Explainer
Which VFD feedback tag actually shows motor output current
Short answer
Motor output current reaches your display only through the drive's network feedback: select the output-current parameter in the Module Definition's Input Data, confirm the raw controller member against the drive's keypad at a steady load, then scale once into a floating-point tag. The reference motor's divide-by-100 is a hypothesis until that comparison passes.

On this page
- The tag lives in the drive's input data, not on the display
- Selecting output current in Module Definition
- Prove the raw member before you scale it
- Worked example: verifying the divisor at a steady 44.7 A load
- Three ways the displayed amperes come out wrong
- Bind the display to the scaled tag
- Questions asked
The tag that shows motor output current is picked at the drive, not on the screen. On a PowerFlex 525 controlled over EtherNet/IP, output current reaches the controller only after you select it as one of the drive's Input Data feedback values — up to four additional selections in the drive's Module Definition — and it arrives as a raw integer count that you scale once into a floating-point controller tag. The previous motor's K_9000_hmi_current tag is a map of that path, not proof that the new drive feeds it: select the feedback, watch the raw member move against the drive's own keypad reading, apply the divide by 100 only after that comparison passes, and bind the display to the scaled tag. Work offline for the definition change, because the download drops the drive's I/O connection.
The tag lives in the drive's input data, not on the display #
A display object has no private wire to the drive. It reads a controller tag, and that tag updates only from the drive's network input connection — an input image that carries the drive's logic status plus whatever feedback values you have assigned to the selectable slots. If nobody ever assigned an output-current parameter to one of those slots, no screen can conjure the number.
K_9000_hmi_current is the destination of a path someone already built on the reference motor. Cross-reference that tag in the controller project, find the instruction that writes it, and identify the raw drive member that instruction reads. That chain — drive input member, one scaling instruction, one controller tag — is exactly what you rebuild for the new motor; the tag name itself carries no drive data, and copying it copies nothing. Identifying a different drive member over the same network is a different job: which drive value is the live DC bus voltage over EtherNet/IP walks through that separate status value, and it will not tell you whether current feedback is selected.
Selecting output current in Module Definition #
In the controller organizer, open the drive module's properties and press Change under Module Definition on the first tab. That window is where you assign a drive parameter to each Input Data and Output Data slot — the datalinks the Embedded EtherNet/IP Adapter user manual, 520COM-UM001B-EN-E, documents for this drive. In Input Data, assign the parameter that reports output current to a free feedback slot: the definition allows up to 4 additional input feedback values, so record every selection existing logic already reads and keep them intact. Output Data carries commands, not feedback — it also allows up to 4 additional output command values, but a current indication needs no command slot, so leave Output Data unchanged unless the new station must write something new.
Because this edits the module definition rather than a screen, expect to make the change offline and download the controller project. The download drops and rebuilds the drive's I/O connection, which can stop the drive under load: stop the agitator first, apply lockout, and verify absence of voltage before anyone opens a terminal cover, then download and watch the connection return to healthy.
| What you touch | Where it lives | Acceptance check |
|---|---|---|
| Input Data feedback slots | Module Definition, drive module properties | output-current parameter assigned; every earlier selection still present |
| Output Data command slots | the same window | unchanged unless the new station issues a new command |
| Definition change and download | the controller project | edit saved offline, project downloaded, I/O connection healthy again |
Prove the raw member before you scale it #
With the download complete and the connection healthy, expand the drive module's input structure in the controller and find the member the new slot created. Run the agitator at a steady, repeatable load and watch that member online beside the drive's keypad current indication. A configured module can exist while its connection is faulted or inhibited, and in that state the member freezes at its last update while the screen still looks alive — confirm the module's connection status, not just the tag's existence, before treating anything on screen as a live measurement. If you want a second instrument behind the keypad number, pick one that reads a drive's output waveform honestly; measuring VFD and soft starter current with the right meter covers that choice. Only when the raw member tracks the keypad do you have a number worth scaling.
Worked example: verifying the divisor at a steady 44.7 A load #
Inputs, all from the agitator drive itself:
- Drive: the agitator's PowerFlex 525, output-current feedback selected as above, I/O connection healthy.
- Load: steady mixing speed, no acceleration or deceleration during the comparison.
- Raw input member: 4470 integer counts, read online in the controller (example reading).
- Keypad indication at the same moment: 44.7 A (example reading; this keypad resolves tenths of an ampere).
- Candidate divisor: 100, carried over from the reference motor's implementation, where the feedback was divided by 100 before it reached
K_9000_hmi_current.
The rule in words: engineering amperes equal the raw count multiplied by the feedback's resolution in amperes per count, so a candidate divisor stands only when its result reproduces an independent reading of the same current — here, the drive's own keypad.
The arithmetic: 4470 counts ÷ 100 = 44.70 A, against a keypad showing 44.7 A at the same load.
Result: the two agree inside the keypad's 0.1 A display step, so the divisor 100 is confirmed for this member on this drive.
Decision: enter one floating-point calculation — scaled tag equals the raw member divided by 100 — and point the display at that tag. Had the member read 447 counts against that same keypad value, the resolution would be 0.1 A per count and the divisor 10; any other mismatch means the resolution is not what the reference motor used, so read it from the drive's parameter documentation before writing any scaling at all.
Three ways the displayed amperes come out wrong #
- Scaling twice. The controller tag already holds engineering amperes; if the display object applies its own scaling or expression on top, the screen shows a hundredth of the real current. Scale once, at the controller, and give the screen object none.
- Integer arithmetic. The same conversion done in integer types truncates the fraction: on the example numbers it would flatten the result to 44 A, and the seven-tenths of an ampere that matters at part load never reaches the screen. Declare the scaled tag as a floating-point type so the fraction survives.
- The wrong member. A feedback slot that actually carries speed or another status value tracks the shaft, not the load, and a slot carrying an input-side value is not motor current either: on a VFD, the current drawn from the line and the current delivered to the motor differ, as why VFD input current can be higher than output current explains. Match the member against the parameter you assigned before you scale anything.
Bind the display to the scaled tag #
Point the agitator's display object at the scaled floating-point tag through the application's controller connection; where the application keeps an intermediate HMI tag, set its controller address first. Give the object amperes as its units, one decimal place to match the keypad's display step, and no scaling or expression of its own. Then repeat the keypad comparison once from the screen: the whole path — feedback slot, raw member, one scaling step, display object — is proven only when screen and keypad agree at the steady load. If the agitator's local station is a single unit beside the drive with the computer and screen built together, that hardware kind is an industrial panel PC, and it reads this same scaled tag with nothing about the path changed.
Questions asked
We reach the drive through a gateway instead of the embedded network card — do the same members apply?
No. The controller then sees the gateway's register map, not the adapter's input image, so member names and addresses differ. One gateway technote for these drives maps the input registers, logic status plus the selected feedback values, from byte 4000 onward in its own map. Check your gateway's documented register layout before reusing any member name or address from this procedure.
Is every value on this drive scaled the same way?
No, each network value carries its own documented resolution, and one is already published for this drive series: the speed reference uses 0.01 scaling, so writing 6000 commands 60.00 Hz. Treat every feedback and command slot the way this article treats current: read the scaling from the parameter documentation or prove it against the keypad before trusting the number.
Does the drive's hardwired analog wiring change any of this?
The network members and the analog terminals are separate paths with separate documentation. This drive provides two analog inputs, one unipolar and one bipolar, jumper-selectable for 0-10 V or 0-20 mA. Anything wired to those terminals follows the analog section of the drive manual, and none of the network scaling shown here applies to it.
The screen shows a plausible current that never changes — what does that mean?
A frozen but plausible value usually means the drive's I/O connection is faulted or inhibited: the module still exists in the project and the display keeps showing the last update. A faulted connection reports itself in the controller organizer and retries once the fault clears; an inhibited module stays silent until someone re-enables it. Restore the connection before treating any stored value as live.