Motors and motor starters Published 7 min read By Current Intel engineering team

Short answer

Yes, one soft starter can start several motors, but only as NFPA 70, the NEC, 2023 edition, Section 430.87 permits: each motor keeps its own running overload protection, the branch contactors open and close only while the starter's output is at zero, and the permitted starts per hour is one thermal budget shared by every motor on its output. One starter per motor remains the default design.

On this page
  1. Can one soft starter start several motors?
  2. What must the wiring include before the first motor is connected?
  3. Which mode fits the loads: parallel or sequential?
  4. How do the contactors switch without switching load?
  5. How many motors can share the starter's start budget?
  6. What decides whether the shared starter is the right design?
  7. Questions asked

One soft starter can start two or more motors, and the NEC states that permission outright: NFPA 70, the National Electrical Code, 2023 edition, allows more than one motor on a single motor controller when every motor on it keeps its own running overcurrent protection. It is an exception design, not the default. Making it correct takes the three things quick proposals skip: a separate overload relay per motor, contactors that only switch at zero output, and one shared starts-per-hour budget.

Can one soft starter start several motors? #

Yes, two or more motors can share one soft starter, and where the NEC governs the permission is explicit: NFPA 70, the National Electrical Code, 2023 edition, Section 430.87 permits two or more motors on one motor controller when each motor has its own running overcurrent protection. Section 430.87 is the clause that covers this arrangement, and its condition does the engineering work: individual running overcurrent protection on every motor. Article 430 also carries the rest of the installation. Section 430.53 covers several motors on one branch circuit, and Section 430.22 governs the conductors from the controller to each motor. Editions and local amendments differ, so confirm the sections your jurisdiction enforces with the authority having jurisdiction, and confirm the starter's own ratings against its documentation.

What must the wiring include before the first motor is connected? #

Each motor needs its own branch through an output contactor and its own overload relay, with short-circuit and ground-fault protection ahead of the starter, because the starter's built-in motor protection models a single thermal image and cannot watch several motors at once. Before any panel is opened: de-energize the feeder, lock it out, and verify absence of voltage at the starter terminals using the method your electrical safety program and NFPA 70E, 2024 edition, define for that panel.

The power path then reads, in order:

  • A short-circuit and ground-fault protective device ahead of the starter, sized by the several-motors rules of Article 430 rather than for a single motor.
  • The starter output onto a common bus feeding each branch.
  • In every branch, an output contactor, then an overload relay set to that motor's nameplate full-load current, then the motor.
  • In sequential mode, a bypass contactor per motor from the line side around the starter to that branch's overload relay, interlocked against its own output contactor so the two can never close together.

Worked example, with illustrative inputs: three nameplates on one 460 V, three-phase, 60 Hz feeder, carrying full-load currents of 40 A, 27 A and 20 A. Section 430.53 sizes the branch conductors at the sum of the motor currents plus 25 % of the largest: 40 A + 27 A + 20 A = 87 A, and 87 A + (0.25 × 40 A) = 97 A. The minimum conductor ampacity is therefore 97 A before ambient or termination corrections; treat that as an estimate and check it against the code edition that governs the job. The same several-motor arithmetic one level up is worked through in the guide to sizing the feeder breaker for three motors on one 208 V feeder.

Each overload relay also gets its own trip class matched to that motor's ramp time, not to the group; the article on reading overload relay trip classes and curves shows how the class maps onto the ramp.

Which mode fits the loads: parallel or sequential? #

Sequential starting fits unequal motors and keeps each motor serviceable; parallel starting only suits matched motors on one shared voltage ramp, because a lighter motor reaches speed while the heavier one still draws starting current. The two modes place the load on the starter very differently:

Parallel Sequential
Starter current rating covers the combined current of all motors during the ramp covers the largest motor alone
Ramp settings one ramp for the whole group one ramp per motor, selected by the sequence
Contactors per motor one output contactor output plus bypass
State after start still soft-starter fed across the line through the bypass
Start budget use one heavy shared ramp several ramps in quick succession

For sequential mode, the starter's rated current must cover the largest motor's ramp, the same matching exercise described in the article on matching a soft starter current range to its power structure. How each ramp should behave is a per-load question, and the article on which soft starter control mode fits each load type sorts the ramp style by load before you decide which motors a single starter can serve.

How do the contactors switch without switching load? #

A branch contactor may close or open only while the soft starter's output is at zero; a contactor that interrupts under a gating output breaks ramp current its rating was never based on, and a bypass contactor closing onto a gating output shorts the thyristors. The sequence that respects that limit runs as follows:

  1. Select motor n: close its output contactor with the starter output off and the bus at zero volts.
  2. Confirm the auxiliary-contact feedback from that output contactor.
  3. Issue the start command to the soft starter.
  4. Wait for the end-of-ramp or up-to-speed signal.
  5. Close that motor's bypass contactor.
  6. Stop the soft starter, bringing its output to zero.
  7. Open the output contactor, now carrying no load.
  8. Release the starter for the next motor and repeat.

Steps 5 to 7 are the handover that decides whether the contactors survive: bypass closed first, starter output off second, output contactor opened last and unloaded. Drive the whole sequence from the control logic with per-step feedback and a timeout, so a welded or stuck contactor halts the sequence instead of passing a start command onto an unselected branch. Each motor's own ramp still has to break its load away, the same initial-voltage question covered in the article on soft starter start voltage and breakaway torque.

How many motors can share the starter's start budget? #

The starter's permitted starts per hour is a single thermal budget for the whole output, published in its manual for the load class and ramp time, and every ramp on every motor spends it; a three-motor sequential start uses three starts, not one. The thyristors dissipate the ramp energy, and in a bypassed starter they only rest and cool while the motors run at speed, so back-to-back sequential ramps stack heat into one thermal image. The application checks are the ones any soft-starter application note lists for sequential duty: each motor's starting current requirement and starting time requirement, checked against the starter's own data for that load class.

Worked example, illustrative again: a manual that permits 4 starts per hour at a 30-second ramp for this load class. Three motors started once each per hour spend 3 of those 4; one restart after a trip spends the fourth, and the group waits for the budget to recover. If restarts after a voltage dip would line every motor up behind one starter, add staggered restart delays so the starter is never asked for a thermal trip it has not recovered from. Log the starter's thermal state, where it reports one, after a full start sequence and again after a second sequence at the minimum planned interval.

What decides whether the shared starter is the right design? #

Build the shared starter only when the process tolerates the whole group losing its starting together and the contactor set still costs less than the starters it replaces; build one starter per motor when any single start failure stops production. The failure math is fixed: the starter is one point of failure for starting every motor on its output, and each added contactor is one more device that can fail on one branch. Where speed control is wanted anyway, a drive per motor removes the contactor set, the handover sequence and the shared start budget at once, and the comparison is no longer close. Where the motors are large, few and non-critical, the shared starter remains a legitimate exception design, built exactly as Section 430.87, the branch rules and the starter's own ratings require.

Questions asked

Does the soft starter's built-in motor protection watch every motor sharing it?

No. The electronic protection inside a soft starter models one thermal image, so it can only represent a single motor. With several motors on the output, the starter's own protection stays set for the largest motor's ramp, and each branch keeps its own overload relay set to that motor's nameplate full-load current.

Can one motor be serviced without stopping the others?

Only in sequential mode with per-motor bypass contactors. A ramped motor runs across the line through its bypass, which frees the starter for the next motor, and that motor's branch isolator can be opened while the rest keep running. In parallel mode, opening any branch usually means taking the shared starter and the whole group out of service.

What fails first if the shared soft starter dies?

Starting, not running. Motors already fed through closed bypass contactors keep turning across the line, but no motor on the starter can be started or restarted until the starter is repaired or replaced. Get operations to accept that failure impact in writing before the one-starter design is built.

How is the starter itself sized in sequential mode?

For the largest motor on its output, not the sum of all of them, because only one motor is connected during any single ramp. The conductors and the branch-circuit protection, though, are sized for all motors together under the several-motors rules of Article 430, so the starter and the circuit are sized on different bases.

Keep reading

  • Troubleshooting

    Diagnosing a soft starter fault or alarm before resetting it

    Record the exact fault or alarm text, the values shown with it, and whether it appeared during start, run, or stop, before you reset, because a reset clears the diagnostic context. Then check the supply, the starter's documented ratings, the configured motor data, and the load: most trips trace to one of those four, not to a failed starter.

    Motors and motor starters

  • How-to

    Setting a soft starter current limit without overheating the motor

    Set the soft starter current limit from the accelerating torque the load needs, not from the starter's duty figure. Estimate the limit as locked-rotor current times the square root of required torque over locked-rotor torque, check that current, dwell time and starts per hour against the starter's duty table, then verify every start with a measured peak current and acceleration time. At a 300% limit a typical design B motor develops only about a third of its full-load torque.

    Motors and motor starters

  • Explainer

    Why a single-phase motor soft start ramps voltage, not frequency

    A single-phase soft starter is an SCR voltage controller: it reduces the effective voltage during the ramp while the supply frequency stays at 60 Hz. Because the start capacitor's reactance depends on frequency, not voltage, the auxiliary winding keeps working and torque falls with the square of voltage, not with frequency.