Why a phase monitoring relay fails on a VFD output

Variable frequency drives Published 6 min read

Short answer

The relay is not faulty: it validates fixed supply conditions — sequence, over- and undervoltage — on a sinusoidal line supply, while the drive output is PWM at varying frequency and voltage. Take run status from a drive discrete output or relay contact assigned to running; if you sense current, clamp one phase with a true-RMS instrument rated for drive output, never all three together.

On this page
  1. What the relay measures versus what the drive produces
  2. Where the phase monitor belongs
  3. Why a clamp around all three phases reads zero
  4. If current sensing is still the plan
  5. The run-status signal to use
  6. Quick diagnosis checklist
  7. Questions asked

The relay is not faulty — it is connected to a waveform it was never built to measure. A three-phase monitoring relay checks supply conditions: phase sequence, phase presence, over- and undervoltage, against fixed thresholds referenced to a sinusoidal line supply. A variable frequency drive's output is a PWM waveform whose frequency and RMS voltage change with every speed command, which is why the same relay picks up on the mains and drops out on the motor side in every connection arrangement you tried. Take the ON/OFF signal from a drive discrete output or relay contact assigned to running status; if you must sense current, clamp one phase with a true-RMS instrument rated for drive output, never all three together.

What the relay measures versus what the drive produces #

Three-phase monitoring relays are supply monitors. Their documented job is to watch the incoming mains for phase failure, reversed sequence, overvoltage and undervoltage, with adjustable thresholds and a trip delay set around a nominal supply — for this example, 3 × 400 V at 50 Hz. The measurement circuit assumes sinusoidal phase-to-phase voltages at a fixed supply frequency, because that is what a mains is.

A drive output is none of those things. The inverter switches the DC bus across the motor terminals at a carrier frequency of a few kilohertz; the motor responds to the average, and the phase-to-phase RMS voltage follows the V/f pattern — roughly proportional to output frequency below base speed, rising from 0 V at standstill to full voltage at base frequency. The fundamental starts at 0 Hz and ramps with every start.

Worked example (illustrative inputs). A 400 V, 50 Hz drive in a linear V/f pattern runs at 25 Hz. Output voltage ≈ 400 V × (25 Hz ÷ 50 Hz) = 200 V. Say the relay's nominal is 3 × 400 V with the undervoltage threshold set at 80% of nominal: 400 V × 0.80 = 320 V. Since 200 V < 320 V, the relay reports permanent undervoltage and its contact never picks up. At 50 Hz the drive reaches about 400 V, but the waveform is still PWM — outside the sine-wave conditions the relay's measurement assumes — so behavior there is undefined: it may pick up at one speed and drop at another.

The decision follows from the physics: no threshold setting turns a mains monitor into a drive-output monitor. The relay is the wrong instrument in that position, in any connection arrangement.

Where the phase monitor belongs #

Move it to the line side of the drive. There it does its documented job: protecting the drive and everything downstream from supply phase loss, reversed sequence, and over- or undervoltage. On the motor side it protects nothing, because the drive itself creates and supervises that voltage. Before adding hardware, read the drive's fault table: many drives supervise their DC bus and input currents and trip a documented fault on input phase loss or a collapsed supply, which can make the external relay redundant.

Why a clamp around all three phases reads zero #

Clamping all three output conductors in one jaw reads the instantaneous sum of the three currents. For a balanced three-wire load that sum is zero at every instant — Kirchhoff's current law: the three conductors are the only paths into the motor. This has nothing to do with the PWM; the same clamp reads zero around the supply feeders of any healthy running motor.

Worked example. A motor draws 4.0 A RMS per phase, so peak current is 4.0 A × √2 = 5.66 A. At the instant phase A crosses zero, i_A = 0 A, i_B = 5.66 A × sin(−120°) = −4.90 A, and i_C = 5.66 A × sin(+120°) = +4.90 A. Sum: 0 A − 4.90 A + 4.90 A = 0.00 A, at full load, at any output frequency. Three Hall sensors summed into an op-amp, or three current transformers with their secondaries summed, cancel the same way. The only summing arrangement that senses anything is unequal passes of the conductors through a common core — for example 1, 2 and 4 turns — which breaks the balance to detect the presence of current; that is a residual-sensing trick, not a run-status signal. Clamp one conductor.

If current sensing is still the plan #

Sense one phase, with an instrument rated for drive output: true-RMS conversion and enough bandwidth that the PWM ripple does not corrupt the reading. The sensor output will carry the switching ripple, so average or filter it before any threshold circuit or analog input. For what that measurement involves, the practice in measuring VFD and soft starter current with the right meter applies directly. If the signal feeds a controller, so do the selection points in measuring three-phase motor current for a PLC alarm input: match the transducer range to the motor's nameplate current and the input the controller offers.

Know what current proves. The drive pushes magnetizing current into the motor whenever it energizes it — including with the shaft stalled — and none after a coasting stop. Current means "drive energizing the motor", not "shaft turning".

The run-status signal to use #

Use a drive discrete output — a relay contact or a transistor output — assigned to the running-status function. The assignment lives in the drive's digital-output configuration; choose the documented function for your model that is true while the drive is switching output to the motor, or a frequency-threshold function if your sequence needs "at speed" rather than "running". Plant instrumentation specifications commonly require exactly this: running-status signals come from auxiliary contacts on the motor-control equipment — the starter or the drive — not from measurements reconstructed around it.

The contact switches your control circuit; it does not supply power. Feed the coil or input from the control-power source (24 V DC is the usual choice), never from the drive's motor-output terminals, and check the contact's rated voltage and current against the load it switches.

One safety note, before any terminal is touched: isolate the drive, lock it out, verify absence of voltage, and wait out the DC-bus discharge time stated in the drive documentation.

Commission it in this order:

  1. With the drive isolated and verified de-energized, confirm which output terminals form the assignable contact and what function they carry today.
  2. Assign the running-status function to that output in the drive configuration.
  3. Wire the contact in series with the control-power source and the receiving coil or input, with suppression across an inductive load.
  4. Restore power and run the drive through start, run, and stop; measure the signal at the receiving device, not only at the drive terminals.
  5. Confirm the downstream interlock responds at the defined points, and that a drive fault drops the signal the way the sequence requires.

Quick diagnosis checklist #

  • Relay picks up on the line supply and never on the drive output: expected for a mains monitor, not a relay fault.
  • Drive running below base speed: phase-to-phase output voltage falls with frequency, below the relay's undervoltage threshold for most of the range (see the worked example above).
  • Clamp meter reads about 0 A around all three output conductors at any load: Kirchhoff's current law; move the clamp to one conductor.
  • Sequence needs proven rotation or rotation during coasting: add shaft-speed sensing; neither a drive contact nor a current switch provides it.
  • Supply-side protection is the goal: the relay belongs upstream of the drive — or it may already exist inside the drive as a documented fault function.

Questions asked

Will lowering the relay's undervoltage threshold make it work on the drive output?

No. Output voltage below base speed scales with frequency, so on a 400 V drive at 12.5 Hz the motor sees about 100 V — no single undervoltage threshold covers a voltage that travels from 0 to 400 V with every speed command. The relay also expects a sine at supply frequency; the PWM waveform is outside its documented measurement conditions, so its behavior is undefined at any speed. Keep it on the line side.

Why did the same relay work on the mains supply in the same panel?

Because the mains is exactly the input it is specified for: three sinusoidal phase-to-phase voltages at fixed nominal value, fixed frequency, fixed sequence. It picks up and stays picked up. The failure appeared only when the relay was moved to the inverter output, which tells you the relay is serviceable and the application, not the part, was wrong.

Does a drive running contact prove the shaft is turning?

No. A running contact is true while the drive is switching output to the motor. The shaft can be stalled by a jam with current still flowing, and it coasts after a stop command with the signal already off. If the sequence needs proven rotation, or rotation during coasting, add a shaft-speed sensor; neither the drive contact nor a current switch replaces it.

Can a current-operated switch be used as the run signal on a drive-fed motor?

Yes, within limits. Sense one phase only, with a true-RMS sensor rated for PWM drive output, and set its threshold above the magnetizing current the drive draws at your minimum output frequency. What you get is current flowing, which is true even with a stalled rotor. For a plain ON/OFF interlock the drive's running output is simpler and needs no threshold.

Does the drive protect itself against supply phase loss without the relay?

Many drives supervise their DC bus and input currents and trip a documented fault code on input phase loss or a collapsed supply — read your model's fault table in its documentation. If the drive does not, the monitoring relay belongs on the line side feeding it, where it sees the supply it was built to measure. It has no role on the output.

Keep reading

  • Troubleshooting

    Finding a 113 V drop between a VFD and the motor terminals

    The drop is real, it lives in the path between the drive lugs and the terminal box, and it works out to about 0.36 Ω per phase — enough to dissipate roughly 11 kW per phase if it is resistance. Verify the reading with a drive-rated meter, then find it with an infrared scan under load and a micro-ohmmeter on every joint; the motor is downstream of both measurement points and is not the cause.

    Variable frequency drives

  • Explainer

    Why a capacitor-run motor needs a special VFD

    A standard three-phase VFD will not run a single-phase capacitor motor usefully: the fixed run capacitor's reactance rises as output frequency falls, so the auxiliary winding loses its phase-shifted current and low-speed torque collapses. Use a drive documented for PSC or shaded-pole motors, or change to a three-phase motor.

    Variable frequency drives

  • Troubleshooting

    Why a drive-controlled motor runs unstably and how to trace it

    Compare three values at the same instant: the reference the controller sends, the reference the drive receives, and the actual output frequency. A fluctuating sent reference puts the fault upstream in the control path; a steady reference with hunting output points to the drive's ramp and limit settings, motor data, or the load. Check the supply and motor circuit before changing any protective setting.

    Variable frequency drives