Troubleshooting
Why a capacitor in a motor terminal box must come off before a VFD
Short answer
Disconnect any capacitor found in a three-phase motor's terminal box before running it on a VFD: every PWM edge pulls a charging spike through it, which heats the drive output stage and trips overcurrent. Then bridge the terminal box in delta so each winding sees its rated voltage; a wye connection cuts winding voltage by √3 and torque to about a third.

On this page
The capacitor-looking part bolted inside a three-phase motor's terminal box — a metal can or plastic body with a threaded stud, wired across two winding terminals — comes off before you connect a VFD. The drive makes its own phase displacement, so the part has no job left, and on a drive output it turns every PWM edge into a charging spike through the inverter stage: heat, distorted phase currents and nuisance overcurrent trips. Then bridge the terminal box to match the nameplate voltage; for a low-voltage delta rating that means three links and the drive outputs landed on the link points.
Why the part has no job on a drive #
A run or start capacitor exists to push a phase-shifted current into an auxiliary winding when a motor is fed from a single-phase supply. A VFD synthesizes all three phases itself by switching the DC bus with PWM, so no phase shift is needed and there is no auxiliary winding to feed. On a motor with three winding pairs, a two-lead component in the terminal box is almost always left over from an earlier single-phase application — common on repurposed machines — and it stays a capacitive load on the output no matter how the bridges are set.
The threaded stud is a mounting point, not a terminal to earth. The part's working leads sit across winding terminals, so tying the stud to the frame does not neutralize it; it can only short a live node to ground.
What each PWM edge does to it #
Capacitor current follows I = C × dV/dt. Take an illustrative example: a 10 µF part on a drive output swinging the DC bus behind a 230 V output — that bus is roughly 325 V, from 230 × √2 — with a 0.5 µs output edge (your drive's rise time is in its manual):
- dV/dt = 325 V ÷ 0.5 µs = 650 V/µs
- I = C × dV/dt = 10 µF × 650 V/µs = 6,500 A
Cable inductance and the drive's output impedance keep the real peak well below that ideal figure, but it still lands far above the drive's rated output current, and it repeats at every switching event — thousands of times a second at a carrier frequency of a few kilohertz. That is the load behind nuisance overcurrent trips during acceleration; if the trip appears the instant the shaft moves, the pattern matches why a VFD trips overcurrent the instant the motor moves.
Fixes that look right and are not #
- Grounding the stud: the working leads sit across winding terminals, so earth does nothing to the part and can short a live node.
- Re-bridging wye or delta with the part still connected: the connection sets winding voltage, not the capacitive load on the output.
- Raising the carrier frequency or adding output filtering: neither removes a capacitor that is in the circuit in the wrong place by design.
Delta or wye: read the nameplate #
The decision rule is that each winding must see its rated voltage. The nameplate, or the connection marks printed beside the voltage values, settles it:
| Input | What it decides | Where to read it |
|---|---|---|
| Rated voltage per connection (for example 230 V against delta) | Delta or wye bridges | Motor nameplate and marks beside the symbols |
| Drive output voltage | Must match the chosen motor rating | Drive nameplate and manual |
| Rated current per connection | Drive sizing and overload setting | Motor nameplate, delta line |
If the nameplate lists the low voltage against the delta symbol and the drive outputs that voltage, wire delta. In wye on the same supply, each winding sees the line voltage divided by √3: for a delta-rated winding that is about 133 V instead of the rated value. Flux falls with the voltage and torque roughly with its square — (133 ÷ 230)² ≈ 0.33 — so the motor delivers about a third of rated torque and runs hot under load. That is a performance fault rather than a hazard, but it is still the wrong connection.
Removing the part and bridging for delta #
- De-energize, lock out and verify absence of voltage at the terminal box before opening it; NFPA 70E, 2024 edition requires de-energizing and verifying before this kind of work, and you confirm the details with your authority having jurisdiction and the equipment documentation.
- Trace the component's two leads to the terminal block and disconnect both; insulate or remove them. Leave the stud unconnected — not to earth.
- Bridge delta with three links: U1 to W2, V1 to U2, W1 to V2. The three link points form the corners of the triangle.
- Land the three drive outputs on the three link points and the protective earth conductor on the motor's earth terminal.
- Enter the nameplate voltage, current, frequency and speed into the drive's motor data settings, exactly as the drive manual specifies for your model.
- Apply power at a low output frequency first and confirm rotation; swap any two output leads to reverse it.
Checks after the first run #
- Clamp all three output currents: they should be balanced and at or below the nameplate current. Unequal readings point to a wrong bridge or an open winding.
- Check frame temperature after a sustained run. A rise well above expectation suggests a wrong connection or an unintended capacitive path still in circuit.
- Confirm the drive holds through acceleration without an overcurrent trip.
- If the motor came out of storage, test insulation resistance before energizing; the megger and winding checks a stored motor needs before a VFD cover the readings and test voltages.
In the reported case, disconnecting the leftover part and bridging delta left the motor running cleanly on the drive, with no trips and balanced phase currents.
Questions asked
How do I know if the part in a three-phase motor's terminal box is a capacitor I must remove before using a VFD?
Look for a metal-can or plastic-bodied component with exactly two leads landing on the winding terminal block, often fixed by a threaded stud. If the motor has three winding pairs (U1/U2, V1/V2, W1/W2) and a drive will feed it, that part is a leftover from single-phase use and comes out. Trace its leads to the block before disconnecting anything.
What actually happens if the capacitor stays connected on a drive output?
Every PWM edge charges it. With an example 10 µF part and a 0.5 µs output edge off a 325 V bus, the idealized spike works out near 6,500 A; cable inductance limits the real peak, but it stays far above the drive's rated output current and repeats thousands of times a second. Expect heating, distorted phase currents and nuisance overcurrent trips.
Should the motor be bridged in delta or wye, and why?
Read the nameplate. When the low voltage is listed against the delta symbol and the drive outputs that same voltage, bridge delta. In wye on the same supply each winding sees the line voltage divided by √3, so a delta-rated winding gets about 133 V instead of its rated voltage; flux and torque fall with it, giving roughly a third of rated torque.
The motor has no wiring diagram at all. What then?
Do not guess. Measure winding resistance between the three lead pairs first: unequal readings point to a fault or misidentified leads. If the nameplate is unreadable, resistances are unequal, or the drive still trips with the extra component removed and delta bridged correctly, contact the motor manufacturer's official support with the nameplate data and the drive's fault code.

