Troubleshooting
Why intermediate circuit voltage goes out of permitted range
Short answer
An intermediate circuit voltage out of permitted range fault means the drive's DC bus left the window its own documentation defines. The timing names the cause: a bus that sinks on acceleration points to the incoming supply, a bus that spikes on deceleration points to regenerative energy, and a slow drift points to aging DC bus capacitors or a failing supply unit. Fix the side the timing names.

On this page
Intermediate circuit voltage out of permitted range means the drive or controller has measured a DC bus voltage outside the window its own documentation defines — high, low, or either, depending on the model. Treat it as a power-conversion event, not a motion-program problem. The timing of the message splits the causes cleanly: a bus that sinks during acceleration points at the incoming supply, a bus that spikes during deceleration points at regenerative energy with nowhere to go, and a slow drift points at aging DC bus capacitors or a failing supply unit. Read the fault history first, match each trip to the motion running at that instant, and the fix path usually names itself.
What the intermediate circuit is, and who sets the range #
The intermediate circuit is the DC link between the input rectifier and the output inverter: the rectifier charges it, the inverter draws it down, and in a multi-axis controller every drive shares it. The page on how a VFD's rectifier, DC bus and inverter stages work walks that chain stage by stage.
On a plain diode rectifier the bus sits near the peak of the line-to-line supply, not its RMS value — that physics sets the neighbourhood, but not the limit. The permitted range itself is a drive-specific specification with tolerances and time limits, published in the drive or controller manual, and no general article can supply the number for your unit.
IEC 61800-5-1 is the safety standard for power drive systems; the 2023 edition (EN IEC 61800-5-1:2023) covers systems with input voltages up to 1 kV AC and DC circuits up to 1.5 kV DC, and it requires protective separation between that bus and anything a person can touch. It frames the hazard; your manual gives the operating window. Confirm both against the equipment documentation and your local authority having jurisdiction.
Read the fault history before anything else #
The message is a window violation; the drive's fault table for your model says whether it latched high or low, and the history timestamps every trip. Pull that before touching a setting: list each trip time against the motion running then, the line voltage if the drive logs it, and the heatsink or cabinet temperature if it logs that too. Three columns of timestamps usually sort the causes below on their own.
Match the timing to the cause #
- Trip lands on acceleration, on a loaded start, or while another machine starts upstream: suspect the supply. The line sags, the rectified bus follows it down, and the controller sees the undervoltage side of the window.
- Trip lands on deceleration, a fast stop, or lowering a load: suspect regenerative energy. The motors return kinetic or potential energy to the bus faster than the drive can burn it off, and the bus climbs past the overvoltage side. Where the trips arrive with no pattern, the article on why a DC bus overvoltage fault appears at random covers that mechanism from the overvoltage side.
- Trips get more frequent over weeks, or cluster when the cabinet is hot: suspect aging DC bus capacitors or a marginal supply unit. Capacitance falls with age and heat, ripple grows, and the bus drifts even at light load.
- Trip appears at power-up or at idle with no motion commanded: suspect the supply unit, a loose bus connection or the input wiring. Nothing is regenerating and nothing is accelerating, so the energy balance is already wrong before the motors move.
Worked example: a 400 V drive that trips during deceleration #
Inputs, for an example case on a typical 50 Hz plant supply:
- Line-to-line supply measured at the drive terminals while running: 400 V AC, three-phase, 50 Hz (example measurement).
- DC bus at the trip instant, from the drive's event log: 620 V DC (example log value).
Rule in words: a three-phase diode rectifier charges its bus to the peak of the line-to-line voltage, which is the RMS line-to-line value times the square root of two, about 1.414.
Arithmetic:
- Supply-imposed bus peak: 400 V × 1.414 = 566 V DC (565.6 rounded).
- Margin at the trip: 620 V − 566 V = 54 V above the supply-imposed peak.
- In percent: 54 V ÷ 566 V ≈ 9.5 %.
Result: the bus finished the stop about 54 V — roughly 9.5 percent — above anything its own supply could have pushed it to, so the extra energy entered from the motor side.
Decision: a bus above the supply-imposed peak at a deceleration trip is regenerative energy; verify the braking resistor and its thermal duty against the drive manual, and use a longer deceleration ramp only as a stopgap. The mirror check sorts an acceleration trip: divide the logged bus by 1.414, and the answer is the line voltage the rectifier actually saw — if that is well below the measured line, the shortfall was on the supply side. Note these are the physics expectations for the example supply, not the drive's permitted-range limit; read the real window from the drive's own documentation before judging any excursion against it.
Fix the side the timing named #
Everything below that opens the controller is de-energized work: switch off, lock out, wait the capacitor discharge time the documentation states, and verify absence of voltage at the bus terminals before touching anything. NFPA 70E, 2024 edition, covers the electrical safety work practices for this kind of work, including verifying an absence of voltage; confirm what applies on your site with your authority having jurisdiction and the equipment documentation.
Supply side: measure the line at the drive's input terminals while the drive is loaded — a reading at a board upstream hides the drop in your own feeder. A line that collapses under load points to conductor size, terminations or the upstream supply; a missing phase deepens the bus ripple and drags the minimum down, and the article on whether a three-phase rectifier overloads after losing one phase covers what one open phase does to the input side.
Regeneration side: give the braking energy somewhere to go. Verify that the braking resistor exists, is connected, and that its duty matches the decelerations you actually run, all per the drive manual; if the line-up has a regenerative supply unit, check its status too. Where the bus rises the moment the motor is connected, the article on why the DC bus voltage rises when the motor connects to the VFD explains that mechanism.
Drift side: capacitors that have aged show falling capacitance and rising ripple; the drive manual gives the test and the replacement procedure, and replacement uses the manufacturer's documented parts.
Idle and power-up side: a bus that cannot reach its window with no motion commanded points at the supply unit or a connection. Test the supply unit's output against its documentation before replacing anything.
Confirming the repair #
Repeat the exact motion that produced the message — same speed, same load, same deceleration — while logging line and bus voltage. Fixed means the move completes with the bus inside the drive's documented window and the fault history stays clean over the following shifts. If the trip returns, re-sort the evidence by timing: a bus that no longer spikes on deceleration but still drifts at rest is the capacitor or supply-unit path, not the braking path you just worked.
Questions asked
How long after switching off is the DC bus safe to touch?
Longer than it feels. Bus capacitors hold a hazardous charge for minutes after the supply is off; wait the discharge time stated in the drive or controller manual, then measure across the bus terminals with a meter rated for that bus voltage and confirm the reading is inside the manual's safe threshold before touching anything. The measurement, not the wait alone, is what clears you to work.
What should the bus read on a healthy drive at rest?
On a plain diode rectifier it sits near the line-to-line peak: about 566 V DC on a 400 V supply, with some ripple, and proportionally lower on a low line. The drive's permitted window is its own specification around that neighbourhood in its manual, not a universal number. A bus far above the expected peak at rest points at a supply-unit or measurement problem; far below points at lost input phases or a sagging line.
Does lengthening the deceleration ramp fix an overvoltage trip?
It treats the symptom, not the cause. The same rotating energy spread over a longer ramp returns at lower peak power, so the bus peaks lower and the trip may stop, but the energy still has nowhere to go and the cycle time grows. Use the ramp change as a stopgap while you verify the braking resistor and its duty against the drive's documentation.
Can this fault come from the incoming supply alone?
Yes, and it tracks load rather than motion. A line that sags under load pulls the rectified bus down with it, and a lost input phase deepens the ripple so the bus minimum falls further. If the trip follows load changes or upstream machine starts instead of your own accelerations, work the supply side: measure at the drive terminals under load and check every input phase.
