Explainer
Which drive value is the live DC bus voltage over EtherNet/IP
Short answer
The live DC bus value is VBUS, the drive's bus-voltage monitor. The entries ULP0 to ULP10 store readings saved with fault records, and 3243 is a Modbus register address with no meaning in an EtherNet/IP path. Read VBUS on the drive display, configure the access the embedded Ethernet manual documents, and accept the PLC mapping only when its converted value tracks that display.

On this page
The live DC bus voltage on an ATV340 is VBUS, the drive's bus-voltage monitor. No entry from ULP0 to ULP10 is that value: they hold readings the drive stored with its fault records, so they answer what the bus was when a fault happened, not what it is now. And 3243, the address usually quoted for VBUS over Modbus, is a register address that means nothing in an EtherNet/IP configuration, because EtherNet/IP addresses data as CIP objects, not Modbus registers. Below is the value to map, the documented access route for the embedded Ethernet interface, and the checks that prove the mapping against the drive's own display.
The live value is VBUS, not the ULP fault records #
The parameter list separates live monitors from stored records, and a bus-voltage figure appears in both groups, which is the trap. VBUS is the monitor: its value is the present DC link voltage, the same number the drive's monitoring display shows. ULP0 to ULP10 belong to the fault log: each entry stores values captured when the drive recorded a fault. On the graphic keypad those records are viewed by pressing Home to reach the Main Menu, scrolling to 3 Diagnostics, pressing OK, then pressing F2 to open the Error history.
A stored record can imitate a live value. It changes when a new fault is written, and its number sits in the same range as the present bus, so watching it move proves nothing. The deciding source is the parameter description in the drive's programming manual, which labels VBUS as the bus-voltage monitor and the ULP group as fault records. Use those labels, not the numeric suffix of the parameter, to decide what to map.
Why the bus reading moves, and the limits it must respect #
The DC link sits between the input rectifier and the inverter stage. With a healthy supply it charges near the peak of the line-to-line voltage and moves from there whenever energy crosses it: a decelerating or overhauling load pumps it up, a sagging supply pulls it down, and why DC bus voltage rises when the motor connects to the VFD walks through that mechanism. The movement is what makes a live reading recognisable: a mapped value that never moves is not measuring this bus.
For the ATV340 the manufacturer's FAQ on voltage trip levels gives two numbers to hold the reading against: an overbraking threshold of 780 VDC on the DC bus and an overbraking trip level of 820 VDC. In normal running a correct reading sits below the threshold; a bus pushed to the trip level stops the drive, the behaviour covered in why a VFD DC bus overvoltage fault appears at random.
Why address 3243 fails on EtherNet/IP #
3243 is valid only inside a Modbus request. EtherNet/IP carries CIP, the Common Industrial Protocol, which addresses every data item as an object class, instance and attribute, reached either by an explicit message or through a cyclic I/O assembly that the interface maps. A register number is none of those, so it cannot be entered as a class, an instance, an attribute or an assembly offset.
The documented EtherNet/IP route lives in the drive's embedded Ethernet manual, document reference NVE61653, which covers hardware and software installation, configuration of Modbus TCP and EtherNet/IP, operational procedures and diagnostics. That manual is where the access path for VBUS is defined, whether object access or I/O mapping, together with the data length, numeric type and scaling to apply. Take every entry for the PLC request from its tables, not from a Modbus register number.
Two supporting details from the manufacturer's documentation. The interface's own address is set from the optional remote keypad display through [Communication] - [Comm parameters] - [Embd Eth Config]. On the PLC side the read is a message instruction: the Rockwell example for messaging an EtherNet/IP unit adds EEM (Ethernet IP Explicit Message) instructions and fills a Message Configuration window with values taken from the target device's table.
Set addresses and any wiring with the drive locked out and absence of voltage verified; the display and PLC checks below are done with covers closed while the drive runs normally.
If Modbus TCP is chosen instead, the register map is the authority and the PLC driver's numbering convention decides the configured request, the same hunt for a drive's Modbus register map that comes up whenever a drive meets a PLC over Modbus.
Mapping VBUS into the PLC #
- Identify the interface and its documentation: the embedded Ethernet port, the firmware the device reports, and the PLC's EtherNet/IP driver. Work from the manual revision that matches that firmware.
- Choose the access the manual documents for VBUS: a cyclic input mapping where the interface supports placing the parameter in I/O data, otherwise an explicit read per message instruction.
- Carry the data length, numeric type, byte order and scaling from the manual's entry for the parameter, and convert only after the raw word arrives intact.
- Expose three separate items to the application: the raw value, the converted volts and the read status. A failed read must mark the value stale instead of leaving the last voltage looking current.
- Prove one drive, then replicate: confirm display match and status on the first drive, repeat the same checks on each remaining drive, and verify every network endpoint against its physical drive before trusting its tags.
Checking a 480 V drive's PLC value against the 780 VDC threshold #
Inputs:
- Supply: 480 V AC, three-phase. Example input, since the question does not state the supply; the 480 V class stands in for it.
- Limits: overbraking threshold 780 VDC and overbraking trip level 820 VDC, documented in the manufacturer's ATV340 trip-level FAQ.
- Drive display on VBUS and PLC converted value: 678 VDC each. Example readings taken under stable load.
The rule, in words: with a healthy supply the bus charges to the peak of the line-to-line voltage, so the expected bus is the line voltage times the square root of two, 1.414. A correct mapping shows the PLC's converted value equal to the display within the display's resolution, and the value sits below the overbraking threshold in normal running.
The arithmetic:
- Expected bus: 480 V × 1.414 = 678.7 V, about 679 VDC.
- Display check: the display reads 678 VDC, one volt under that peak, so the supply is healthy and the display is tracking the live bus.
- Margin: 780 VDC − 678 VDC = 102 VDC to the overbraking threshold, and 820 VDC − 678 VDC = 142 VDC to the trip level.
- PLC check: converted value minus displayed value = 0 V, so the scaling is right.
Result: the mapping returns the live bus voltage with the correct scaling, and the bus holds roughly a hundred volts of margin before overbraking.
Decision: replicate this mapping to every remaining drive only after each one passes the same three checks, plausible against the line peak, below the threshold in normal running, and equal to its own display. If a converted value stays frozen while its display moves during a normal stop, the mapping points at a fault record: discard it and re-point to VBUS. If a converted value climbs to the threshold while the drive runs normally, the fault is on the bus, deceleration energy or the supply, not in the mapping.
What each wrong reading tells you #
- The value is frozen and jumps only after a trip. You mapped a ULP record, not VBUS. Re-point the mapping.
- The value is a constant multiple or fraction of the display. The scaling is wrong; apply the conversion the manual states for the parameter.
- The magnitude is nonsense or the sign flips. The data type or byte order is wrong; correct the word length and the byte swap.
- There is no value, only communication errors. The path is wrong, class, instance, attribute or assembly, or the endpoint is not the drive you think it is.
- The value is plausible but belongs to another drive. Identical drives on one supply show nearly identical buses, so a swapped address hides at steady state; during an approved maintenance window, take one drive offline and confirm which tag loses its read status.
Questions asked
What bus voltage should a 400 V supply show on the display?
Near the peak of the line-to-line voltage: 400 V times 1.414 is about 566 VDC. A display far below that points to a supply or rectifier problem, and a value well above it means the motor is returning energy or the reading is wrong. Compare the display with the PLC value at the same moment, under stable load, before changing any mapping.
Can the embedded port serve EtherNet/IP and Modbus TCP at once?
The embedded Ethernet manual covers the configuration of both protocols on that interface, but the PLC should use one documented access method per connection. If you fall back to Modbus TCP, request the VBUS register using the numbering convention your PLC driver applies, because drivers differ in how they present register addresses to the program.
Why did ULP0 look like a live value when it was watched?
The fault records update whenever the drive logs a fault, so a stored value can change between observations. Change alone does not make it a monitor: between faults it holds a snapshot while VBUS tracks the bus continuously. Trust the parameter description in the programming manual over the observed behaviour.
Is the optional remote keypad display required to set the Ethernet address?
The keypad route runs Communication, then Comm parameters, then Embd Eth Config, and the embedded Ethernet manual also covers software configuration through the port itself. Give every drive its own address and confirm each one before mapping tags in the PLC, so each tag can later be tied to its physical drive.