Protection: breakers, fuses and SCCR Published 6 min read By Current Intel engineering team

Short answer

A motor protection relay does not calculate the heating, starting and cooling time constants of its thermal replica; it takes them as settings and applies them to the measured current. Take them from the motor manufacturer's datasheet, thermal limit curves or heat-run report, and derive them only when the manufacturer states nothing.

On this page
  1. How the relay uses the three constants
  2. Worked example: tau 2 from the cold locked-rotor time
  3. Check the datasheet first
  4. Enter and verify the settings
  5. Confirm each constant by injection
  6. If trips still disagree with the motor data
  7. Questions asked

The heating, starting and cooling time constants of a motor thermal replica are not values the relay calculates. They are settings: the relay applies them, with the measured currents, inside a first-order thermal model, and the motor designer owns the physics behind them. So the answer is to take the three constants from the motor manufacturer's documentation, and derive them yourself only when the datasheet states nothing, working from that motor's own locked-rotor times, overload curve or heat-run report.

How the relay uses the three constants #

A current-based thermal replica estimates the motor's thermal state from the equivalent heating current and the thermal reference current. The state sits between 0 percent (cold) and 100 percent (trip threshold), and each motor state has its own time constant because the heat flow paths differ:

  1. The running constant, tau 1, describes whole-machine heat storage versus dissipation with the cooling fan at speed.
  2. The starting constant, tau 2, describes rotor and stator heating at high current with little cooling airflow.
  3. The cooling constant, tau 3, describes heat leaving the machine after shutdown or at standstill.

The model's trip time from an initial state depends logarithmically on the constants, so a wrong constant shifts every trip time, not just one. Treat any manufacturer-stated constant as authoritative: a value you derive from a curve is a fallback and must never override a stated number.

Worked example: tau 2 from the cold locked-rotor time #

The starting constant comes from the cold stall data. This example uses illustrative inputs typical of a medium induction motor; take your own values from the motor's datasheet.

Inputs:

  • Cold locked-rotor withstand time: 25 s (from the motor datasheet stall data)
  • Locked-rotor current: 6 times the rated current (from the same datasheet)
  • Thermal reference current: the motor rated current, so the locked-rotor condition gives a final thermal state of 6 squared = 36

Rule: from cold, the replica reaches trip in t = tau times the natural logarithm of the final state divided by (final state minus 1).

Arithmetic: the logarithm term is ln(36/35) = ln(1.0286) = 0.02817. So 25 s = tau 2 times 0.02817, which gives tau 2 = 25 / 0.02817 = 888 s, about 14.8 minutes.

Decision: enter 888 s as the starting constant, in the unit the relay setting expects. If the datasheet also gives a hot stall time, back-calculate the initial thermal state it assumes and compare; a large disagreement means the curves do not follow a single-exponential model, and you should ask the manufacturer rather than force a fit.

The same equation derives the running constant from one point on the motor's overload curve (a current multiple and the stated trip time from a known initial load), and the cooling constant from a cooling curve: the time at which the temperature rise falls to 36.8 percent of its value at shutdown is tau 3 directly.

Check the datasheet first #

  1. Read the motor datasheet or the manufacturer's protection data sheet for the heating, starting and cooling time constants. If all three are listed, enter them directly and skip the derivations. If some are listed, take them and derive the rest.
  2. If no constants are listed, look for the locked-rotor current, the cold and hot stall withstand times, and any overload curve of time against multiples of rated current. These are the inputs the worked example above needs.
  3. If neither exists, look for a heat-run or type-test report. Temperature rise against time under constant load gives the running constant: the time at which the rise reaches 63.2 percent of its final value. The post-shutdown cooling trace gives the cooling constant the same way.
  4. If the manufacturer states nothing at all, request the three constants or the limit curves. Do not enter typical values copied from another motor, cable or transformer; the settings would describe a different machine and either trip on normal starts or fail to trip on a real overload. Record the source document and revision beside the settings in the commissioning file.

For how these withstand times relate to trip classes and overload curves, the trip class readings on an overload relay cover the same withstand logic from the relay side. IEC 60034 parts 1, 11 and 29 describe how machines are rated and thermally tested; verify the clauses in the current editions with your motor manufacturer.

Enter and verify the settings #

  1. Set the thermal reference current to the value the manufacturer's curves use, normally the rated current, because every derivation above assumed it.
  2. Enter all three constants with the correct unit, even where starting or cooling behaviour seems minor, so no value stays at a factory default. A seconds-versus-minutes mismatch shifts the model by a factor of 60.
  3. Set any thermal alarm threshold below the 100 percent trip threshold, within the relay manual's setting range.
  4. Check the remaining thermal-function settings against the motor data, including any negative-sequence weighting of the equivalent current, because each one shifts every trip time.
  5. Read from the relay manual whether the thermal state survives a power cycle; it determines the starting point for the checks below.

Confirm each constant by injection #

One safety note before you open the relay panel or the switchgear cubicle: de-energize the circuit, lock out, and test for absence of voltage before touching anything inside.

With the relay isolated from the process and fed from a secondary injection test set:

  1. Reset or record the thermal state. From cold it should read 0 percent; if the relay retains state, use the reading as the initial value in the equations.
  2. Inject a steady 2 times the reference current in the running state. The final state is 4, so the expected trip time is tau 1 times ln(4/3), which is 0.288 times tau 1. Compare the measured time with the relay's accuracy specification.
  3. For the starting constant, inject the locked-rotor multiple from cold and compare the trip time against the datasheet stall time that produced tau 2.
  4. For the cooling constant, trip the replica, remove the current, and time the decay of the thermal state; the time to fall to 36.8 percent of the tripped value is tau 3.

Take the allowed deviation from the relay's own accuracy datasheet, not from a rule of thumb.

If trips still disagree with the motor data #

Read the relay's event and trip history before changing settings, and compare the recorded trip time and pre-trip thermal state with your calculated values. A trip during a normal start usually points to the starting constant set too short, the reference current set too low, or residual heat from a prior run modelled with a cooling constant that is too short. Trip times far later than the overload curve point to a running constant set too long, most often a unit error. A restart blocked far longer than the machine's real cool-down points to the cooling constant set too long. Fix the setting that the arithmetic names, re-inject, and record the result.

Questions asked

Can I copy thermal time constants from a similar motor of the same frame size?

No. The constants describe one machine's heat storage and heat dissipation, and they vary with rotor construction, cooling method and rating even within one frame size. Settings copied from another machine either trip on normal starts or let a real overload run past the withstand time. Request the values from the motor manufacturer, or derive them from that motor's own limit curves or heat-run data.

Why is the cooling time constant usually longer than the running one?

A self-ventilated motor loses its fan airflow at standstill, so heat leaves the machine more slowly after shutdown than it is carried away at speed. The cooling constant is therefore normally longer than the running constant. If a heat-run report gives equal values for both, ask the manufacturer to confirm before entering them.

What happens if I enter a time constant in minutes when the relay expects seconds?

The model runs sixty times slower than intended. Trip times come out sixty times longer than the motor's withstand times, so the relay fails to protect a stall or a locked rotor. Read the unit and range of each setting in the relay manual before entry, and confirm the entered values with a secondary injection test.

Does the relay keep the thermal state through a power cycle?

That depends on the relay model and firmware, and you should read it from the manufacturer's manual before commissioning. If the state resets to cold on power-up, a hot motor that trips and is then re-energized starts the replica from zero percent even though the real machine still holds heat, which shortens the apparent margin. Record the behaviour in the commissioning file.

Keep reading

  • Explainer

    Why an ANSI 79 reclosing relay does not belong on a motor circuit

    An ANSI 79 reclosing relay is built for distribution feeders, not motor circuits. Reconnecting a still-spinning motor while its residual voltage is out of phase with the bus produces a transient torque spike that can break shafts and couplings. Fix dip trips with control-power ride-through and a restart permissive that waits for the residual voltage to decay.

    Protection: breakers, fuses and SCCR

  • Explainer

    Fire pump motor protection under NEC Article 695

    NFPA 70 (NEC) Article 695 protects the water, not the motor: the fire pump's supply device must hold locked-rotor current indefinitely — the sum of the pump and jockey pump locked-rotor currents, or six times the single motor's rated current, whichever is greater. Overload, unbalance and phase-loss functions alarm instead of tripping, and the weekly churn test stays attended so an abnormal start is stopped by hand.

    Protection: breakers, fuses and SCCR

  • How-to

    Sizing the feeder breaker for three motors on one 208 V feeder

    NFPA 70, National Electrical Code, 2023 edition, Article 430.62 sizes a multiple-motor feeder breaker as the largest motor branch short-circuit device rating plus the table full-load currents of the remaining motors. For three 5 hp, 208 V three-phase motors on 45 A branch breakers that is 45 A + 33.4 A = 78.4 A, so the feeder takes an 80 A inverse-time breaker. The 2.5 × total running-current shortcut gives 101.5 A and over-sizes the feeder.

    Protection: breakers, fuses and SCCR