Current IntelPower LibraryShop main store

Troubleshooting

Why power factor capacitors don't fix motor starting sag

Power quality and harmonics Published 9 min read

Short answer

No — panel power factor capacitors will not fix motor-start dimming. They cancel steady-state reactive current; the dim is a locked-rotor surge several times full-load through the source and feeder impedance for about a second. Cut the impedance or cut the starting current: fix the feeder, strengthen the supply, or soft-start with a VFD or starter where three phase allows.

On this page
  1. What is actually pulling the voltage down
  2. What a power factor capacitor can and cannot cancel
  3. Capture the start before you buy anything
  4. Worked example: the same start, with and without the bank
  5. Fixes that actually move the dip
  6. The decision, case by case
  7. Questions asked

No. Power factor correction capacitors at the main panel will not fix the dimming when a motor starts. A correction bank cancels steady-state reactive current, and a start is not steady state: the dim is locked-rotor current, roughly five times full-load, pushed through the impedance of the service, transformer and feeder for the second or so the motor needs to reach speed, and every load downstream of that shared impedance dips with it. Sized the ordinary way, a bank moves that dip by about one percentage point. What moves it is less impedance or less starting current: larger or shorter feeder conductors, tight terminations, a stronger service, or a soft starter or VFD on the machines that have three phase. The worked example below puts numbers on a typical 7.5 hp single-phase start, with and without the bank.

What is actually pulling the voltage down #

During a start a motor behaves for a second or so like a stalled load, and the current it draws is set by its locked-rotor rating, not its full-load rating. The example used through this article: a 7.5 hp single-phase motor with a 40 A full-load nameplate and a 209 A locked-rotor marking, illustrative but typical of the class. The surge is 5.2 times full-load and checks out against the NEMA MG-1 code letters: 209 A × 230 V = 48.1 kVA, and 48.1 kVA ÷ 7.5 hp = 6.4 kVA/hp, inside code letter H at 6.3–7.09 kVA/hp. Every ohm between the utility and the motor terminals — transformer winding, service drop, feeder conductors, every lug — carries that surge, and the voltage dropped across those ohms is exactly the dip the lights and the computer see.

NFPA 70, the National Electrical Code, 2023 edition, does not stop this. Article 430 sets motor branch-circuit ampacity at no less than 125% of full-load current — an ampacity rule with no starting-drop test — and the informational notes in Articles 210 and 215 recommend holding running drop to 3% on a branch and 5% total; those are recommendations, not enforceable limits, so confirm the enforceable requirements with your authority having jurisdiction and the equipment documentation. The working floor for the start itself is a common design check rather than a code number: keep terminal voltage above about 80% of nominal while accelerating, because below that contactor coils, relays and electronics begin to drop out. Verify the exact dropout ratings against your own contactor and control documentation.

What a power factor capacitor can and cannot cancel #

At steady state a correction bank does real work. It supplies the reactive current a running motor keeps drawing to magnetize itself, so the line supplies less of it, running current falls, and running voltage drop improves a little. That job is worth doing when measurements show a low running power factor; the sizing rules, including the ceiling on correcting a motor at its own terminals relative to its full-load current, are laid out in correcting power factor on a motor with low measured PF.

A start defeats that mechanism three ways. Magnitude: an induction machine's power factor during lock sits near 0.2–0.3, so the surge is mostly vars, and a bank sized to the running load supplies a rounding error of them. Duration: the surge lasts about a second, and a bank sized for it would sit as overcorrecting dead weight between starts. Physics: the capacitor already inside a capacitor-start single-phase motor is not correction — it sits in series with the start winding to shift phase for torque and disconnects once the motor is at speed.

Cancelling the surge's vars outright would take a bank sized to the starting reactive — roughly twenty-three times the running bank in this example — switched in at start and out at speed, which is special apparatus used on large motors, not panel correction hardware. The running-sized bank is what actually gets installed, and it moves a start dip by about one percentage point, as the worked example shows.

Capture the start before you buy anything #

De-energize, lock out and verify absence of voltage with a proven tester before you open the panel, the motor terminal box or any enclosure. The start capture itself is done from outside with covers on, using instruments rated for the installation's measurement category per the instrument documentation. If anything must be done inside energized, NFPA 70E, 2024 edition, governs the hazard assessment, protective equipment and permit; confirm the details with your authority having jurisdiction and the equipment documentation. An averaging clamp underreports a locked-rotor surge — use one with a true inrush capture, and a meter with min/max RMS for the dip.

  1. Record the motor nameplate: full-load current, locked-rotor amps or code letter, voltage, phase. Confirm the supply matches the nameplate.
  2. Log the pre-start voltage at the motor terminals and at the main panel, motor off.
  3. Start the motor and capture both points with min/max RMS, plus the acceleration time. Clamp one motor conductor with the inrush clamp for the surge magnitude.
  4. Split the dip. Whatever the panel loses is the upstream share — transformer, service drop, utility. Whatever extra the motor terminals lose is your feeder and branch. The arithmetic that turns those dips into impedances is the same one walked through in estimating voltage sag from motor inrush current.
  5. De-energize and verify again, then pull and re-torque the accessible terminations: feeder lugs, breaker connections, motor leads and the grounded conductor. A loose lug is added impedance that shows up exactly as a start dip, and a bad neutral on a 120/240 V split makes some circuits sag while others flare bright.

Read the shares against each other. If the panel itself dips more than about 5% during a start, the upstream share dominates and the utility owns it: ask them to verify the transformer size and secondary connections against your starting duty. If the panel holds near steady while the motor terminals plunge, the feeder and branch are yours, and the fixes below apply.

Worked example: the same start, with and without the bank #

Inputs, all illustrative so you can substitute your own: the 7.5 hp single-phase motor above, 40 A full-load, 209 A locked-rotor; a 25 kVA single-phase transformer, 230 V secondary, 4% impedance (an example value — read the nameplate); 200 ft of feeder one way in #6 copper; locked-rotor power factor 0.30, the top of the usual band.

Transformer: rated secondary current = 25,000 VA ÷ 230 V = 108.7 A. Available fault current ≈ 108.7 A ÷ 0.04 = 2,717 A. The transformer-limited share of the dip ≈ 209 A ÷ 2,717 A = 7.7%.

Feeder: #6 copper is 0.491 Ω per 1,000 ft of DC resistance at 75 °C (NFPA 70, Chapter 9, Table 8). For 200 ft out and back on a 240 V circuit: R = 0.491 × 0.400 = 0.196 Ω. Drop = 209 A × 0.196 Ω = 41 V, which is 17.8% of nominal.

Total dip ≈ 7.7% + 17.8% = 25.5%, so the motor terminal sits near 171 V (230 × 0.745) while it accelerates. The panel and the lights ride the transformer share alone, roughly 8% — plainly visible dimming — and the computer at the panel rides it with them.

Now the bank, sized the ordinary way at about 2 kvar for this motor's running power factor: 2,000 var ÷ 230 V = 8.7 A of cancellation. At 0.30 power factor the surge splits into 62.7 A real and 199.4 A reactive; cancel 8.7 A of the reactive part and the line current falls to √(62.7² + 190.7²) ≈ 201 A. Best case, with the bank at the motor terminals: feeder drop 201 A × 0.196 Ω ≈ 39 V, or 17.0%; transformer share 201 A ÷ 2,717 A = 7.4%; total ≈ 24.5%. With the bank at the panel instead, the feeder still carries the whole surge and the total is about 25.2%. One percentage point, either place.

To cancel the vars outright: the surge's apparent power is the 48.1 kVA from the code-letter check; real part 0.30 × 48.1 = 14.4 kW; reactive part √(48.1² − 14.4²) ≈ 46 kvar. That is twenty-three times the 2 kvar bank, and it would have to switch with the start.

These are estimates built on impedance magnitudes, an assumed transformer impedance and no feeder reactance, which is negligible at #6. Treat the result as an estimate to be checked against the governing code and the equipment documentation — and against your own measurements.

Fixes that actually move the dip #

Ordered by payoff against cost, using the example's numbers:

  1. Repair and enlarge the path. Re-torqued lugs and clean terminations cost almost nothing and remove impedance added by accident. Then conductor: on #2 copper, 0.194 Ω per 1,000 ft from the same table, the feeder share falls to the surge × 0.0776 Ω = 16 V, about 7%, and the whole start dip drops from about 25% to about 15% — still a visible dim, but a desktop computer usually stops complaining below that.
  2. Cut the starting current on every three-phase machine. A soft starter applies reduced voltage through acceleration with its current limit set to the driven load; a VFD accelerates the motor at roughly rated current instead of a locked-rotor multiple and lets you tune the ramp. Either turns a five-times surge into a start near rated current on that machine.
  3. Convert the single-phase offender. For a 7.5 hp single-phase motor there is no cheap electronic fix — a single-phase soft starter will not carry a heavy single-phase start, as why a single-phase soft starter can't fix a heavy fan start explains — so the practical cure is a three-phase motor on the same shaft, driven by a VFD fed from the single-phase line. Sizing a VFD for a three-phase motor on single-phase input covers the derating that input demands. The five-times surge becomes roughly rated current, and the dimming goes with it.
  4. Feed the problem upstream when the panel share dominates. If the dip measured at the main panel is the larger share, copper inside the shop cannot reach it: the utility owns the transformer and service drop, and a request to verify transformer size against your starting duty is the correct move. A larger transformer lowers the shared impedance for every load on the service.

None of these is a capacitor.

The decision, case by case #

  • Capacitors sized for running power factor: install them only when a measured running power factor calls for it. For the start they are a rounding error.
  • Panel dips more than about 5% on a start: upstream-dominated. Ask the utility to check the transformer and service first; conductor work comes after that share is fixed.
  • Panel steady, motor terminals plunge: your feeder. Re-torque, then upsize or shorten until the start dip clears the 80% floor with margin.
  • Three-phase machines: soft starter or VFD, current limit or ramp set to the load.
  • The single-phase workhorse: feeder fixes first; if the dip is still too deep, re-motor with a three-phase motor and a VFD sized for single-phase input.

Questions asked

Why does the computer freeze when it is on a different panel from the motor?

Both panels sit downstream of the same service drop and transformer, so both see the dip those impedances create. Panel separation only isolates faults created inside the panels, not a dip born upstream of both. Either fix the shared impedance or give the computer ride-through: an uninterruptible power supply sized by its manufacturer's sizing method holds a desktop through a one-second sag that a plain surge strip cannot.

How big a capacitor bank would it take to cancel a motor start?

Cancelling the full starting reactive demand of the example start takes roughly 46 kvar, switched in at the moment of start and out at speed — more than twenty times a normal running-power-factor bank. A bank that large, left connected between starts, drives a small service leading, raises voltage and stresses other loads. Switched starting-capacitor banks exist as special apparatus for large motors; panel correction hardware is the running-sized kind.

Does the sag itself damage the motor?

Low voltage during a start cuts an induction motor's torque roughly with the square of the voltage, so a deep dip slows acceleration and the rotor spends longer at high current. One hard start is routine duty; repeated deep-dip starts overheat the rotor and stator and shorten insulation life. If the dip exceeds about twenty percent at the motor terminals, treat the start as a fault condition to fix, not a nuisance.

The lights recover the moment the motor reaches speed — is the wiring at fault?

Usually not a fault: the dimming tracks the locked-rotor current, which ends as the rotor reaches speed in a second or two, so recovery at speed is the expected signature of a starting sag. A dip that persists after the motor is up to speed points to different causes: loose terminations, an undersized conductor running hot, or a genuine supply problem; measure voltage at the panel while the motor runs to separate them.

Keep reading

  • Troubleshooting

    Why a 4.16 kV motor start dips a 120 V branch to 109 V

    The one-second dip to 109 V on the branch is the medium-voltage motor's starting current flowing through impedance shared with that branch: about 8 V, or 6.8%, well inside the 15% starting-drop practice but low enough to trip one sensitive device. Capture the dip at the load, fix it at the motor start or at the device, and leave the utility tap alone - raising the bus to 4368 V only lifts the floor to about 114 V without removing the dip.

    Power quality and harmonics

  • Troubleshooting

    Why a capacitor bank limits current in a UV lamp ballast circuit

    The capacitor bank in series with the lamp is a current-limiting ballast reactance, not a filter. The lamp voltage across CL–L is lower than the transformer's roughly 900–1000 V secondary because the bank drops the difference, and an instant 1CB trip points to a lamp-side ground fault through the grounded secondary reference, not to a supply fault.

    Power quality and harmonics

  • How-to

    Correcting power factor on a motor with low measured PF

    The nameplate full-load current already contains the motor's power factor and efficiency, so a measured 0.56 does not raise the 195 A limit — only a stamped service factor does. Correcting 0.56 to a 0.95 target needs about 1.15 kvar per measured kilowatt and cuts supply line current to about 59% of what it was.

    Power quality and harmonics