Troubleshooting
Why DC bus voltage rises when the motor connects to the VFD
Short answer
A bus that reads about 520 VDC unloaded and about 722 VDC once the motor leads land, with no run command, points to AC voltage arriving on the motor circuit and rectifying into the bus through the inverter's freewheeling diodes. The resting bus on a 400 V supply is the line peak, about 566 VDC, so anything higher comes from the motor side or from a bad measurement. Measure the disconnected motor leads for AC voltage and verify the bus with a rated meter before replacing parts.
On this page
- Why does the bus climb only when the motor leads are connected?
- What should the DC bus read on a 400 V supply?
- Where would voltage on dead motor leads come from?
- Is a "dead short" between all three phases a real fault here?
- What measurement sequence settles it?
- When do you blame the drive instead?
- Is the no-start a separate problem?
- Questions asked
The drive sits near 520 VDC on the bus until you land the three motor leads, and then the reading jumps to about 722 VDC with no run command issued. That pattern is not proof of a bad motor and not proof of a bad drive: it means voltage is present on the motor circuit and is being rectified into the bus through the inverter's freewheeling diodes. Before any part gets replaced, measure AC voltage on the disconnected motor cable, re-verify the bus with a properly rated meter, and read the drive's own fault list. The decision sequence below gets you there without guessing.
Why does the bus climb only when the motor leads are connected? #
The inverter's freewheeling diodes tie the output terminals to the bus permanently, so even with the IGBTs idle they rectify any motor line-to-line voltage that exceeds the bus, and a reading that appears only with the leads landed comes from the motor side. This is the same path the drive uses to return regeneration energy during deceleration, and it needs no run command to work: a diode conducts whenever its anode is more positive than its cathode, whether or not the control board is doing anything.
That narrows the case to whatever changes when you land the three leads, which is only three things:
- the motor itself, including anything mechanically turning its shaft;
- the cable and its terminations between drive and motor;
- any other circuit accidentally tied into that cable somewhere along its route.
Nothing inside the drive changes when you connect the motor, so the drive stays on the suspect list but does not move to the top of it.
What should the DC bus read on a 400 V supply? #
On a 400 V line-to-line supply the resting bus is the peak of the line, 400 × √2 ≈ 566 VDC, so any reading above the measured line's peak cannot come from the input rectifier. The familiar 520 VDC is what the display typically shows under ripple and load; it is not a textbook value, and chasing the difference between it and the calculated peak is a distraction. The number that matters is the jump.
The worked check, with the line voltage you should measure rather than assume:
- Measured line-to-line RMS at the drive input: 400 V
- Expected resting bus: VDC ≈ VLL × √2 = 400 V × 1.414 ≈ 566 VDC
- Reported reading with the motor connected: 722 VDC
- Excess above the line peak: 722 − 566 = 156 VDC
An input rectifier cannot produce that excess. Either voltage is arriving on the output side, or the bus reading is wrong. Both are testable, and both tests come before a replacement order.
Where would voltage on dead motor leads come from? #
With the IGBTs idle the drive puts nothing on its output terminals, so measurable AC on the motor cable after you disconnect it from the drive means an outside source is energizing that circuit. The realistic candidates, in the order you should check them:
- A shaft that is being turned by the load: a windmilling fan, a pump on a shared header, an inclined conveyor. A rotating induction motor with residual magnetism or capacitance excitation can generate, and even a slow shaft can back-feed through the diodes.
- A closed bypass or across-the-line contactor, or a wiring error tying the motor circuit to line power somewhere else in the plant.
- A star point bonded to ground, which creates a rectifier path through the output diode bridge back to the bus.
- A second drive or starter still connected to the same motor terminals.
A steady AC reading at the disconnected cable end is the finding that matters; zero there moves the investigation back to the drive.
Is a "dead short" between all three phases a real fault here? #
On a motor with an internal star and only three leads, every phase-to-phase measurement runs through two windings in series, so a low-ohms reading or a continuity beep is the winding path itself, not a short. There is no way to isolate a single winding at the terminals of a three-lead motor; you cannot do the per-winding tests that a nine-lead motor allows, so the honest measurement is the comparison between the three pairs. That a known-good identical motor gives the same beeping result confirms the meter and the method, not a fault.
- Measure U–V, V–W and W–U with the same meter, the same range and the same connection technique, and write down the values rather than the beep.
- Matching readings within the meter's tolerance point away from the windings; a significant spread between the three pairs points at the motor.
- Normal insulation resistance to ground, phase by phase, is real evidence against a ground fault, and it is the same lesson as in the case where a VFD ground fault trip appears even when insulation tests pass: good megger numbers say nothing about an external voltage source on the circuit.
What measurement sequence settles it? #
The sequence that settles it has seven steps and it starts de-energized: record the drive state, measure the line, verify the bus independently, then test the motor circuit in pieces. De-energize, lock out, test for absence of voltage, and wait for the bus to discharge per the drive's manual before opening anything; the bus capacitors hold a lethal charge after the input is off, and nothing in this procedure is done live.
- Record the drive state while it is still in its faulted condition: the displayed bus value, the active fault code from the drive's own fault list for your model, and the run and enable status. A secondhand description of a fault is not a fault code.
- Measure line-to-line RMS voltage at the drive input and run the peak calculation from the section above with the measured value.
- Verify the bus with a meter rated for the voltage and the measurement category, for example a 1000 V CAT III instrument, and compare it with the display. Meter choice for drive work is covered in the article on measuring VFD and soft starter current with the right meter.
- Disconnect the motor leads at the drive and measure AC voltage between each pair at the cable end. The expected reading is 0 V. Any steady reading must be traced to its source before anything is reconnected.
- Measure winding resistance with the cable attached and again with it removed, which splits a cable fault from a winding fault.
- Insulation-test the isolated motor and the isolated cable separately, each lead to ground, with the drive completely out of the circuit.
- Reconnect one change at a time and re-read the bus under the same conditions, so every change in the reading has exactly one cause.
The step-4 result is the decision point:
| Step-4 result | Meaning | Decision |
|---|---|---|
| 0 V at the cable end | No external source on the motor circuit | Suspect the drive's output stage or bus sensing; see the next section |
| Steady AC at the cable end | Outside source energizing the motor circuit | Trace and remove it; the drive is probably healthy |
| AC present only while the shaft turns | The load is back-driving the motor | Mechanical cause; secure the machine, not the electrical panel |
When do you blame the drive instead? #
Blame the drive only when the disconnected motor cable measures 0 V and the bus still climbs with nothing on the output terminals; that is the different pattern covered in the article on a VFD overvoltage fault with no motor connected, and it moves the suspicion onto the drive itself. One in-place test narrows it further: if your drive's functional safety documentation states that safe torque off, the function defined in IEC 61800-5-2, isolates the output stage from the bus, enable STO with the motor still connected. A bus that stabilizes under STO confirms the feeding path runs through the output stage; a bus that stays high with STO active points at the bus sensing or display circuit instead. Check the drive documentation for that STO behavior first, because it is a documented detail of specific models, not a property of every drive.
Is the no-start a separate problem? #
Treat the no-start as a second finding: an unmet run enable blocks the control chain, and a blocked drive will never fire its IGBTs while the diodes keep rectifying whatever reaches the output. The two clues share a panel but not a cause, so close them separately:
- Pull the actual active fault and the fault history from the drive and work from the manufacturer's fault table for the named model, not from the earlier shift's description.
- Walk the enable chain: safety loop, hardwired enable, communications-controlled start, and any interlock in between.
- Do not accept fluxing as an explanation. A drive that has not been commanded to run does not magnetize the motor; nothing on the output terminals at rest is the expected state, which is exactly why measurable voltage there is a finding.
Fix the external voltage first, because it is the condition that can damage the bus capacitors and confuse every other test; then chase the enable. The bus that drops back to its resting value the moment the source is removed is your confirmation that the drive was telling you the truth the whole time.
Questions asked
Can the input supply itself push the DC bus that high?
No. The input rectifier can only charge the bus to the peak of the line voltage. Even a line running ten percent high, 440 V, gives a bus of about 622 VDC, still well below the reading in question. A bus above the measured line's peak needs another voltage source on the output side or a measurement error, not a supply problem.
Should I insulation-test the motor while it is still wired to the drive?
No. Disconnect the motor and cable from the drive first. An insulation tester puts hundreds of volts onto the winding, and that voltage goes straight into the drive's output stage if the leads are still landed, which can destroy the IGBTs and diodes you are trying to diagnose. Test the isolated motor and the isolated cable separately, each lead to ground.
Is a braking resistor the fix for this rise?
No. A braking chopper and resistor clamp the bus only during regeneration, such as a high-inertia load ramping down, and only above the chopper's switch-on threshold. A bus that climbs at rest with no run command is being fed from an external source through the output diodes, and the feeding continues until that source is found and removed.
What would the resting bus be on a 480 V supply?
The same formula applies: 480 V times the square root of two gives about 679 VDC. Measure the actual line-to-line voltage at the drive input rather than trusting the nominal system voltage, because the real line can sit several percent either side of nominal, and that moves the expected bus with it.