Current IntelPower LibraryShop main store

How-to

Wiring start and stop pushbuttons when a VFD replaces a DOL starter

Variable frequency drives Published 8 min read

Short answer

One motor gets one starting method: a closed DOL contactor would put the supply directly across the drive output, so drop the starters and keep one VFD per motor. Wire the stop pushbutton normally closed and the start pushbutton normally open to the drive's digital inputs on its own 24 V DC control supply, and take the emergency stop through safe torque off or the drive's supply contactor.

On this page
  1. Why the DOL starter and the drive cannot share one motor
  2. The decision: two drives, zero starters
  3. How to wire the pushbuttons to the drive's control terminals
  4. What changes on the power side
  5. Worked example: full-load current for two 11 kW, 380 V motors at 0.9 power factor
  6. Commissioning checks before handover
  7. Wiring mistakes that recur on rebuilt panels
  8. Questions asked

One motor gets one starting method, so the panel as specified cannot work: a closed DOL contactor connects the motor terminals straight to the supply, and that same point is the drive's output. Speed control is in the specification, so keep one VFD per motor, delete the two DOL starters, and turn the start and stop pushbuttons into drive inputs. Wire the stop button normally closed and the start button normally open to the drive's digital inputs, powered from the drive's own 24 V DC control supply, and take the emergency stop through the drive's safe-torque-off input or its supply contactor. The wiring order, the current arithmetic for the 11 kW motors and the pre-handover checks follow.

Why the DOL starter and the drive cannot share one motor #

A DOL starter is a contactor that switches the motor directly onto the mains, with an overload relay behind it — that relay is the difference between a motor starter and a contactor. A drive feeds the motor from its own inverter stage: it rectifies the supply to DC and synthesizes a variable-voltage, variable-frequency output at its motor terminals. If a line contactor and a drive output both land on one motor, the two sources meet at the motor terminals with nothing between them.

Closing that contactor while the drive is connected puts full line voltage across the drive's output transistors, which can destroy the output stage. The drive also has no influence over a motor fed from the mains, so on the panel door the failure looks like a motor that runs flat out regardless of the speed reference, or a drive that trips and will not reset — a power-circuit fault, not a tuning problem. A drive's fast-switching output also stresses winding insulation differently than a sinusoidal supply, which is why motor makers define inverter-duty insulation for motors bought to run on drives.

The decision: two drives, zero starters #

The drive performs the start function itself: it ramps voltage and frequency up from zero under a current limit, so there is no inrush to suppress and no starter needed to suppress it. Each 11 kW motor gets its own drive, fed from its own branch protection, with the drive output wired straight to the motor.

A drive with a line bypass is the only legitimate way to keep both paths: one contactor between drive and motor, one between supply and motor, interlocked so only one can ever close, plus a changeover selector and its own commissioning. Fit that only when you can name what the process loses with a dead drive. This specification names nothing, so leave the starters out of the panel.

How to wire the pushbuttons to the drive's control terminals #

  1. Lock the panel out and verify absence of voltage at the drive terminals, then wire the control side with the panel dead.
  2. Identify the control-voltage terminals on the terminal card of the drive model you actually have: the 24 V DC supply terminal, its common, and the digital inputs. Terminal numbering differs between drive families, and landing the supply and common swapped is a documented wiring mistake, so follow the card exactly.
  3. Wire the stop pushbutton normally closed, in series in the run-permission loop between the 24 V DC supply and the digital input the drive uses for stop. Pressing it, or a broken wire anywhere in that loop, removes the run command. When the same stop contact also has to land in a controller input, wiring normally closed pushbuttons into controller logic keeps the fail-safe behaviour on both sides.
  4. Wire the start pushbutton normally open to a second digital input for three-wire momentary control, or use a maintained selector for two-wire control. The latching that an auxiliary contact across the start button used to do in the starter now happens inside the drive: set its start and stop mode to momentary or maintained to match the hardware. How the DOL latching circuit holds current through one path shows the scheme the drive replaces.
  5. Assign the digital input functions — run forward, stop, run reverse where needed — from the same manual, since the function names differ between product families.
  6. Connect the speed reference: a potentiometer on the analog setpoint terminals, or a 0-10 V or 4-20 mA signal from a controller, and set the drive's signal-type parameter to match.
  7. Emergency stop: run the e-stop device's normally closed contacts into the drive's safe-torque-off input where it has one. IEC 61800-5-2:2021, the safety-functions standard for adjustable-speed drives, defines safe torque off as cutting the torque-producing power to the motor without opening the drive's main circuit. IEC 60204-1:2016, which covers the electrical equipment of machines, requires an emergency stop to act as a category 0 stop (power cut immediately) or a category 1 stop (ramped to standstill, then power cut) and to work in every operating mode — a ramp commanded through an ordinary digital input meets none of that. Where the drive has no such input, drop its control power or its input contactor instead. Confirm the stop category with the machine's risk assessment, the drive documentation and the authority having jurisdiction.
  8. Use screened motor cable with the screen bonded at both ends per the drive's EMC instructions.

What changes on the power side #

  • Each drive needs its own branch protection, fuse or breaker, sized from the table in that drive's manual for a 380 V supply, not from the motor kW.
  • Nothing goes between the drive output and the motor in a one-drive-one-motor build. The drive's motor-protection function, set to the nameplate full-load current, replaces the starter's overload relay; confirm the function is enabled before handover.
  • An input contactor or isolator is fine for isolation and long shutdowns. Do not cycle it for every start and stop: each close recharges the drive's DC bus, which slows the response and wears the contactor.
  • If an output contactor is required for isolation, interlock it so it can open only after the drive has been inhibited, never under load.
  • Where the supply or the cable run calls for added impedance, choosing a line reactor or a motor reactor for the drive settles which side of the drive it belongs on.
  • Enter the motor nameplate data — voltage, current, frequency, speed — then the acceleration and deceleration ramps and the current limit, all under the parameter names in your drive's manual.

Worked example: full-load current for two 11 kW, 380 V motors at 0.9 power factor #

The inputs come from the machine specification: P = 11 kW per motor, a three-phase supply of V = 380 V line-to-line, a power factor of 0.9, and two motors in one panel. The specification does not say whether the 11 kW is electrical input or shaft output, and motor nameplates rate kW at the shaft.

The rule in words: on a three-phase circuit, line current is the power divided by the product of root three, the line-to-line voltage and the power factor.

The arithmetic:

I = P / (root 3 x V x PF)

I = 11 000 W / (1.732 x 380 V x 0.9)

1.732 x 380 = 658.2

658.2 x 0.9 = 592.3

I = 11 000 / 592.3 = 18.6 A per motor, valid if 11 kW is input power.

Apparent power per motor: S = 11 kW / 0.9 = 12.2 kVA, so both motors at full load draw 2 x 12.2 = 24.4 kVA from the feeder.

The decision: treat 18.6 A as the floor, not the selection value. A shaft-rated 11 kW motor draws more than that because the input must also cover losses, so the nameplate full-load current — not this calculation — sets every choice: the drive is selected so its rated output current is at least the nameplate value, and where the nameplate current exceeds a frame's rated output current, take the next frame up, never the reverse. Cables and branch protection follow the drive manual tables and the governing installation code, and this result is an estimate to be checked against both.

Commissioning checks before handover #

  1. With the panel locked out and verified dead, confirm every termination: each drive input on its own protection, each output straight to its motor, screens bonded at both ends, and no contactor left in the drive-to-motor path.
  2. Energize under your site's electrical-safety procedure and, using a meter rated for the circuit, read all three phase-to-phase pairs at each drive input: all three should show the nominal supply voltage and be balanced.
  3. With the motor cable still disconnected, power one drive alone and confirm it reaches ready with no fault displayed.
  4. Reconnect the motor, enter the nameplate data and enable motor protection. Start at minimum speed and confirm rotation; if it runs backwards, swap any two motor leads at the drive output or change the drive's direction setting — swapping phases at the drive input does nothing, because the drive rectifies them.
  5. Raise the reference and compare the drive's displayed motor current with the nameplate full-load current; in normal operation it sits at or below that value.
  6. Press stop and confirm the motor ramps down on the deceleration ramp.
  7. Press the emergency stop and confirm the drive removes torque regardless of the speed reference, and that resetting it does not restart the motor — a new start command should be required.
  8. With the motor stopped, open the stop-circuit loop at a terminal and confirm a start command is refused. Restore it.
  9. Repeat every check on the second drive and confirm each motor starts and stops independently of the other.

Wiring mistakes that recur on rebuilt panels #

Mistake What the operator sees Fix
Pushbuttons wired through a coil in series with the motor feed Motor runs but the drive never receives a run command, or trips at power-up Move start and stop to the drive control terminals
Input contactor cycled for every start and stop DC bus recharges on every cycle; sluggish starts, contactor wear Start and stop through the drive; contactor for isolation only
Drive chosen on kW alone Overcurrent trip at load Select on rated output current against nameplate full-load current
Unscreened motor cable, or screen bonded at one end only Nuisance trips, analog reference drift Screened cable, screen bonded at both ends
Stop pushbutton normally open Motor keeps running when a control wire breaks Rewire the stop normally closed

Questions asked

Can both 11 kW motors share one drive to save panel space?

No. One drive per motor. The drive holds one set of motor nameplate data and one motor thermal model, and its current limit protects one machine. Two motors on one output lose individual protection, cannot be started separately, and cannot be speed-trimmed independently.

Should the stop pushbutton be normally open or normally closed?

Normally closed. The stop contact sits in the drive's 24 V run-permission loop, so a broken wire, a pulled terminal or a cut cable reads as a stop command and the motor stops. The start button is normally open for the mirror reason: the same faults cannot create a run command on their own.

Where do the emergency stop contacts land if the drive has no safe-torque-off input?

Open the drive's control-power circuit or its input contactor. An emergency stop must remove torque regardless of what the speed reference or a program commands, so it cannot rely on a ramp sent through an ordinary digital input. The button must latch and require a deliberate reset before anything can restart.

The drive trips as soon as the start button is pressed. Where do I look first?

Read the fault code on the drive display and look it up in the fault table for your exact model, because the code names the drive's own diagnosis. Then check the three usual causes on a rebuilt panel: motor-cable faults, nameplate data not yet entered, and output wiring that leaves a contactor in the drive-to-motor path.

Keep reading

  • Selection guide

    Replacing a three-speed lathe motor with a VFD

    Swap in the 3 hp, 230 V motor and drive it with a 230 V single-phase-input VFD, keeping the gearbox and back-gear for torque. But do the ratio arithmetic first: at 75 Hz the new motor turns about 2156 rpm, and on the stock pulleys the spindle tops out near 1600 rpm, so the top speed needs a pulley change, not more frequency.

    Variable frequency drives

  • Selection guide

    Sizing a VFD for a three-phase motor on single-phase input

    On single-phase input, size the drive's continuous output current at no less than twice the motor nameplate full-load amps when the drive's 50% derating applies, and feed it from a branch circuit sized to 125% of the drive's published single-phase input current — never from the ideal wattage estimate. For a 10 hp, 208 V motor that means a drive rated at least 61.6 A output.

    Variable frequency drives

  • Explainer

    Why a capacitor-run motor needs a special VFD

    A standard three-phase VFD will not run a single-phase capacitor motor usefully: the fixed run capacitor's reactance rises as output frequency falls, so the auxiliary winding loses its phase-shifted current and low-speed torque collapses. Use a drive documented for PSC or shaded-pole motors, or change to a three-phase motor.

    Variable frequency drives