Troubleshooting
Why a soft starter trips control voltage above 110% on a generator
Short answer
A steady 228 V on a 230 V rated control supply cannot trip the 110% fault, which needs more than 253 V held for longer than 2 s. Log the voltage directly across the control-supply input through the generator transfer: a regulator overshoot above the threshold, or a measurement taken on the wrong terminals, explains the trip.
On this page
- What does a control voltage above 110% fault mean on a 3RW44?
- Is 228 V within tolerance for a 230 V control supply?
- How can a generator transfer push the control supply past the trip point?
- Where should you measure the control supply voltage?
- How do you catch the excursion a steady reading misses?
- What fixes stop the trip once the generator carries the load?
- Does the message ever point at something other than high control voltage?
- Questions asked
A soft starter that runs clean on the utility and trips with a control-supply overvoltage message the moment the plant moves to generator power is not reacting to the steady reading you took after the transfer. On a 230 V rated control supply the trip point works out to 253 V, and the fault needs it held for longer than 2 s, so a settled reading in the low two hundreds cannot be the trigger. What remains is either a voltage excursion during the transfer that the spot check missed, or a measurement taken somewhere other than the starter's control-supply input. Log the input through the transfer and the answer falls out.
What does a control voltage above 110% fault mean on a 3RW44? #
In the manufacturer's fault table for the 3RW44 series, the supply-voltage-above-110% entry fires when the control supply voltage stays above 110% of its required rated voltage for longer than 2 s, and it names voltage peaks and a wrong control supply as the causes.
That wording settles three things. The entry evaluates the control supply, not the three-phase main circuit. The excess must persist for the full evaluation window, so a sub-cycle switching spike on its own will not latch the message. And whatever the main terminals are doing is a separate diagnostic with its own message, which matters because on this machine the two readings were being mixed together.
Is 228 V within tolerance for a 230 V control supply? #
Yes: with the +10% positive tolerance the datasheet gives the BC44 variants, the upper limit is 253 V — 230 V × 1.10 = 253.0 — and a steady 228 V sits 25 V under it, at 99.1% of the rating.
The suffix on the order number decides which tolerance applies, which is why the nameplate matters: the order number first reported for this fault, 3RW4426-1BB14, does not exist in the series, and the corrected machine reads 3RW4424-1BC44. Read that suffix off your own nameplate before applying any tolerance figure.
The arithmetic also tells you what to stop chasing. Since the message requires the input above the limit for the whole window, a value parked at 99% of the rating cannot explain the display. Either the input went higher at some point, or the message is watching a different supply than the one the meter touched.
How can a generator transfer push the control supply past the trip point? #
A generator's automatic voltage regulator overshoots when a load is stepped onto the set, and the reported generator output of 413 V is already 3.25% above a 400 V nominal before any transient is counted.
On a 400 V system the control supply is fed line-to-neutral, so the value at the input terminals is the line voltage divided by the square root of three. Here is the worked example, with its inputs stated: a 400 V nominal system, the generator regulating at 413 V line-to-line, the control supply fed line-to-neutral, and a variant carrying the +10% positive tolerance.
- Threshold: 110% of the control rating = 253.0 V.
- Settled per-phase voltage: 413 V ÷ 1.732 = 238.5 V — 14.5 V inside the limit.
- Regulator overshoot to 440 V line-to-line as the pump load steps on: 440 V ÷ 1.732 = 254.0 V — 1.0 V above the threshold.
- Duration: if the overexcited regulator takes longer than the 2 s evaluation window to pull the voltage back, the entry latches even though the input is back to 238.5 V by the time anyone puts a meter on it.
The settled 3.25% rise alone is harmless for the control input. The problem is transient overexcitation, and a large pump motor coming onto a set is the hardest load step the regulator sees — exactly the moment the transfer happens.
Where should you measure the control supply voltage? #
Measure directly across the two terminals of the starter's control-supply input, because a value quoted "in all three phases" describes the three-phase main circuit, which the fault table treats as a different monitored quantity from the auxiliary supply.
The control supply is a separate input with its own rating and its own alarms, and the family's supply-alarm documentation makes the same point: read the exact diagnostic text to identify which supply is being monitored before you chase a number. A handheld meter held on the main circuit tells you nothing about the two terminals this entry watches, and a spot reading taken after the set settles cannot show what those terminals saw during the transfer.
How do you catch the excursion a steady reading misses? #
You log the control-supply input with a meter that captures the maximum through the transfer, because a handheld spot reading taken after the generator settles can never show a transient that came and went seconds earlier.
- De-energize the panel, lock out, and test for absence of voltage before any terminal work; NFPA 70E, 2024 edition, governs that sequence in the US — confirm the practice with your local authority having jurisdiction and the equipment documentation.
- Read the complete order number from the nameplate and confirm which tolerance variant you have.
- Trace the auxiliary-supply conductors to the control-supply input terminals and mark them.
- Connect a logging meter across those two terminals with minimum and maximum capture enabled, clear the fault, and command a start on generator power.
- Read the captured maximum, the exact displayed message, and the starter's fault history, and compare the maximum against the calculated upper limit.
- If the maximum stays under the limit while the message keeps repeating, send the logs, the message text and the confirmed order number through the manufacturer's official support channel.
What fixes stop the trip once the generator carries the load? #
If the log confirms an overshoot, have the generator regulator's setpoint and transient response checked; if the log shows the input never crossed the limit while the message keeps repeating, take the logs and the exact message text to the manufacturer's support channel.
Between those two outcomes, the fixes separate cleanly:
- Overshoot confirmed. Trim the set's voltage adjustment — the reported steady output already runs 3.25% above nominal — and have the regulator's transient tuning reviewed against the pump start. Even with a soft starter limiting the current, a large motor coming onto the set is the worst step the regulator handles.
- Steady overvoltage confirmed. The input sits above the limit even when the set is settled, so the generator's voltage adjustment is the fix and the starter is only reporting it.
- Neither. Verify the control-supply input is fed at its own rated voltage from the intended source. A wrong control supply is the second cause the fault table names for this entry, and it covers a control circuit wired to an unintended voltage.
Does the message ever point at something other than high control voltage? #
It can, so read the exact diagnostic on the display and the starter's fault history before assigning a cause: this family produces several supply alarms and separate high-voltage trips with different mechanisms behind them.
The same series, for example, trips a high-voltage message at bypass switchover for reasons that have nothing to do with the generator (why a soft starter trips high voltage at bypass switchover), and a voltage change during a supply transfer can just as easily surface a phase-loss fault (fixing a soft starter phase loss fault after a voltage change). If your logged maximum stays below the calculated limit through repeated transfers while the message keeps returning, stop measuring and escalate: the logs, the exact diagnostic text and the confirmed order number from the nameplate are what the manufacturer's support channel needs.
Questions asked
What upper limit applies to a 3RW44 control supply rated 230 V?
The datasheet for the BC44 variants gives a +10% positive tolerance on the control supply rating, so the threshold works out to 253 V, and the fault fires only when that level is exceeded for longer than 2 s. Verify the tolerance on your exact order number before applying it.
Can the fault appear with the generator steady inside its regulation band?
Yes, if the input saw a sustained excursion during the transfer that a later spot check cannot show. The evaluation window is only seconds long, which is exactly the span a handheld reading taken after the set settles will miss. Log the input through the transfer instead.
How is the fault reset after the cause is corrected?
The manufacturer documents fault reset by removing the control supply voltage, longer than 1.5 s in the 3RW30/3RW40 manual, so treat a control-supply interruption as the generic reset path and follow the reset procedure in the manual for your own series.
What if the logged voltage never exceeds the limit but the message keeps coming back?
Then the message is either monitoring a different supply than the one you logged, or the measurement point is still wrong. Keep the logs, capture the exact diagnostic text and the starter's fault history, confirm the order number from the nameplate, and escalate through the manufacturer's support channel.