Selection guide
Choosing a 480 V or 240 V supply for a 7.5 hp motor on a VFD
Short answer
Stay at 480 V unless the motor nameplate offers a 230 V connection and no future machine needs the higher voltage. Going to 240 V doubles the drive's input current, so the input conductors, fuses and disconnect are rebuilt at 125% of the drive's rated input current, while the rotary converter's loading is unchanged. Choose the drive by rated output current against the motor nameplate: for a 7.5 hp motor the 10 hp frame is the buy unless its datasheet says otherwise.

On this page
- The motor nameplate decides before the supply does
- What doubles and what does not
- The two options side by side
- Horsepower is the screen, current is the verdict
- Working the 7.5 hp case at the lower input voltage on the 10 hp frame
- Rewiring to the lower voltage, in order
- The decision for your bench
- Questions asked
Go to 240 V only if the motor nameplate offers a 230 V connection and no future machine will need the higher voltage; otherwise stay at 480 V through your 45 kVA transformer. Halving the voltage doubles the current in the drive's input circuit, so its conductors, fuses and disconnect are sized again at 125% of the drive's rated input current, while the rotary converter's loading stays put. And the 15 hp frame is not the default for a 7.5 hp motor: the drive is chosen by rated output current against the motor nameplate, and the 10 hp frame clears every screen the load applies.
The motor nameplate decides before the supply does #
A standard drive cannot output more voltage than its input provides, so a low-voltage class drive cannot hold up a motor left connected for 460 V. With the circuit locked out and verified dead, read the motor terminal box: a 230/460 V dual-voltage machine gives you the choice, with the link pattern for the low connection on the diagram under the cover, while a 460 V-only machine ends the discussion and the transformer stays. The physics of feeding a winding below its design voltage is the subject of why a 415 V delta motor cannot run on 240 V, and the verdict there applies here.
What doubles and what does not #
For the same power, current scales inversely with voltage: halving the voltage doubles it, so each amp on the high side becomes two on the low side. At full load this motor pulls about 25 A into the low-voltage drive, against roughly half that through the existing feed. Everything sized by that current in the drive's input circuit — conductors, fuses, the disconnect, any contactor — moves up with it.
The rotary converter is the exception, and it is the part people worry about for nothing. The converter was already feeding the transformer's primary at essentially the current the new drive will draw, give or take the transformer's own losses, because the transformer changed voltage, not power. The converter, its single-phase supply and its protection stay exactly as they are.
The conductor rule is written down: NFPA 70, the National Electrical Code, 2023 edition, covers adjustable-speed drive systems in Article 430 Part X, and 430.122(A) requires the conductors supplying the power conversion equipment to have an ampacity of at least 125% of the drive's rated input current. Confirm the edition in force and any local amendment with the authority having jurisdiction, and take that rated input current from the drive's documentation rather than from an estimate.
One converter trait matters at either voltage: its generated leg runs weaker than the two pass-through legs, and a drive's phase-loss or voltage-imbalance trip can pick that up. The limit-setting reasoning in setting voltage imbalance limits on a 480 V phase monitor applies to the drive's input protection the same way.
The two options side by side #
| Stay at 480 V | Go to 240 V | |
|---|---|---|
| Drive input current at full load | about 12.5 A | about 25 A |
| Minimum conductor ampacity, 125% rule | 15.625 A | 31.25 A |
| Input fuses and disconnect | keep as built | resize from the drive's rated input current |
| Motor connection | 460 V | 230 V links, dual-voltage machines only |
| Transformer | stays in service | retired, or kept for the next higher-voltage machine |
| Drive class | high-voltage class, output current at or above motor nameplate current | low-voltage class, output current at or above motor nameplate current |
The transformer was never the constraint in either direction: 45 kVA ÷ (1.732 × 480 V) = 54 A of secondary capacity, roughly four times this drive's input, so what you would remove was only the voltage itself.
Horsepower is the screen, current is the verdict #
The horsepower screen is quick: multiply the motor rating by 1.25 and take the next frame up. Here that is 7.5 hp × 1.25 = 9.375 hp, so the 10 hp frame passes and anything larger is already beyond the screen. But a screen is all it is: drive sizing guides are unanimous that the selection is made on voltage and current. The drive's rated output current at the motor's connection must equal or exceed the motor nameplate current, and its short-time overload rating must cover the acceleration; VFD rated current versus motor full-load starting torque works through that comparison. Then apply the frame's derating, because a carrier frequency above the default and a hot cabinet both cost output current, and a drive bought with no margin trips on the first hot week.
Working the 7.5 hp case at the lower input voltage on the 10 hp frame #
Inputs, and where each comes from. The motor is your 7.5 hp machine; its nameplate current is not in hand here, so the output-current test is written against the value you read off the plate. The supply is the rotary converter's three-phase 240 V. Full-load input current at that voltage is about 25 A for this size of motor. The screening factor is 1.25 on horsepower, a common rule of thumb, and the conductor factor is the code's 125% of rated input current (NFPA 70, 2023 edition, 430.122(A)). The candidates are the two frames you asked about.
The rules, in words. Conductors feeding the drive carry at least 125% of its rated input current, and the drive's rated output current at the motor's voltage must be at least the motor nameplate current after derating.
The arithmetic. 25 A × 1.25 = 31.25 A sets the ampacity floor for the low-voltage feed; halved for the high-voltage path, 12.5 A × 1.25 = 15.625 A would have been the floor there.
Result. The smaller frame clears the horsepower screen with room to spare, and the low-voltage input circuit must be built for at least 31.25 A.
Decision. Buy the smaller frame if its documented output current at the motor's voltage meets the nameplate after derating, and build the feed at 125% of its rated input current, which can exceed the 31.25 A floor but never fall below it. Step up to the larger frame only when the smaller one's output current comes up short, or when derating drops it short — not for peace of mind.
Rewiring to the lower voltage, in order #
- Lock out the rotary converter's supply circuit and the transformer primary, then test for absence of voltage at the drive's input terminals and inside the motor terminal box before either is opened.
- Change the motor's link connections to the 230 V pattern shown on the diagram under the terminal-box cover.
- Land the converter's three-phase output on the drive's input terminals (R S T on most frames), with conductors sized to 125% of the drive's rated input current and fuses or a breaker matching the drive manual's maximum input protection.
- Retire the transformer, or leave its secondary circuit intact and de-energized if a higher-voltage machine may follow.
- Enter the motor's nameplate data for the new connection before first start.
If you would rather take the rotary converter out as well and feed the drive from the single-phase supply, that is a different conversion with its own derating rules, and wiring a VFD R S T input from a single-phase supply covers it.
The decision for your bench #
Three cases, one answer each.
- The nameplate reads 230/460 V and no higher-voltage machine is coming: go to the lower voltage, buy the 10 hp frame if its output current covers the nameplate after derating, rebuild the input circuit at 125% of its rated input current, and retire the transformer.
- A higher-voltage machine is likely next: keep the transformer and buy the high-voltage drive. A transformer of that capacity is not quickly replaced, and the converter's loading is identical either way, so you give up nothing by waiting.
- The nameplate reads 460 V only: stay with the transformer and the high-voltage drive; there is no rewire to make.
Either way the rotary converter and its supply stay untouched, the drive is bought on current rather than the box label, and for this motor the smaller frame is the purchase — the larger one is overkill unless its own datasheet says the current demands it.
Questions asked
Will the motor run hotter on the 230 V connection?
No. On a dual-voltage motor the low-voltage connection puts the two winding halves in parallel, so each half carries the same current it carried on the high-voltage connection and the copper loss barely moves. Line current doubles, but that current is shared between the halves. The heat to manage after the change sits in the drive's input circuit, not in the motor.
What changes in the drive's settings after the rewire?
Everything tied to the motor. Enter the nameplate voltage, current, frequency, rated speed and power factor for the new connection in the drive's motor-data group, then run its motor identification or autotune routine as the manual directs. Tuning stored for the old connection is invalid, and a drive left with stale motor data stalls or trips on its first commanded ramp.
Does the cable to the drive need to be bigger for the same run length?
Yes, by more than intuition suggests. Cable loss rises with the square of current, so doubling the current quadruples the heat in the same conductors. Holding the same percentage voltage drop at the lower voltage takes about four times the copper area; twice the area only if you accept the same absolute drop. Count that copper as part of the job before treating the transformer removal as pure gain.
Can I keep the transformer and still buy the 240 V drive?
Yes. Feed the drive from the converter side and leave the transformer with its higher-voltage secondary circuit in place for whatever comes next; the drive does not care that the transformer exists. If nothing else uses that voltage, open the circuit's disconnect so the transformer is not sitting energized and burning no-load loss for nothing.

