Generator swing and voltage control in motor start studies
Short answer
Your motor start study shows a flat, sagging voltage because that study type does not calculate exciter and governor response — no generator setting will add it. Keep one generator as the swing source for the power-flow solution, run the start as a transient stability study initialized from the load flow, and trend motor-terminal voltage separately from the generator bus, because the soft starter pulls the motor terminals down even as the bus recovers.

On this page
- Why doesn't your motor start study show the voltage recovering?
- What does the swing setting actually do in the solution?
- Can a generator be swing and voltage control at the same time?
- Which study type models the exciter and governor?
- How do you set up the motor start as a transient stability run?
- How much current does a 5000 hp motor pull on a 350 percent current limit?
- Why does the motor terminal voltage stay down while the generator bus recovers?
- What do you change before the next study run?
- Questions asked
The flat sag in your motor start study is the study type talking, not the generator settings. The acceleration calculation you ran solves the machines' dynamics with their excitation left out, so no swing or voltage-control flag can put regulator-driven recovery on that plot — the trace is correct for the model set, and it reads like a start against a stiff utility feed. Keep one machine flagged swing, because the solver needs a source to close the power balance, and run the start event as a transient stability study initialized from the load flow, where the machines are dynamic from the first instant. Then trend two voltages separately: the generator bus, which the regulators pull back up, and the motor terminals, which the soft starter holds down by design while it limits current.
Why doesn't your motor start study show the voltage recovering? #
Because the acceleration study you are running does not calculate exciter and governor response, there is no automatic voltage regulator in the model to drive field current up when the voltage sags — the trace falls and holds, exactly as a start against a stiff utility source would.
The calculation behind that study type solves the motor's electromechanical behavior: torque accelerates the rotor, slip sets the current, and the network answers through its impedances. The sources sit in the case as fixed voltage behind impedance, with nothing that measures terminal voltage or moves excitation. A source that cannot change its own field cannot recover, so the flat line your plot returned is the correct output for the model set, not a defect in the generator dialog. Read the modeled-component list for each study type in your software's documentation: the exciter, AVR and governor equations are documented with the stability toolset, and their absence from the acceleration module is exactly what caps your curve.
What does the swing setting actually do in the solution? #
The swing source is the solver's balancing account: it supplies whatever real and reactive power the rest of the modeled network fails to provide, so the load-flow solution closes — it is bookkeeping, not a claim that one machine regulates the plant.
A power-flow iteration must balance real and reactive power exactly, and something has to absorb the leftover left by loads, losses and every other source in the case; the swing bus does that by holding a fixed voltage magnitude and angle. Your twelve identical machines share kW and kVAR in the real plant, and nothing in the operating scheme names a balancer — that changes nothing for the solver, which still needs the slot. Assign one machine, the largest on the bus being a common convention, and read its calculated output as the remainder the model required rather than as that engine's duty. In the acceleration study the balance is struck once, at the solved operating point, and it never runs in time, which is why the swing flag cannot lift a sagging trace.
Can a generator be swing and voltage control at the same time? #
No — a bus carries one generation role in the power-flow solution, so a machine set to swing cannot also hold a voltage-control setpoint, and no combination of the two flags will synthesize a time-domain excitation response.
The two roles answer different questions with different solved quantities. Swing fixes the bus voltage magnitude and angle and absorbs the power mismatch; voltage control holds a voltage target and lets real power float. Swap the flags and you swap which quantity is imposed and which is solved — which is why, under voltage control, your machine's kW output stopped tracking the load: real power had become a solved result instead of a balance obligation. Neither flag integrates anything in time, so neither can behave like a regulator, which measures terminal voltage continuously and drives the field through the transient. Stop iterating between the two settings; they decide how the solution closes, and your question is how the machines respond.
Which study type models the exciter and governor? #
The transient stability study is the calculation that integrates the machine, exciter/AVR and governor equations through time, and it is where the recovery you see in the field will finally appear on the plot.
Stability toolsets document dynamic machine models together with their excitation and prime-mover controls, and some packages add a generator start-up analysis that simulates the whole start sequence, automatic controls included. Motors already spinning on the bus can be carried as dynamic machines too, which matters when one large unit is running while its twin starts. Confirm the split in your own software's documentation before the run: check which study carries the exciter and governor models and which study your start event is assigned to today.
| Study type | What the solver carries | What the voltage trace can show |
|---|---|---|
| Dynamic motor start | Acceleration against a source network held static | The sag set by network impedance, then nothing |
| Transient stability, initialized from load flow | Machine, exciter/AVR and governor equations in time | The sag plus the regulator-driven recovery |
| Generator start-up analysis | The start sequence with exciter, governor and prime-mover dynamics | Voltage and frequency through the whole sequence |
How do you set up the motor start as a transient stability run? #
Build and solve the pre-start load flow first, then initialize the stability run from that solved operating point so every machine begins at a consistent voltage, angle and flux at time zero.
- Build the running case: all twelve machines at their dispatch, the step-up transformers, the already-running motor at its load, and the plant auxiliaries as they stand before the start.
- Solve that load flow and clear every topology, transformer-data and dispatch warning first — the stability run inherits these initial conditions wholesale.
- Attach the exciter/AVR and governor models to each machine and enter the manufacturer's dynamic data; a machine without them cannot recover in any study type.
- Initialize the transient run from the solved load flow; from the first instant after initialization the machines are dynamic.
- Switch the starter in shortly after the trace begins so the pre-start level stays visible, then plot generator-bus voltage, motor-terminal voltage, motor current and each machine's kW and kVAR output.
The swing assignment still does its job inside the initializing load flow. After that, the dynamic models — not the flag — carry the response you were trying to reach by toggling modes.
How much current does a 5000 hp motor pull on a 350 percent current limit? #
With the example inputs below — 5000 hp, 4160 V three-phase, 95 percent efficiency, 0.85 power factor — full-load current computes to about 641 A, and the 350 percent limit holds the inrush near 2244 A.
- Motor input power: 5000 hp × 746 W/hp = 3,730,000 W
- Apparent power drawn: 3,730,000 W ÷ (0.95 × 0.85) ≈ 4,619,000 VA
- Full-load current: 4,619,000 VA ÷ (1.732 × 4160 V) ≈ 641 A
- Held starting current: 3.5 × 641 A = 2243.5 A, call it 2244 A
- Bus demand at rated voltage: 1.732 × 4160 V × 2243.5 A ≈ 16,165,000 VA, about 16.2 MVA
Set that against the transformers: 16.2 MVA ÷ 2.5 MVA apiece ≈ 6.5, so the start alone demands the rating of roughly six and a half of those step-up transformers, with its twin already loaded on top of them.
The efficiency and power factor are example inputs; NFPA 70, the National Electrical Code, 2023 edition, Table 430.250 ends its full-load current listings at 500 hp, so a machine this size takes its working current from the nameplate and the manufacturer's data sheet — treat the 641 A as an estimate until it matches, and confirm final sizing values with the authority having jurisdiction. The 16.2 MVA demand also assumes the bus holds essentially rated voltage, and each percent of sag trims it proportionally. The ramp itself is your choice: the 250–350 percent band is a case input balanced against motor heating, which setting a soft starter current limit without overheating the motor works through in detail.
Why does the motor terminal voltage stay down while the generator bus recovers? #
Because the soft starter makes its current limit by cutting the voltage applied to the motor, the motor terminals are held down by design even after the regulators have pulled the generator bus back to essentially rated voltage.
Between the generator terminals and the motor terminals sit the step-up transformers, the medium-voltage bus and the starter's phase-control elements; each adds impedance, and the starter deliberately adds voltage drop to hold current at its limit. A recovery at the 480 V generator terminals therefore says nothing about the voltage at the motor — the same decoupling that explains why a soft starter barely improves the utility bus voltage dip. Trend both curves and judge them separately: bus voltage against the plant's dip criteria, motor-terminal voltage against the machine's ability to make torque, which falls with the square of the voltage at its terminals.
If the terminal voltage sits too low for too long at the limit, the machine can bog down before it is ever across the line — the failure mode described in why a large motor stalls when the soft starter hits current limit. A good report carries both curves and never merges them into a single all-purpose voltage line.
What do you change before the next study run? #
Leave one generator flagged swing for the load-flow balance, move the start event into a transient stability study initialized from that load flow, enter the manufacturer's exciter and governor data, and plot the motor-terminal and generator-bus voltages as separate curves.
The model set, not the flag, decides what a trace is allowed to show, so label every curve you hand anyone with the study type that produced it. The flat trace from the acceleration study remains a valid result — it reads as a start against an unregulated source — while the stability run represents what the plant actually does. Start the generator dynamic data moving first, because exciter and governor parameters are the long-lead item and every recovery curve downstream depends on them. When someone asks why the study disagreed with the switchyard, the answer is one sentence: different calculations, different model sets, and two voltages that only look like one.
Questions asked
What generator data do the exciter and governor models need?
The machine reactances and the inertia constant from the generator data sheet, plus the exciter/AVR and governor model types and their settings from the voltage-regulator and governor documentation or the OEM dynamic data sheet. If the plant never received that package, request it from the generator packager: the stability run is only as good as those inputs, and a guessed exciter produces a confidently wrong recovery curve.
How long should the simulation run to capture the full recovery?
Run until both curves are flat rather than to a preset clock: motor speed settled and generator terminal voltage back at its setpoint. If the exciter data includes a slow field, or the starting load is large, extend the end time. A trace stopped early reads as a deeper and longer dip than the machine actually produces, which is the wrong side to err on in a report.
Is it acceptable to sketch the expected recovery onto the study plot by hand?
No. A hand-drawn curve is an expectation, not a calculation, and it does not belong on a study plot or in a report. If the acceleration study cannot model the regulators, keep its calculated trace, label it as a result without exciter response, and attach the stability run as soon as the dynamic data is in hand.
Which voltage number decides whether the motor will actually accelerate?
The motor-terminal voltage during acceleration, because torque tracks the square of applied voltage: at 80 percent voltage an induction machine delivers roughly 64 percent of its rated-voltage torque. Judge that against the load's torque-speed demand across the whole acceleration, and read it from the motor manufacturer's torque curves rather than from one number at one voltage.