Current IntelPower LibraryShop main store

Explainer

What the A2 terminal on an overload relay means

Motors and motor starters Published 6 min read By Current Intel engineering team

Short answer

A2 is standard contactor-coil notation, not an overload contact. When it appears on an overload-mounted assembly, it is the contactor's A2 repeated on a terminal you can reach after the two units are mounted together. Verify that from the assembly diagram and an isolated continuity check, then wire it as the coil connection while the NC trip contact stays in series with the coil circuit.

On this page
  1. A2 means a coil terminal, not an overload contact
  2. Why the coil terminal is repeated on the overload
  3. The trip function lives on the 95-96 contact
  4. Confirming a repeated A2 on a mounted assembly with an isolated continuity check
  5. Wiring the A2 once it is identified
  6. Questions asked

The A2 you see on an overload relay is almost never an overload contact. A2 is the standard marking for one side of the contactor coil, and when it shows up on the overload or its mounting adapter, it is the contactor's A2 repeated on a terminal you can reach after the two units are mounted together. The decision: treat it as the coil connection, confirm that with the assembly diagram and an isolated continuity check, and wire it as the coil terminal it repeats, while the overload's own NC trip contact stays in series with the coil circuit.

A2 means a coil terminal, not an overload contact #

Contactor manufacturers mark the two operating-coil terminals A1 and A2. That pair of markings is about as close to a universal convention as motor control gets, and it identifies the coil, nothing else. A2 is not protective earth, and it does not inherently mean neutral: which conductor belongs there depends on the control supply and the drawn coil circuit, not on the label.

The overload relay does its switching with a different set of markings. Its normally closed trip contact is conventionally numbered 95-96, and that contact belongs in the control path, not the power path. So when you find an A2 marking on an overload assembly, you are not looking at a third overload contact: you are looking at contactor coil notation that has been brought along for the ride.

Why the coil terminal is repeated on the overload #

A thermal overload relay usually mounts directly beneath its contactor, and on many assemblies that mounting puts the contactor's own coil terminals where your screwdriver cannot go once the pair is together. The fix manufacturers use is to repeat the contactor's A2 on the relay body or adapter, where it stays accessible, so you can land the coil wire after mounting.

Understand what that terminal is and is not. It is a connection point, an extension of the contactor's A2. It performs no thermal protection, carries no trip function, and does not set or change the coil voltage. The overload's trip mechanism still operates through its own auxiliary contact; the repeated A2 just gives your wire somewhere to land.

The trip function lives on the 95-96 contact #

In a conventional starter circuit, the overload's normally closed trip contact is wired in series with the contactor coil, typically on the coil side of the control circuit. When the relay trips, that contact opens, the coil de-energizes and the contactor drops out. Wiring the coil circuit correctly through that contact is covered in the article on wiring overload relay contacts to the coil and the PLC.

This is why identifying A2 correctly matters. The repeated A2 and the 95-96 contact sit in the same control circuit but do different jobs: one feeds the coil, the other breaks that feed on a trip. Confusing the two, or substituting one for the other, gives you a starter that either never pulls in or keeps running after the overload trips.

Confirming a repeated A2 on a mounted assembly with an isolated continuity check #

This example works through the check on a typical directly mounted contactor-and-overload pair.

Inputs, with their source:

  • The suspected repeated terminal: the one marked A2 on the overload face, read from its own label.
  • The reference point: the contactor's A2 coil terminal, located on the assembly diagram for your exact contactor, relay and adapter combination. A diagram for a visually similar assembly is not good enough when the terminal arrangement differs.
  • The meter: any decent digital multimeter set to ohms, proven by touching the leads together first.
  • Example readings, to show the arithmetic: leads shorted together read 0.2 ohm, and the two A2 terminals read 0.2 ohm between them.

The rule in words: if the overload's A2 is a plain extension of the contactor's A2, the meter sees copper the whole way, so the terminal-to-terminal reading should equal the meter's own lead resistance. Anything else means you are measuring through a coil, a suppression module, external wiring, or the wrong terminal.

Safety note before you probe: isolate the control supply as well as the power circuit, lock it out, and test for absence of voltage at the terminals. Coil circuits are often fed from a separate control transformer or 24 V DC supply, so a dead power circuit does not mean dead A2 terminals. Disconnect any external wires from both terminals and label them so each one goes back where it came from.

The arithmetic written out:

Terminal-to-terminal reading minus lead-to-lead reading:

0.2 ohm − 0.2 ohm = 0.0 ohm of excess resistance

Result: the path between the two A2 terminals adds nothing beyond the meter's own leads, so it is a direct internal link, and the overload's A2 is the contactor coil connection repeated for access.

The decision, with its threshold: a reading within a fraction of an ohm of the lead-to-lead value confirms a direct extension, so wire that terminal as the contactor's A2. A reading many times higher means the path runs through the coil or a suppression component rather than a plain link; an open reading means the terminal is not an extension at all on your assembly. In both of those cases, stop, read the identity labels on the contactor, relay and adapter, and get the diagram for those exact parts before connecting anything.

Wiring the A2 once it is identified #

With the function confirmed, land the coil wire on the repeated A2 and treat it exactly as the contactor's own A2:

  • Check the coil voltage and supply type against the coil's marked rating and your control supply before energizing; the terminal does not transform anything.
  • If the contactor has a DC coil with built-in suppression, the coil is polarity sensitive: A1 is the positive terminal as marked, so the positive control conductor goes to A1 and the return to A2.
  • Leave the NC 95-96 trip contact in series with the coil circuit so an overload trip still drops the contactor.
  • Use the conductor size, strip length and tightening torque specified for that terminal, with no strands escaped or insulation trapped in the clamp.
  • Restore every wire you disconnected for the check, verified against the drawing, then function-test: give a run command and measure coil voltage at A1 to A2, operate the relay's documented test function, and confirm the contactor releases on trip.

If the continuity check failed, or the diagram assigns a different function to that terminal on your assembly, follow the diagram rather than the marking. The marking tells you the convention; the diagram tells you your device.

Questions asked

Is the A2 terminal on an overload relay a neutral connection?

No. A2 identifies one side of the contactor coil, and the marking says nothing about which control conductor lands there. That depends on the control supply in your schematic: the wire that completes the coil circuit per the drawing goes to A2, whether or not that wire happens to be the grounded side of a control transformer.

Which polarity goes to A1 on a DC coil contactor?

On contactors fitted with DC coils and built-in surge suppression, the coil is polarity sensitive and A1 is the positive terminal as marked on the device. Reverse the two wires and the coil may not pull in correctly. This applies to DC coils only; an AC coil of the same frame does not care which of A1 or A2 is which.

Can the repeated A2 replace the 95-96 trip contact in the control circuit?

No. The repeated A2 is only a connection point for the coil circuit; it carries no trip function. If you feed the coil through it and leave the NC trip contact out, an overload trip will not drop the contactor and the motor keeps running with a tripped relay, which is exactly the failure thermal protection exists to prevent.

The continuity check between the two A2 terminals reads open. What now?

First rule out the meter and the setup: correct range, leads proven on a known short, probes on clean terminal metal, external wires disconnected. If it still reads open, the terminal on your assembly is not a plain extension of the contactor coil A2. Read the identity labels on the contactor, the relay and any adapter, get the diagram for those exact units, and follow what it assigns to that terminal.

Keep reading

  • How-to

    Wiring overload relay contacts to the coil and the PLC

    The overload relay's NC trip contact (95-96) belongs in series with the contactor coil so a trip drops the motor out even while the PLC still commands run; the NO auxiliary (97-98) is a separate status input to the PLC. A PLC input is not overload protection, because no general-purpose controller input is a listed motor overload device, so a panel wired the other way needs rewiring.

    Motors and motor starters

  • How-to

    Identifying terminals on an old star-delta starter panel

    A1 and A2 are the contactor coil terminals, and the coil's labeled voltage must sit within the 85 to 110 percent band IEC 60947-4-1 requires against the control supply. NO only means a contact is open at rest; its traced wiring decides whether it is a start or holding contact. With the panel locked out and verified dead, tracing the six motor leads through the contactors is what proves a star-delta scheme.

    Motors and motor starters

  • Troubleshooting

    Why neutral-side switching trips a smart DOL starter

    Move the direction changeover contactor to the line side so the starter feeds the selected winding directly, and leave the run capacitor between the CW and CCW terminals: in the tested 110 V, 2.6 A circuit that raised successful starts from about 1 in 20 to 19 in 20. Return-side switching lets capacitor charging current through the unselected winding distort the current the starter measures at closure, so its residual-current diagnostic reports a missing path.

    Motors and motor starters