Why a 15 Hz ripple on a genset bus is usually speed-locked

Power quality and harmonics Published 7 min read By Current Intel engineering team

Short answer

A 15 Hz ripple of about 1 V and 30 A on a 480 V, 750 kW isolated bus is 0.2 percent of nominal and matches the set's mechanical orders — once per revolution at 900 rpm, a half order at 1800 rpm. Confirm it with a second recorder, an AVR field check and feeder current logging; if no feeder owns the ripple, record it as genset content and commission the replacement against the same capture.

On this page
  1. Size the ripple before chasing it
  2. Map the frequency to a shaft order
  3. Why voltage and current ripple together
  4. The checks, cheapest first
  5. The decision for the replacement design
  6. Questions asked

The ripple is almost certainly the set itself, not an undocumented load — but you can prove that in one day of recording, and the proof is what you carry into the replacement design. On this isolated 480 V, 750 kW bus the recorded ripple is about 1 V of voltage and 30 A of current at 15 Hz, a frequency that lands on the machine's mechanical orders: once per revolution on a 900 rpm set, a half order on a 1800 rpm set. The magnitude is 0.2 percent of nominal voltage, and nothing on a barge trips on that. The set is leaving anyway, so this is an attribution job, not a repair: here is the arithmetic, the test order, and the decision for each outcome.

Size the ripple before chasing it #

Two divisions put the finding in proportion.

  • Voltage: 1 V / 480 V = 0.0021, just over 0.2 percent of nominal.
  • Current: at 0.8 power factor the set's apparent power is 750 / 0.8 = 937.5 kVA, and rated current is 937500 VA / (1.732 × 480 V) = 1128 A, so the ripple is 30 / 1128 = 2.7 percent of rating. Read the power factor and kVA off your data plate and redo the division if they differ.

An islanded set is never rock solid, and modulation this small at the rotation rate is normal background. The only reason to spend time on it is the possibility that a cyclic load produced it — because that load, unlike the set, stays on the barge.

Map the frequency to a shaft order #

Speed and frequency trade through rpm = f × 60 s/min: for the recorded ripple that gives 15 × 60 = 900 rpm, which is why it reads as rotation. The diagnostic quantity is the ripple's order, its frequency divided by shaft frequency. Worked example for the common case, a 1800 rpm diesel on a 60 Hz system: shaft frequency = 1800 / 60 = 30 Hz, so order = 15 Hz / 30 Hz = 0.5. On the slower eight-pole machine the same arithmetic gives order 1.0, once per revolution.

A 60 Hz alternator locks to a synchronous speed of 120 × f / poles — 3600, 1800, 1200 or 900 rpm at 2, 4, 6 or 8 poles — so read the speed off the data plate; do not infer it.

Data-plate speed Shaft frequency Ripple order Usual mechanical source
1800 rpm 30 Hz 0.5 One cylinder contributing uneven torque: a four-stroke fires each cylinder every second revolution, so one weak cylinder is exactly half order
900 rpm 15 Hz 1.0 Once-per-revolution torque pulsation, unbalance or misalignment
1200 rpm 20 Hz 0.75 Not a normal engine order: treat as load or torsional content until the feeder test decides

Governor and AVR hunting on a set this size runs at fractions of a hertz to a few hertz. The ripple is an order of magnitude faster, which puts it in the mechanical band: uneven engine torque, or a lightly damped torsional mode of the shaft line, which behaves identically for this diagnosis.

Why voltage and current ripple together #

The recorded pair hides a useful check. Divide the modulation amplitudes, 1 V / 30 A ≈ 0.033 Ω, and you have the effective impedance the ripple current flowed through. The machine's base impedance is the line-to-line voltage squared over its apparent power, 230400 / 937500 = 0.246 Ω for the example above, so the ripple behaved as if it came through roughly 0.14 of base — the leakage-flux order you expect from the machine itself. One current modulation, reflected into voltage through ordinary source impedance, explains both traces; you do not need AVR hunting to account for the voltage. Treat this as a consistency check on the capture, not a measurement of any data-sheet reactance.

Expect the frequency wobble to be tiny. The swing equation puts the speed deviation at the torque modulation divided by 2 × H × ωm, with H the inertia constant and ωm the modulation's angular frequency: 0.0266 / (2 × 2 s × 94.2 rad/s) = 7 × 10⁻⁵, about 0.007 percent of rated speed, or roughly 4 mHz on a 60 Hz bus, with H assumed at 2 s. That is an estimate, and it says a null frequency reading proves nothing.

The checks, cheapest first #

Work down the list and stop when a step hands you the answer.

  1. Validate the recorder. Confirm the component sits on all three phases and in both voltage and current, check the CT and PT ratios in the setup, then repeat the capture with a second instrument — ideally a power quality recorder meeting IEC 61000-4-30 (Edition 3.0, 2015), which defines measurement methods and accuracy classes for power quality parameters; confirm the method in the instrument manual. Ripple on one channel only, or ripple that vanishes with the second instrument, is an artifact of sampling or scaling: correct the setup and re-baseline.
  2. Read the data plate and compute the order with the arithmetic above; one minute of work that frames everything after.
  3. Capture raw waveform at high rate and watch the frequency. Zero-crossing jitter that wobbles in step with the voltage and current envelopes is the speed-locked, standalone-set signature. Given the estimate above, treat a positive as strong evidence and a null as no information.
  4. Log or scope the AVR field voltage. A clean field with terminal ripple present points at mechanical or load causes; a field carrying the same modulation points at the excitation control. Shut the set down, lock it out and test for absence of voltage before opening the terminal box or connecting anything to the field circuit, and close it up before restarting — the field is live whenever the set runs. NFPA 70E (2024 edition) covers the shock and arc-flash risk assessment such work requires; follow your site's electrical safety program, the local requirements and the set's documentation.
  5. Log every main feeder's current on the same time base as the bus capture. The load that owns the ripple carries it at the highest amplitude on its own feeder; the other feeders show only the small share that bus-voltage ripple drives through them. Genset-origin ripple sits at the terminals and spreads across feeders with no single owner. Think reciprocating compressors, pulsating-discharge pumps and welders — the family behind the bus disturbances traced in tracing 480 V voltage swings that burn up welders — plus drives with a repeating duty cycle.
  6. Shed loads one at a time where the schedule allows. The component dies with the owning load, or it survives every shed and belongs to the set. Record each step.

The decision for the replacement design #

  • No feeder owns it, the field is clean, the component rides on every feeder: it is speed-locked content of the outgoing set. Write that into the design basis, specify nothing extra, and let it leave with the machine. The performance class of the new set — ISO 8528-1:2018 defines the G1 to G4 classes and the voltage and frequency tolerances behind them — comes off the load list, not off this ripple; confirm the class with your specification and the set's documentation.
  • One feeder owns it: you found the unknown load. Put it on the load list with its measured modulation, amplitude and rate, and specify the new set's governor and AVR response around it; the tuning side of an islanded set is covered in governor settings for islanded power systems. The step-response side — the motor starting dips and voltage recovery that actually size the set — is treated in generator swing and voltage control in motor start studies.
  • It was an artifact: correct the recorder configuration, re-baseline, and carry nothing into the design.

At commissioning, capture the new set at the same points with the same settings and file both datasets together; that comparison is the whole reason to do the attribution properly now.

Questions asked

Could the ripple be a torsional resonance instead of simple torque pulsation?

Yes, and it would not change the decision. Shaft lines have torsional eigenfrequencies, and published measurements on generator shaft lines identify components between 10 and 30 Hz, with a first eigenfrequency of 23.6 Hz in one documented case, so this component sits inside that band. A torsional mode is still engine-excited and speed-locked, so it leaves with the old set. If the load list keeps a large cyclic member, ask the new set's supplier for the torsional study.

How can a recorder invent a ripple line that is not real?

Through aliasing. For example, a recorder sampling at 1050 Hz cannot resolve anything above 525 Hz, and components above that fold back into the band: a genuine 1035 Hz component from a rectifier appears at 1050 minus 1035, which is 15 Hz. Change the sample rate or swap instruments: a folded component moves or vanishes, a real one holds its frequency. That is why the instrument check comes before any work on the set.

The data plate says 1200 rpm — what order is the ripple then?

A 1200 rpm shaft turns at 20 Hz, so the component lands at order 0.75. Four-stroke engines produce half-integer orders — 0.5, 1.0, 1.5 and up — so 0.75 is not normal engine content. Suspect a cyclic load first and a torsional mode second, and lean on the feeder logging: if one feeder owns the component, the engine is cleared in a single test.

What should the commissioning capture on the replacement set include?

The same measurement points, sample rate and instrument class as the old baseline, at load levels you can repeat from the old logs — for example 25, 50, 75 and 100 percent of the recorded peak. Capture bus voltage, current and frequency at high rate, plus every main feeder's current, and file both datasets together. If the ripple reappears with the old set gone, the load list missed something.

Keep reading

  • Troubleshooting

    Tracing 480 V voltage swings that burn up welders

    515-520 V line-to-line on a 480 V system is 7.3-8.3% above nominal, past the ANSI C84.1 Range B service ceiling of 508 V, and it is a steady-state regulation problem until a transient capture proves otherwise. Measure line-to-line at the distribution panel, at both sides of the 480/480 isolation transformer, and at the welder terminals, then fix the tap or regulation at whichever stage the readings indict. Surge protective devices will not lower it.

    Power quality and harmonics

  • Troubleshooting

    Why power factor capacitors don't fix motor starting sag

    No — panel power factor capacitors will not fix motor-start dimming. They cancel steady-state reactive current; the dim is a locked-rotor surge several times full-load through the source and feeder impedance for about a second. Cut the impedance or cut the starting current: fix the feeder, strengthen the supply, or soft-start with a VFD or starter where three phase allows.

    Power quality and harmonics

  • Troubleshooting

    Diagnosing current imbalance across every motor on a service

    Compute unbalance per NEMA MG-1 as maximum deviation from the three-phase average, not the min-to-max spread: a 13% spread is 6.5% unbalance. Identical A-mid, B-low, C-high readings on ten different motors mean the asymmetry is upstream of the machines, so measure voltage unbalance and negative sequence at the motor terminals and current sharing in the parallel feeder sets, not ten motor circuits.

    Power quality and harmonics