Troubleshooting
Why a VFD trips on DC link undervoltage and what to check first
Short answer
A DC link undervoltage fault means the drive's DC bus fell below the trip level set for that model, and the cause is usually on the input side: a line sag, a lost input phase, an undersized source or a loose input connection. The bus tracks line voltage at about 1.35 times line-to-line, so measure the input first and suspect the rectifier only when the supply is proven good.

On this page
- What does a DC link undervoltage fault actually tell you?
- What DC bus voltage should a 480 V drive show?
- How deep a line sag trips the drive?
- What does a lost input phase do to the DC bus?
- What should you check first when the drive trips?
- Why does the fault appear only at high load?
- When is it the drive and not the supply?
- Can you reset and keep running, or do you fix the supply?
- Questions asked
A DC link undervoltage fault means the drive's internal DC bus fell below the trip level set for that model, and in most cases the cause sits on the input side: a line sag, a lost input phase, an undersized source or a loose input connection. A six-pulse rectifier holds the bus at about 1.35 times line-to-line voltage, roughly 650 V DC on a 480 V system, so the bus follows the supply down almost instantly. The productive order is to measure the input power at the drive terminals first, suspect the bus sensing or the rectifier only when the supply is proven good through the trip, and treat every trip as an event to explain rather than clear.
What does a DC link undervoltage fault actually tell you? #
It tells you the DC bus voltage fell below the trip threshold programmed into that drive model; it does not tell you which part failed, because the same fault comes from a supply dip, a lost input phase, a bad connection or, rarely, a fault inside the drive. The displayed code and wording differ by manufacturer and series, so record what the drive shows, pull its fault history — most drives log recent faults with a counter — and read that code in the manual's fault table for the exact model. That table gives the trip threshold, the input voltage range and the reset conditions; one maker's number is not another's. Keep three things separate in your notes: the code displayed, the cause you verify, and the action you take. The code alone assigns no cause.
What DC bus voltage should a 480 V drive show? #
A six-pulse rectifier holds the bus at about 1.35 times the line-to-line RMS voltage under load, so a 480 V system charges it to roughly 648 V DC, near 650 V DC, and a 400 V system to about 540 V DC. The factor is the average of a three-phase bridge, 3√2 divided by π, and it makes the bus a voltmeter for your supply: the capacitors smooth the rectified peaks but cannot hold the bus up for long once the line drops. At light load the bus drifts up toward the line-to-line peak, about 679 V DC here, so compare readings taken at similar load. How the bridge and capacitors produce that number is covered in how a VFD's rectifier, DC bus and inverter stages work.
How deep a line sag trips the drive? #
The trip depth is the manual's DC threshold divided by 1.35: with an illustrative 435 V DC threshold, any line-to-line sag below about 322 V pulls the bus under the trip level. Worked example, with every input stated: a 480 V, 60 Hz supply; a six-pulse drive; a trip threshold taken as 435 V DC, a stand-in for the figure in your manual's fault table, which you read for your own model.
- Nominal bus: 1.35 × 480 V = 648 V DC.
- Bus during a sag to line voltage V: 1.35 × V.
- Trip condition: 1.35 × V ≤ 435 V DC, so V ≤ 435 ÷ 1.35 = 322 V.
- Check: 1.35 × 322 V = 434.7 V, which rounds to the threshold.
So a sag to 340 V leaves the bus at 459 V DC and no trip, while a sag to 300 V leaves 405 V DC and trips. Use the number: set a recording power-quality meter — Class A, measured by the methods of IEC 61000-4-30, 2015 edition, which defines how voltage dips are measured and classed — to log every event below that line voltage, then match its timestamps against the drive's fault history. A match confirms the supply; no event during a trip points inside the drive.
What does a lost input phase do to the DC bus? #
Losing one input phase drops the bus toward 0.90 times line-to-line, about 432 V DC on a 480 V system, with deep ripple at twice line frequency, so the drive trips as soon as it is loaded. With one phase open, the six-pulse bridge becomes a single-phase bridge across the two live phases, whose average is 2√2 divided by π, and the ripple valleys fall well below that average under load. The trap is that at no load the capacitors charge toward the peak of the remaining line-to-line voltage, so a bus reading taken with the drive idle can look healthy. Verify the phases directly with the power off: continuity-check each input fuse and each contactor pole, and inspect every input lug. A drive whose idle bus reads high but which trips within seconds of a load step is the classic single-phased-input signature. Find and repair the open element — fuse, pole, lug or feeder — before restarting; a reset without the repair just repeats the trip.
What should you check first when the drive trips? #
Check the input power at the drive terminals first, in this order: all three phases present, voltage inside the manual's input range while loaded, connections tight and cool, then the drive's own fault history — the rectifier comes last. One safety note before anything opens: lock out the input, test for absence of voltage, and wait the bus-discharge time the manual states, because the DC capacitors hold a dangerous charge after the supply is off. NFPA 70E, 2024 edition covers the electrical-safety practices for energized work and the PPE its risk assessment requires; any live measurement follows your site's procedures under it, confirmed with the local authority having jurisdiction and the equipment documentation.
- Record the displayed fault, pull the fault history, and read that code in the manual's fault table for the exact model: threshold, input range, reset conditions.
- With the drive locked out and the bus verified discharged, inspect the input lugs and the breaker, fuse and contactor terminals for discoloration, and re-torque to the value in the manual's terminal table.
- Continuity-check all three input fuses and each contactor pole, and confirm the feeder carries all three phases.
- Log the three line-to-line voltages at the drive terminals with a recording meter while the load steps — the moment of the trip is what matters, not an idle reading.
- Compare the terminal voltage with the upstream panel under load: a gap between the two localizes a high-resistance connection in between.
- Only if the supply is proven good through the trip, follow the manual's internal diagnostics and fuse checks for the model, or hand the rectifier and bus-sensing checks to qualified drive service.
Why does the fault appear only at high load? #
Because the sag deepens with current: the drop equals load current times source impedance, so a weak transformer, a long feeder or a loose lug shows healthy voltage at idle and a bus below threshold at full torque. Illustrative numbers: 0.25 Ω of combined source, feeder and connection impedance per phase carrying 100 A of input current drops 100 A × 0.25 Ω = 25 V of phase voltage, about 43 V line-to-line after multiplying by √3, and the bus loses roughly 1.35 times that, near 58 V. A loose lug adds a time signature: its resistance climbs as it heats, so the trip lands minutes after a load step, and a thermal camera under load finds it. Trips can also track other equipment — a large across-the-line motor start on the same feeder dips the bus for every drive on it, the mechanism behind why a VFD DC bus overload fault appears when a soft starter starts. Do not retune the drive to chase it; the case is walked through in why a drive undervoltage fault is a supply sag, not a tuning fix.
When is it the drive and not the supply? #
Only when the line-to-line voltage at the drive terminals stays inside the manual's input range, on all three phases, through the moment of the trip — proven with a recording meter or the drive's own logged readings, not a single handheld check an hour later. With the supply proven good, two candidates remain: a bus-voltage sensing chain that reads low while the bus is healthy, or a rectifier leg with an open device that can no longer hold the average up under load. Follow the manual's diagnostic procedure and internal-fuse check for the named model, and compare the drive's displayed bus voltage against a direct DC measurement at the test points the manual names — energized work under the same NFPA 70E procedures. One timing clue separates the cases: a trip that lands during deceleration, when the bus should be rising as the motor returns energy, points at a coincident supply event rather than braking behavior, as covered in why an undervoltage fault on decel is a supply sag, not braking. Supply good through the trip plus a low measured bus means rectifier service; supply good plus a healthy measured bus means the sensing chain.
Can you reset and keep running, or do you fix the supply? #
Fix the cause, because a drive that keeps resetting into a low bus pays twice: at reduced bus voltage the input current rises for the same power, heating the rectifier and the DC capacitors, and the motor loses the voltage it needs for full torque. When a recorder confirms recurring sags, the fixes rank in order: repair the bad connection or the missing phase; upsize or regulate the source when the drop is systemic; enable the ride-through function if the manual's function list shows one for your model, since some drives coast or lean briefly on the motor's inertia through a dip; or put a regulator or UPS in the drive's power feed, sized to the drive's input current and the input tolerance the manual documents. Decide by the pattern:
- Trips that track a known plant event — a large motor start, a welder, a transformer tap change: it is the supply; soften that start, add ride-through, or regulate the feed.
- Trips that grow with the drive's own load: measure for a weak source or a high-resistance input connection, then repair or upsize.
- An idle bus that reads high but collapses at load with a phase missing: repair the open fuse, pole or lug before restart.
- Input proven good through the trip: the fault is inside — rectifier or sensing — and goes to qualified service by the manual's procedure.
Questions asked
Does a UPS on the drive's control power stop DC link undervoltage trips?
No. The DC link is charged by the main rectifier from the line-power terminals, not from the 24 V supply or the control transformer. A control UPS keeps the keypad and logic alive through a dip, but the power rectifier still sees the sag and the bus still falls. Only a regulator or UPS in the drive's power feed changes the bus voltage.
Why does the input contactor drop out at the same moment?
On a deep sag the coil can no longer hold its armature, so the drive loses its input entirely and the bus decays under load to the trip, even when the sag alone would have been survivable. If the contactor opened first, repair the supply dip or the contactor's coil circuit; the drive's power section is not the fault.
Will a longer acceleration time stop the trips?
Only when every trip lands during this drive's own acceleration on a weak source: a gentler ramp draws less input current, so the same source and connection impedance drops less voltage. If the trips follow other plant loads or arrive at steady speed, the ramp changes nothing; record the line voltage and fix the supply or the connection instead.
Can the drive show its own DC bus voltage while it runs?
Most drives list live bus voltage among the signals their display or diagnostics can show, under a name that varies by model, so find it in the manual's signal list and watch it while the load steps. A bus that dives while the terminal voltage holds points inside the drive; a bus that tracks the line down points to the supply.