low-voltage connection, drive motor current set to the 230 V nameplate amps.
  • 460 V drive: high-voltage connection, drive motor current set to the series-connection nameplate amps.
  • Cut-up or re-tasked cable: conductors identified by continuity or the cable replaced; green reserved for ground.
  • Wrong rotation: two output conductors swapped, or the drive's rotation setting, with the circuit locked out.
  • Unmarked leads: manufacturer connection data, not guesswork.

Questions asked

Can I land the T4-T5-T6 tie on a spare drive terminal so it is out of the way?

No. That junction is the winding star point, not a spare: it sits at winding potential on a switched drive output. Landing it on any drive terminal, including the ground terminal, puts drive output where it must not be and can trip a ground fault or damage the output stage. Join the three leads in their own insulated connector and secure them inside the terminal box.

The lead numbers are worn off my nine-lead motor. Can an ohmmeter sort them out?

Not with confidence. On a wye nine-lead motor the half-winding resistances are too similar to assign all nine numbers by resistance alone, and one wrong pair can burn a winding. Get the connection diagram from the motor manufacturer using the nameplate data, or have a motor shop identify and re-mark the leads before the drive is connected.

Why does the motor draw twice the current on the low-voltage connection?

The same shaft power taken from half the voltage means double the line current: the voltage ratio is 2, and 1.7 A times 2 is 3.4 A. That is why the drive's motor-current parameter takes the nameplate value printed beside the low voltage. The 1.7 A beside the high voltage belongs to the series connection only.

Can I reverse rotation at the motor instead of in the drive?

Yes. Swapping any two of the three phase connections reverses a three-phase motor; do it with the disconnect locked out and absence of voltage verified, and leave the equipment-grounding conductor exactly where it is. Many drives also have a rotation setting that swaps the output phase order in software, which avoids opening the terminal box again.

Keep reading

  • Troubleshooting

    Why a VFD trips overcurrent the instant the motor moves

    A trip a fraction of a second after the shaft first moves is a motor-circuit fault until the meter proves otherwise: the 17 A drive holds a 1.75× margin over the motor's 9.7 A full-load current, so acceleration cannot explain it. Verify the nine-lead grouping, measure resistance between all three pairs with the drive disconnected, then check torque compensation — a bigger drive is last.

    Variable frequency drives

  • How-to

    Wiring start and stop pushbuttons when a VFD replaces a DOL starter

    One motor gets one starting method: a closed DOL contactor would put the supply directly across the drive output, so drop the starters and keep one VFD per motor. Wire the stop pushbutton normally closed and the start pushbutton normally open to the drive's digital inputs on its own 24 V DC control supply, and take the emergency stop through safe torque off or the drive's supply contactor.

    Variable frequency drives

  • Selection guide

    Choosing a line reactor or motor reactor for a VFD

    Pick the side first. A line reactor goes between supply and drive input, sized on drive input amps at 3% impedance for transient buffering or 5% for harmonic reduction; a motor reactor goes between drive output and motor, sized on motor FLA, for reflected-wave protection on long shielded leads. The two are not interchangeable.

    Variable frequency drives