Current IntelPower LibraryShop main store

Explainer

Why an ANSI 79 reclosing relay does not belong on a motor circuit

Protection: breakers, fuses and SCCR Published 6 min read

Short answer

An ANSI 79 reclosing relay is built for distribution feeders, not motor circuits. Reconnecting a still-spinning motor while its residual voltage is out of phase with the bus produces a transient torque spike that can break shafts and couplings. Fix dip trips with control-power ride-through and a restart permissive that waits for the residual voltage to decay.

On this page
  1. What device 79 is for
  2. What happens when you reclose a spinning motor
  3. Find what actually drops out
  4. The fix: ride through the dip, never reclose into it
  5. Worked example: sizing the control-power ride-through
  6. The decision
  7. Questions asked

A motor that trips during a short-circuit dip has lost its contactor hold-in or its protection element for a few cycles to a few seconds, and an ANSI 79 reclosing relay does not fix that. Device 79 controls the automatic reclosing and locking out of an AC circuit interrupter; it is designed for feeder reclosing practice after a transient fault clears. Applied to a motor feeder it does nothing during the dip, then reconnects a machine that is still spinning with a residual voltage out of phase with the bus, and the resulting air-gap torque transient can bend or break shafts, shear keys and destroy couplings. The working fix is ride-through on the contactor's control power plus a restart permissive that waits for the residual voltage to decay.

What device 79 is for #

Device 79 is one of the ANSI/IEEE device function numbers: the 79 function is the AC reclosing relay that controls automatic reclosing of an interrupter after it has tripped. Its natural home is an overhead distribution feeder, where the large majority of faults are transient, a brief dead time lets the arc de-ionize, and the load is passive. A motor is not a passive load. It is a rotating source that keeps generating voltage at its terminals after the supply disappears, and reclosing practice built for feeders ignores exactly that.

What happens when you reclose a spinning motor #

When the supply is lost, an induction or synchronous motor keeps a decaying residual voltage on its terminals, with frequency and phase drifting away from the system as the rotor slows. If the interrupter closes while that residual voltage is significantly out of phase with the incoming bus, the stator current and air-gap torque spike. The torque can be positive or negative depending on the phase angle at the instant of closing, and IEEE work on limiting induction motor transient shaft torques identifies the momentary source discontinuity and re-energization transient as the damaging case. A fast reclose leaves the least time for the residual voltage to decay, so it is the worst case, not the best.

Field damage from wrong-phase reconnection includes bent or broken shafts, sheared keys in keyways, failed couplings and stators rotating in their housings. The severity grows with machine size. The quantity that decides whether a reclose is safe is the magnitude and phase angle of the residual voltage at the instant of closing, never the dead time printed on the relay.

Find what actually drops out #

Before choosing any fix, separate the two ways a motor disappears during a dip. Record the dip at the motor control center and at the control-power transformer secondary, then compare against the device limits.

Observation Likely cause Where to read it
Contactor drops or chatters, no relay trip Coil voltage below the contactor's drop-out level during the dip Recorder on the coil supply; the contactor datasheet's drop-out voltage
Protection relay trips on undervoltage Undervoltage pickup and delay set tighter than the dip Relay event record and the undervoltage settings
Drive or soft starter faults on supply loss Its own bus undervoltage threshold Device fault history and undervoltage parameters

The mismatch between the measured dip depth and duration and the drop-out voltage or relay delay is the whole problem. Where the failing device is a drive, read its own event history and its fault table for the named model to learn which threshold tripped before you touch anything else.

The fix: ride through the dip, never reclose into it #

If the contactor coil is dropping out, hold only the control circuit up. A UPS or a dip-stabilizing device on the control power carries a few hundred volt-amperes, not the motor load, so it is a small unit. This is the same control-power thinking as keeping a control transformer secondary grounded or floating correctly in an MCC, covered in grounded versus floating control transformer secondaries in MCCs. If the protection relay is tripping, set its undervoltage pickup and time delay against the measured dip so it rides through dips the process tolerates and still trips on sustained loss.

Where automatic restart is wanted, block the instantaneous reclose and add a permissive that permits closing only after the residual voltage has decayed, or use a sequenced restart with staggered delays so large motors do not reaccelerate together on voltage return. If you add control-power ride-through, treat the UPS as a single point of failure: monitor its status and define the motor's safe state when it fails.

One safety note: any work inside the MCC or at the control-power transformer starts with de-energizing and verifying absence of voltage under NFPA 70E, 2024 edition; confirm the lockout and PPE requirements with your authority having jurisdiction before opening anything.

Worked example: sizing the control-power ride-through #

Inputs for this illustrative example: a 75 kW, 460 V, three-phase induction motor on a contactor starter, a control-power transformer secondary at 120 V, 50 VA of coil and relay load, and a recorded dip of 30 % residual voltage lasting 0.5 s.

The contactor datasheet gives a drop-out voltage, for example 65 % of rated coil voltage; check your own contactor's number. During the dip the coil sees 30 % of 120 V, which is 36 V, well under that 78 V drop-out threshold, so the contactor opens and the symptom is explained.

Ride-through device sizing: 50 VA of control load with margin for inrush on relays, say 2 times, gives 100 VA. A 250 VA ride-through unit covers it with room for a second starter's coil. Nothing here carries the 75 kW motor; the motor simply drops and restarts under the permissive.

Restart permissive: set the closing permissive to block until the residual voltage at the motor terminals has decayed below a small fraction of rated voltage and its phase relationship with the bus is acceptable per the machine data. On an induction machine this decay follows the open-circuit time constant, typically on the order of one to several seconds; size the delay from the motor's own data and prove it by test, not by dead time.

Verify the whole scheme by reproducing the dip with the recorder still connected: the coil voltage stays above hold-in for the full 0.5 s, the relay event log shows no undervoltage trip inside the ride-through window, the interrupter cannot close before the permissive clears, and removing the ride-through device's input in turn ends in a lockout, never a reclose.

The decision #

Never install a device 79 reclosing relay on a motor feeder; use a reclosing lockout there instead. If the contactor drops out, put ride-through on the control power at a few hundred volt-amperes. If the relay trips, match the undervoltage pickup and delay to the measured dip. If restart after an interruption is required, permit it only after the residual voltage has decayed, verified by test. That combination keeps the motor in service through short dips and keeps the shafts intact through the long ones.

Questions asked

How do I stop a motor contactor from dropping out during a voltage dip?

Hold the coil supply above the contactor's documented drop-out voltage for the full dip duration. A UPS or a dip-stabilizing device sized for the coil load, typically a few hundred volt-amperes, does this. Confirm the result with a recorder on the coil circuit during a real or reproduced dip, not on paper.

How long should a motor wait before restart after an interruption?

Long enough for the residual voltage at the motor terminals to decay to a level where the phase difference with the incoming bus cannot produce damaging torque. On most induction machines the open-circuit time constant puts this in the range of one to several seconds; size the delay from the machine's own data and verify the permissive by test.

What is the ANSI 79 device function, in one sentence?

Device 79 controls the automatic reclosing and locking out of an AC circuit interrupter after a trip, as a timed sequence intended for feeder reclosing practice.

Is a UPS on the motor power circuit a good alternative?

No. A UPS carrying motor starting and running current is large and expensive, and it becomes a single point of failure for the motor. Support the contactor coil and control circuit only, and let the motor restart under a permissive after the interruption.

Keep reading

  • How-to

    Sizing the feeder breaker for three motors on one 208 V feeder

    NFPA 70, National Electrical Code, 2023 edition, Article 430.62 sizes a multiple-motor feeder breaker as the largest motor branch short-circuit device rating plus the table full-load currents of the remaining motors. For three 5 hp, 208 V three-phase motors on 45 A branch breakers that is 45 A + 33.4 A = 78.4 A, so the feeder takes an 80 A inverse-time breaker. The 2.5 × total running-current shortcut gives 101.5 A and over-sizes the feeder.

    Protection: breakers, fuses and SCCR

  • Selection guide

    Using a motor circuit breaker on a servo infeed

    Yes — a GV2ME-class manual motor controller is acceptable on a servo drive infeed when the drive manual lists that device class for short-circuit protection, its short-circuit rating at the panel voltage exceeds the available fault current, and its thermal dial is set to the drive's rated input current. A UL 1077 supplementary protector alone is never the branch-circuit protective device under NFPA 79 or the NEC; replace each one with a UL 489 breaker, a listed fuse, or an approved motor circuit breaker.

    Electrical safety and codes

  • Explainer

    Why a 50:5 zero-sequence CT fits an 800 A motor

    Keep the 50:5 zero-sequence CT. Balanced phase currents cancel in the window, so the ratio never follows the 800 A motor full-load current; it follows the ground-fault current the 25 A resistor permits, the relay's secondary pickup, and the practical floor for a window-type CT, which sits near 50:5.

    Protection: breakers, fuses and SCCR