Current IntelPower LibraryShop main store

Troubleshooting

Why a motor loses speed during a voltage dip

Motors and motor starters Published 8 min read By Current Intel engineering team

Short answer

A dip that leaves 90% of rated voltage at the motor cuts an induction motor's torque capability to 81% of its pre-dip value, because torque varies with the square of voltage. A motor running above that reduced peak slips into a stall that persists at full voltage and draws about twice normal current. The cold-versus-hot test and the torque-curve overlay decide the cause.

On this page
  1. Torque falls with the square of the terminal voltage
  2. Why speed and current stay high after the voltage returns
  3. The measurements that decide between the causes
  4. Worked example: a 10% dip on a 3.3 kV, 900 kW fan motor
  5. Checking a double-cage rotor, cold and hot
  6. The decision for each case
  7. Questions asked

A voltage dip should not stop a motor that started fine hours earlier, yet it stops motors that run close to their breakdown torque. An induction motor's torque at a given slip falls with the square of the voltage at its terminals, so a dip that leaves 90% of rated voltage at the motor leaves roughly a fifth less torque, and a fan that was already demanding 90% of the motor's breakdown torque now beats everything the motor can produce. The motor decelerates into high slip, draws about twice its normal current, and stays there even after the bus recovers, because the fan curve still crosses the recovered torque curve only at that low speed. The two checks that decide the cause are a cold-versus-hot comparison and an overlay of the motor torque-speed curve on the fan curve with the dampers in their running position.

Torque falls with the square of the terminal voltage #

At a fixed supply frequency, torque at any slip scales with the square of terminal voltage. At 95% of rated voltage the capability is 0.95 × 0.95 = 0.9025, about 9.75% less torque; at 90% of rated it is 0.90 × 0.90 = 0.81, about 19% less. The square law is an approximation for the usual operating range, but it tracks how the whole torque-speed curve shrinks during a dip, and near breakdown torque, which is the region that decides this fault, it is close enough to size the margin with.

Current does not follow the square law. A fan whose speed has barely moved needs barely less shaft power, and balanced three-phase input power is the square root of 3 times line voltage times line current times power factor. Holding power and power factor constant, a dip to 90% voltage raises current by a factor of 1/0.90 = 1.111, about 11.1%: the same high-slip physics that explains why an induction motor draws heavy current at starting, but far less than the rise being reported. When measured current does double, slip has run far past nameplate toward the breakdown region, and stator copper loss, which rises with current squared, reaches roughly four times normal. That is the winding temperature rise in the reported case.

Why speed and current stay high after the voltage returns #

Restored bus voltage does not restore the operating point. Below the breakdown peak, torque falls as slip grows, so once a dip pushes the motor past the peak, more slip means less torque, the opposite of recovery, and the motor settles at a high-slip point or stalls. Full voltage shifts the whole curve back up, but if the fan curve still intersects the motor curve only at low speed, the motor stays there and the current stays high because slip is high.

Reacceleration is the same physics as a start: net accelerating torque against the load, integrated through the train's inertia, until the motor crosses the breakdown peak back into the low-slip region. The motor starting time calculation of torque margin and inertia is the tool for sizing whether that crossing can happen. The reason the same motor started fine in the first place is damper position: during the original start the fan's inlet and outlet dampers were closed, so the fan added almost no aerodynamic torque and the motor only accelerated inertia. During a dip in normal running the dampers are open, the fan demands its full running torque, and the margin that carried an unloaded start does not exist. Pinching a damper during a dip is the field test for this: if the motor picks up speed, the problem is margin, not the rotor.

One caution before blaming the machine: record the voltage at the motor terminals, all three phases, through the event. An upstream indication can show recovery while the motor still sees low or unbalanced voltage.

The measurements that decide between the causes #

Work through this list in order; the first two items usually settle it.

  • Record motor terminal voltage, all three phases, across the whole event, to confirm the dip ended and stayed balanced. Persistent or unbalanced terminal voltage is a supply problem, not a motor one.
  • Measure shaft speed and compute slip as s = (ns − nr)/ns with both speeds in the same units, then compare with nameplate slip. Slip parked at several times nameplate, steady on cold and hot runs, points to torque margin; slip that worsens with temperature points to the rotor cage.
  • Log damper positions during the original start versus during running, and plot the fan's running torque demand against the manufacturer's motor torque-speed curve.
  • Run the machine cold and again hot through the same dip, comparing speed loss and whether recovery follows cool-down.
  • Capture a current spectrum under load and look for slip sidebands around the supply frequency.
  • Verify stator condition only if the phases behave differently, since interturn faults also raise current and temperature. Winding tests had already cleared the stator in the reported case.

Worked example: a 10% dip on a 3.3 kV, 900 kW fan motor #

The inputs:

  • Motor: 3.3 kV, 900 kW, 3000 rpm (the two-pole synchronous speed at 50 Hz; read the actual rated shaft speed from the nameplate), across-the-line, driving a centrifugal fan. These are the reported machine's nameplate values.
  • Dip depth: 10% of rated, terminal voltage at 0.90 of rated (the reported event).
  • Running point: 90% of breakdown torque, an assumed example value for a motor with little margin; get the real margin from the manufacturer's curve and the measured running current.
  • Fan demand during the dip: held at 90% of breakdown torque, because fan torque varies with speed squared and the speed has not yet fallen far.

The rule: during the dip the entire torque curve, breakdown peak included, scales with the square of the voltage ratio, 0.90 × 0.90 = 0.81.

The arithmetic: the dip-limited peak torque is 0.81 of breakdown; the fan still demands 0.90 of breakdown; the deficit is 0.90 − 0.81 = 0.09 of breakdown torque even at the peak, and larger at the original operating slip. The current check agrees: a healthy motor would rise by 1/0.90 = 1.111, about 11.1%, not the reported doubling, so the extra current is slip, not load power.

The result: with the running point above 0.81 of breakdown torque, a dip to 90% voltage leaves no stable operating point near rated speed. The motor decelerates past the peak into high slip and stays there after the voltage returns.

The decision: riding through this dip requires the running torque to sit below the dip-limited peak, the square of the voltage ratio times breakdown torque. A dip to 95% voltage sets that ceiling at 90.25% of breakdown, so the margin between the two cases is thin, which is why these machines sit one motor start away from a stall. Where the running point sits above the ceiling, fix it by reducing fan load, specifying a replacement with higher breakdown torque, or shedding the fan before re-energizing after a dip.

Checking a double-cage rotor, cold and hot #

De-energize, lock out and test for absence of voltage at the motor terminals before opening the terminal box or touching the rotor, and stop any test run when current, temperature or duration reaches the machine's limit.

A double-cage rotor carries two cage circuits per bar, one sized for starting torque and one for efficient running, and a broken bar or a bad bar-to-end-ring joint redistributes rotor current and cuts the torque the cage can deliver. Thermal expansion can open a marginal joint, so a motor that starts fine cold can fail to reaccelerate hot, and recovery that follows cool-down condemns the cage. That cold-versus-hot logic is the same one used in diagnosing a thermally sensitive rotor fault on other machine types, and the comparison method carries over directly.

No appreciable vibration and no current oscillation weaken the case for a cage fault, but they do not close it: broken bars clustered under the same magnetic pole produce the strongest modulation, while scattered or early breaks can modulate very little. The non-invasive test is motor current signature analysis: run the motor loaded, capture one phase current at fine frequency resolution, and look for the pole-pass sidebands at the supply frequency plus and minus twice the slip frequency. On this two-pole, 50 Hz machine at an example slip of 5%, the sideband spacing is 2 × 0.05 × 50 = 5 Hz, placing components at 45 Hz and 55 Hz. Use the slip from the measured speed to place them, and compare the sideband size cold against hot; growth when hot is the cage opening with temperature. A current clamp together with vibration data under load is the cross-check. A panel-mounted current meter cannot resolve components this close to the fundamental.

The decision for each case #

  • Speed loss appears only hot and recovery follows cool-down: thermally sensitive rotor-cage defect. Take the motor out of service for cage testing and repair before a bar fails outright; each hot run through a dip heats the stator at roughly four times normal copper loss.
  • Steady high slip, the same cold and hot, dampers open in running: no torque margin. Reduce the fan load, automate damper pinching on a detected dip, or re-specify the drive for higher breakdown torque; ride-through needs the running point below the square of the voltage ratio times breakdown torque, 81% for a dip to 90% voltage.
  • Terminal voltage still low or unbalanced at the motor after the bus recovers: find and fix the supply problem upstream; the motor may be innocent.

Questions asked

Why does a motor draw more current when voltage drops?

A fan running at nearly unchanged speed needs nearly unchanged power, so at a 10% dip the current should rise only about 11%. A current that doubles means the slip has climbed far beyond nameplate, usually near or past breakdown torque, and copper loss goes with current squared, so twice the current heats the winding roughly four times as fast.

How do you test a double-cage rotor without dismantling it?

Motor current signature analysis. Run the motor loaded, capture one phase current at fine frequency resolution, and look for sidebands around the supply frequency at plus and minus twice the slip frequency, using the slip from measured speed to place them. Compare sideband size on cold and hot runs; growth when hot indicates a cage joint opening with thermal expansion.

Why did the motor start fine but fail to reaccelerate after the dip?

At the original start the fan's dampers were closed, so the motor accelerated little more than inertia. During the dip in normal running the dampers were open and the fan demanded full load torque while the dip cut available torque to the square of the voltage. If the running point sat above that reduced peak, no stable high-speed point existed and the motor stayed in high slip.

What slip indicates a stalled or nearly stalled motor?

Compare measured slip with nameplate slip. A healthy fan drive runs at roughly nameplate slip; a motor hanging below its breakdown torque runs at several times nameplate slip. On the reported two-pole machine, slip went from about 20 rpm at nameplate to 40 to 60 rpm or more. Stable slip that high, the same cold and hot, points to torque margin rather than the rotor.

Keep reading

  • How-to

    Estimating voltage sag from motor inrush current

    Do not divide the motor's asymmetrical first-cycle peak by √2; screen the dip with RMS locked-rotor current as dip % = transformer Z% × I_start ÷ I_rated. On a 750 kVA, 480 V, 6% transformer, a 50 HP motor at 395 A locked-rotor dips the bus about 2.6%, to roughly 467 V — start it across the line.

    Motors and motor starters

  • Explainer

    Why a 415 V delta motor cannot run on 240 V

    A plate that reads 415 V delta, with no second voltage-connection pair, describes single-voltage windings that need 415 V across each coil. On a 240 V supply the motor reaches about one third of rated torque in delta and about one ninth in star, so it will not serve as a full-rated rotary phase converter idler. Replace it with a motor whose plate reads 240 V delta or feed it through a step-up transformer.

    Motors and motor starters

  • Troubleshooting

    Why a large motor stalls when the soft starter hits current limit

    Log shaft speed against current at the stall. A reading near 214 rpm (one-seventh of the 1500 rpm synchronous speed) or 115 rpm (one-thirteenth), with 3-4 current-envelope teeth per second at the 1809.5 A limit, is induction-motor crawling aggravated by SCR harmonics, not a rotor fault. Raise the current limit and shorten the dwell; the paralleled transformers made it worse by stiffening the source.

    Motors and motor starters